Troubleshooting
Soft starter motor heating prewarning at full load
Short answer
A motor heating prewarning on a soft starter feeding a pump that runs at 97–100% of nameplate current is the calculated thermal model settling at its steady-state plateau, not a fault. Set Current must match the nameplate value for the wiring, three-phase current must be logged over a full duty cycle, and the prewarning threshold should sit above the observed plateau with the trip settings left untouched.
On this page
- Why does the starter warn about motor heat build-up when the currents look normal?
- What does the motor heating value actually calculate?
- Is the Set Current right for this motor and this wiring?
- How do I log the current to prove the load is real?
- How high should the prewarning limit sit?
- When does a motor at full load need a real temperature sensor?
- What should the readings look like after the changes?
- Questions asked
A motor heating prewarning on a soft starter feeding a pump at nameplate current is the calculated thermal model settling at its steady-state plateau, not a fault in the starter or the motor. The case below is a 275 A, 460 V, 184 kW pump motor that warned after five hours of running, with 266–274 A measured on the three phases and heating displayed at 90% against a prewarning limit entered at 90%. The model did exactly what it is built to do; the settings around it need checking. Verify Set Current against the nameplate and the wiring topology, log three-phase current across a full duty cycle, then move the prewarning limit above the logged plateau and leave the trip settings untouched.
Why does the starter warn about motor heat build-up when the currents look normal? #
The warning fired because the calculated heating value reached the 90% prewarning limit you entered while the pump ran at 96.7–99.6% of nameplate current, so the model is reporting that a full-load motor sits near its trip reference rather than announcing a fault.
The nameplate reads 275 A, 460 V, delta, 184 kW, 0.88 power factor, 1788 rpm. Five hours into the run the starter showed 266 A, 274 A and 268 A on the phases with 179–180 kW at the shaft. With no temperature sensor connected there is no winding measurement, so the motor heat build-up value on the display is pure calculation, and a motor held continuously at essentially rated current converges toward the trip reference.
The equipment manual lists the setting as a prewarning limit for motor heat build-up with a factory value of 80%, below any legitimate full-load plateau, which is why a continuously full-loaded motor warns soon after commissioning rather than only on a real problem. Nothing you entered caused it either: Low current limit 18.75% and Upper current limit 150.00% belong to current monitoring, Idle time 0 s belongs to restart supervision, and Remaining time for tripping 0 s confirms no trip countdown is running.
What does the motor heating value actually calculate? #
With no temperature sensor connected the starter cannot see winding temperature at all; it computes the heating value from the current it measures, the Set Current and the tripping class, displayed as a percentage of the level at which it would trip.
At a constant load the calculation settles: heat generated in the windings balances heat rejected to the air, so the displayed value stops climbing and sits on a plateau, the same steady-state balance covered by these steady-state heat transfer calculations for industrial heating. A motor parked at 97–100% of nameplate current therefore rests close to the trip reference, which is exactly the reading behind this warning.
The tripping class scales how fast the model reacts. Class 10 is the fast IEC trip class, required to trip within 10 seconds at 7.2 times the set current, and semiconductor motor controllers such as this soft starter fall under IEC 60947-4-2, which carries the same class convention for electronic motor protection. Class 10 suits most pump loads with normal starts, but confirm it against the motor's locked-rotor time; the curves are read the same way as on overload relays, as covered in reading overload relay trip classes and curves.
Is the Set Current right for this motor and this wiring? #
For the standard in-line connection the Set Current must equal the 275 A nameplate value; for an inside-delta connection the starter carries winding current and the documented entry is nameplate current divided by √3, about 159 A.
The arithmetic: 275 A / 1.732 = 158.8 A, entered as about 159 A. Delta on the plate describes how the motor windings connect, not where the starter sits, and only a six-lead motor with the starter wired inside the delta takes the reduced entry. The manual directs the nameplate rated current into the quickstart menu, and the check that matters just as much is which parameter set is active: if the corrected value sits in a set that is not selected, the starter keeps running on the old numbers.
An entry below the true rated current overstates heating at every load; an entry above it hides a real overload. The same nameplate-first logic applies when setting overload relays from motor nameplate full-load current. Read and change these settings with the motor stopped, and before opening any enclosure or terminal box, de-energize the circuit and verify absence of voltage as NFPA 70E, 2024 edition, requires.
How do I log the current to prove the load is real? #
Record all three phase currents through one complete start and at least a full running cycle, because the heating model integrates current over time and a single snapshot cannot show whether 266–274 A is a plateau or a slow climb.
Worked example, calculated from this pump's snapshot, with loads taken against the nameplate current of 275 A:
- Average line current: (266 A + 274 A + 268 A) / 3 = 808 A / 3 = 269.3 A.
- Load against nameplate: 266 A = 96.7%; 274 A = 99.6%; 268 A = 97.5%.
- Phase imbalance: largest deviation from average = 274 A − 269.3 A = 4.7 A; 4.7 A / 269.3 A × 100 = 1.7%, well under the 2% that usually points at a supply or winding problem.
- Shaft loading: 179.5 kW / 184 kW = 97.6% of rated output, so the pump holds the motor at essentially continuous full load.
These figures are estimates to be checked against the governing code and the equipment documentation. Use a clamp meter suited to the circuit, as covered in measuring VFD and soft starter current with the right meter, and log the heating value alongside the currents through at least one start and one full running period.
| What the log shows | What it means | What to do |
|---|---|---|
| Current holds at 97–100% of nameplate with no peaks | Model at its steady-state ceiling for this duty | Check the pump duty point, then the prewarning limit |
| Current above nameplate for long stretches | Real overload or low supply voltage | Measure voltage at the starter under load; check pump, valve and impeller |
| Heating jumps sharply after every start | Long ramp or current limit stretching the start | Trim ramp time or start frequency |
| One phase consistently higher | Supply imbalance or a winding fault | Measure phase voltages and winding resistance |
A centrifugal pump loads the motor hardest at the high-flow end of its curve, so an open discharge valve, a low-head condition or an oversized impeller can hold it at full load around the clock. Measure the supply voltage at the starter terminals under load as well, because low voltage raises current for the same shaft power. Throttling toward the design duty point lowers both the current and the calculated heating.
How high should the prewarning limit sit? #
Set the prewarning limit about five points above the logged plateau — 95% for this pump — keeping it below the 100% trip so the warning still fires on an abnormal rise.
The entered 90% equals the plateau this motor settles at, so the message never clears, and the manual's factory value of 80% sits lower still. Raise the limit only after Set Current is verified and the log shows current at or below nameplate, then leave Tripping Class, Set Current and Idle time exactly as they are. Never lift Set Current above the nameplate value to silence the warning: NFPA 70, the National Electrical Code, 2023 edition, Article 430 requires motor overload protection matched to the motor that still permits starting, and an electronic setting above the nameplate current defeats that intent — confirm the requirement and any local amendment with your authority having jurisdiction.
When does a motor at full load need a real temperature sensor? #
Fit winding temperature sensing whenever the duty is continuous at 95–100% of nameplate current or the room runs hot, because the calculated model cannot see ambient heat, blocked cooling airflow or a failing motor fan.
A water-treatment pump that lives at the top of its curve is exactly that duty. Connect the motor's thermistor set to the soft starter's sensor input and enable the function as the manual describes, so real winding temperature backs up the calculated value; the sensor catches high ambient temperature, a blocked cooling fan or a clogged filter that the current-based model treats as a normal day. While you are there, check the motor's fan cowl and filter, because a full-load motor has no thermal margin to spare for dirty cooling.
What should the readings look like after the changes? #
A healthy run after the corrections shows three phases at or below nameplate current, imbalance under 2%, a heating value that rises on each start then settles below the new prewarning limit, and Remaining time for tripping holding at 0 s.
Work through the verification in this order:
- The active parameter set shows Set Current 275 A for in-line wiring, or about 159 A inside delta, matching the engineering software.
- The start completes inside the ramp time and the bypass closes without a trip.
- Logged phase current holds at or below the nameplate value with imbalance under 2%.
- The heating value climbs during each ramp, then flattens at a stable plateau below the 95% prewarning limit.
- Remaining time for tripping stays 0 s throughout running.
- After the pump stops, the heating value decays as the model cools.
- The prewarning message stays absent across a full duty cycle.
The decision: this warning is expected behavior for a pump motor running at its nameplate current. Keep the trip settings, confirm Set Current against the wiring, prove the load with a logged duty cycle, raise the prewarning limit to 95%, and back the calculated model with real temperature sensing on a motor that lives at full load. If the log instead shows current above the nameplate value for long stretches, the warning is telling the truth, and the duty point or the supply needs correcting before any setting moves.
Questions asked
What happens if I raise Set Current above the motor nameplate to stop the warning?
The whole thermal model rescales, so the calculated heating falls and the message clears, but the trip point moves up with it. A genuine overload, whether a blocked pump, a closed discharge valve or low supply voltage, then heats the windings for longer before protection acts. Set Current stays at the nameplate value; only the prewarning limit moves, and only above the logged plateau.
Does the integrated bypass contactor stop the heating calculation?
No. The bypass contacts short out the thyristors after the ramp to cut starter heat loss, and the documentation for these starters states that they provide the motor overload protection themselves. The starter keeps measuring current and integrating the thermal model while bypassed, so a pump that overloads during running still raises the heating value and can still trip.
Why did the warning appear after five hours rather than on the first start?
The heating value is an exponential approach to steady state, not an instant reading. Starting from cold, it climbs slowly during the ramp and needs hours of running at high current to close on its plateau. Five hours of pumping at 97–100% of the 275 A nameplate current was enough for the model to reach the 90% limit and raise the warning.
What temperature sensor suits a motor that runs full load continuously?
Use the winding protection the motor manufacturer built in, usually a PTC thermistor set, and connect it to the soft starter's sensor input, enabling that function in the motor protection settings as the manual describes. Real winding temperature then raises an alarm on high ambient heat, blocked cooling airflow or a failing cooling fan, conditions the current-based model cannot see.