Troubleshooting
Diagnosing a soft starter fault or alarm before resetting it
Short answer
Record the exact fault or alarm text, the values shown with it, and whether it appeared during start, run, or stop, before you reset, because a reset clears the diagnostic context. Then check the supply, the starter's documented ratings, the configured motor data, and the load: most trips trace to one of those four, not to a failed starter.
On this page
- Record the exact indication before you reset
- Confirm the supply and the installed ratings
- Match the configured motor data to the nameplate
- Worked example: fitting a 495 A motor to both power structures
- Sort the remaining trips by operating phase
- Correct one thing, then verify
- When to escalate
- Questions asked
Record the exact fault or alarm before you reset it: a phase-loss code such as PhF points you to the supply, and a motor whose 495 A nameplate full-load current sits above the installed power structure's 480 A range trips in run with nothing wrong inside the starter. Write down the code or message exactly as displayed, the values shown with it, and the operating phase it appeared in — start, run, or stop. That record is the diagnosis: a reset can clear the indication and the context that explains it. Then work four checks in order — supply, starter ratings, configured motor data, and load. Most soft-starter trips come out of one of those four, and a failed starter is the conclusion you reach last, not first.
Record the exact indication before you reset #
Use whichever interface is installed — a plug-in human interface module, a parameter configuration module, or PC-based software — and capture the status before anything else. If the unit has no display, count the flashing sequence on its indicator LED and decode it from the manual; some general-purpose starters signal every diagnostic through a red-LED flash sequence. Some models also keep a fault history you can read back after the event.
Record all of it:
- The code or message exactly as shown, including any sub-status. Two trips that display the same word can have different causes.
- The values displayed with the indication — motor current, thermal state, voltage — whatever the unit reports.
- Whether it is a fault or an alarm. On most units a fault ends the run and latches until cleared; an alarm reports a condition while the run continues. Your manual defines the set your unit uses.
- The operating phase: during acceleration, during steady run, or during a stop. Do not infer a cause from the timing alone — the phase tells you where to measure, not what broke.
- What happened on the last reset, if there was one.
Preserve that record before clearing anything. If the starter has tripped before, its fault history may still hold the earlier events.
Confirm the supply and the installed ratings #
Before any cover comes off the starter or its terminal box, open the disconnect, lock it out, and test for absence of voltage at the starter input with a meter rated for that voltage. NFPA 70E, 2024 edition, sets the safe work practices for that verification; confirm the requirements with your site program and the authority having jurisdiction.
Then check, reading the ratings off your own unit's nameplate and manual:
- All three line-to-line voltages feeding the starter, with a meter rated for the voltage. One low or missing phase points upstream — a loose lug, a blown fuse — not at the starter, and phase-loss codes (PhF on some units) mean exactly that. For that branch, troubleshooting a line-side fault on a soft starter walks the supply side.
- Measured voltage and frequency against the starter's documented range. As a documented example, the Allen-Bradley SMC-50 series is rated 200…690 V AC at 50/60 Hz. Outside that range, fix the supply or the application selection before retesting.
- The power structure on the nameplate, and the application against its current range. The same series documents 90…520 A with the solid-state power structure and 108…480 A with the internal bypass power structure. Those two ranges are not interchangeable.
- That the motor is a three-phase induction motor, the machine type this starter class is built for.
If supply and ratings check out, go to motor data before touching start parameters.
Match the configured motor data to the nameplate #
The starter's built-in electronic motor overload acts on the motor data you configure, so that data is the next suspect:
- Read the configured motor current out of the starter and compare it, value by value, with the motor nameplate. A configured full-load current below the nameplate value trips on ordinary load; one above it leaves the motor unprotected. Neither is a starter failure.
- Turn the load by hand where the process allows and confirm the driven machine is not binding. Pumps, fans, compressors, conveyors, crushers and mixers impose very different starting and running demands.
- Watch motor current in the phase where the trip happens, using the interface's live values. If the motor runs over its nameplate current after the bypass closes, see a motor running over nameplate amps after soft starter bypass; the same nameplate-first rule applies to discrete relays in setting overload relays from motor nameplate full-load current.
- Never raise the protection setting to quiet a trip. Correct the data or the load, then confirm the protection response matches the application.
Worked example: fitting a 495 A motor to both power structures #
Inputs:
- Motor nameplate — this example's input, so read your own: three-phase induction motor, 575 V, 60 Hz, full-load current 495 A.
- Starter ratings, documented for the series named above: 200…690 V AC at 50/60 Hz; 90…520 A with the solid-state power structure; 108…480 A with the internal bypass structure.
- Recorded indication: an overload-type trip during steady run, on a starter whose nameplate says internal bypass.
Rule in words: the motor's nameplate full-load current must fall inside the current range of the power structure actually installed.
Arithmetic:
- Solid-state structure: 90 A ≤ 495 A ≤ 520 A — inside, with 520 A − 495 A = 25 A of headroom above full load.
- Internal bypass structure: 495 A > 480 A — outside by 495 A − 480 A = 15 A, which is 15 A ÷ 480 A = 3.1% over the top of the range.
- Scale check: S = √3 × V × I = 1.732 × 575 V × 495 A = 492,970 VA ≈ 493 kVA at full load. This is the size of machine for which the 520 A − 480 A = 40 A gap between the two structures decides the selection.
Result: the 495 A motor fits the solid-state structure and does not fit the internal bypass structure at all.
Decision: the trip is a selection error, not a component failure. No parameter change makes a 480 A bypass structure carry 495 A continuously; specify the solid-state power structure for this motor, and treat the arithmetic as a fit check that the manufacturer's selection tables still govern. To run that selection properly from the start, see matching a soft starter's current range to its power structure.
Sort the remaining trips by operating phase #
Before editing anything, confirm which start and stop mode is actually configured. This class of starter offers many — one series documents 17 start and stop modes plus four special operating modes — and a diagnostic that ignores the configured mode can read normal behavior as a fault.
| When the indication appears | First checks |
|---|---|
| During acceleration | Supply voltage and phase loss, configured motor data, selected start mode and ramp settings, whether the load turns freely |
| During steady run | Motor current against nameplate, overload data, supply conditions, any process load change at the time of the event |
| During a stop | Configured stop mode, whether the load can overhaul the motor, stopping ramp settings |
| Immediately after every reset | Stop resetting; recheck the recorded status, supply, wiring, motor data and load |
If a networked command sits in the start or stop path, check the installed communication module's own diagnostics before blaming the power section.
Correct one thing, then verify #
- Make one targeted correction at a time, so the result stays attributable to that change.
- Clear the indication from the installed interface only after the cause is corrected — not to test whether it comes back.
- Restart under controlled conditions and watch the starter status and motor current through the phase where the trip occurred.
- Record the final configuration and the measurements that confirmed the fix.
- If the same indication returns, stop. Repeated resets into a known fault condition stress the motor and the power structure and prove nothing.
When to escalate #
Escalate when the exact indication survives all four checks, or when the interface reports a status its manual does not define. Take with you:
- starter nameplate details, including the power structure;
- the exact recorded status text and the values shown with it;
- motor nameplate data and the configured motor data;
- the operating phase of each event and the measurements you took.
Manufacturer documentation and its official support channel are the source for unit-specific wiring and fault interpretation.
Questions asked
How many times should I reset a soft starter that keeps faulting?
Once, after you have recorded the exact indication and finished the supply, ratings, motor-data and load checks. If the same fault returns, stop restarting. You are re-applying power into the condition that tripped it, which heats the motor and the power structure for nothing, and the repeat itself is evidence: it usually means a real mismatch or a failed component, not noise.
Do soft starters keep a record of past faults?
Many do, and the record survives the reset. The WEG SSW-06, for example, stores its fault sequence in parameters P014 through P017: the last fault, the second, the third and the fourth. You can read four events back without having caught any of them on the display, so check your manual for the equivalent fault-history parameters before you clear anything.
What is the difference between a fault and an alarm on a soft starter?
A fault trips: the run ends and the indication latches until it is cleared. An alarm reports a condition the starter is riding through, and the motor may keep running. Starters that expose status over a network separate the two, with the WEG SSW900 reporting with-fault and with-alarm as distinct statuses. Record both: a climbing alarm count often comes before the fault.
Can I stop nuisance overload trips by raising the current setting?
No. The built-in electronic overload is meant to match the motor nameplate full-load current, and a setting above that value leaves the motor unprotected. Nuisance trips come from one of three causes: configured motor data that does not match the nameplate, a genuinely heavier load, or a power structure whose current range does not cover the motor. Fix the cause, never the protection setting.