Troubleshooting
Why a motor meggers good but trips the breaker on start
Short answer
A 500-megohm winding-to-ground reading only proves the groundwall insulation; it says nothing about turn-to-turn shorts and nothing about starting current. A 75 HP, 89 A motor draws roughly 530-1160 A at start, and a 6 × 150 A = 900 A nominal instantaneous pickup carries a ±15-25 % tolerance, so a 680 A start plus first-cycle asymmetry lands inside the trip band. Identify the trip unit, read its curve, record one start, then raise the pickup or repair the winding.
On this page
A motor that meggers 500 megohms on every winding and still trips its breaker on start is not a contradiction: the two facts measure different things. The megger proves the insulation between winding and ground is intact, and nothing else. It cannot speak to turn-to-turn insulation inside a winding, and it cannot speak to starting current. On the numbers from this recorded case, a 75 HP, 460 V fan with 89 A full-load current, 680 A measured at start, and a 150 A frame breaker set to 6x, the trip is expected behavior, not a mystery. Six times 150 A is 900 A nominal pickup, the fine print on published curves allows a ±15 % to ±25 % tolerance on that number, and the first cycles of a start reach peaks well above that measured rms value. Work that arithmetic before blaming the breaker, the setting or the winding.
What the megger reading proves #
About 500 megohms from each winding to ground on a 460 V machine is a healthy groundwall reading. The test applies a DC voltage between the copper and the frame and measures leakage across that one barrier, and that barrier passed. The same instrument cannot examine insulation between turns of one winding: those conductors sit at nearly the same potential and form a single copper path as far as a DC tester is concerned. A phase-to-phase check adds the insulation between windings and confirms no open winding, which the no-reading result already told you, and still sees nothing between turns. The procedure matters too: for where to isolate the circuit and what a valid reading takes, see insulation resistance testing from the switchgear versus the motor terminals.
The megger result and the trip are therefore fully compatible. The trip is decided by current magnitude against the magnetic element's real pickup, and the test measures neither.
The start in numbers #
Inputs as recorded on this job:
- Motor nameplate: 75 HP, 460 V, three phase, 1750 RPM, 89 A full-load current.
- Breaker: 150 A frame, magnetic element adjusted to 6 × 150 A = 900 A nominal pickup.
- Measured starting current: 680 A.
- Starter: NEMA Size 4 magnetic contactor, overload relay separate from the breaker element.
The arithmetic:
- 680 A ÷ 89 A = 7.6 × full load. A Design B motor typically draws about 6 × full-load current at locked rotor, so 6 × 89 A = 534 A; the measured start is a normal, somewhat high, start.
- The first cycles exceed the locked-rotor rms. Point-on-wave asymmetry pushes the instantaneous peak toward 12 to 13 × full load on many machines, and some energy-efficient designs are worse in theory. For this motor, 13 × 89 A = 1157 A.
- Even the rms reading above has a sinusoidal peak of 680 A × 1.41 = 961 A before any DC offset is added.
Why that start trips a 900 A pickup #
The word doing the work is nominal. Published time-current curves for adjustable magnetic elements print a tolerance on the instantaneous band, commonly ±15 % to ±25 %. Run the edges:
- 900 A × 0.75 = 675 A on a −25 % unit. The accelerating current is above that, so a breaker at the bottom of its band opens on run-up current alone.
- 900 A × 0.85 = 765 A on a −15 % unit: same conclusion, more margin.
- 900 A × 1.25 = 1125 A on a +25 % unit. The 1157 A first-cycle peak clears even that.
Any unit inside that spread trips on some share of this motor's starts, and the element operates with no intentional delay, a few cycles at most. That overlap between pickup tolerance and inrush is the same mechanism behind intermittent instantaneous trips on motor starts: an identical setting holds one closure and trips the next, depending where the contactor lands on the voltage wave.
When the winding really is the problem #
A shorted turn is invisible to a megger and fatal to a start. The shorted loop behaves like a shorted transformer secondary: as the motor accelerates and counter-voltage builds, circulating current in the damaged section climbs and drags the phase current with it. The end state is burned insulation, often with no trip from anything watching ground leakage or average current, the failure family behind why motors burn up with no overload trip on 480 V. Two instruments see it: a micro-ohmmeter, by comparing the winding resistances phase to phase, and a surge comparison tester, which stresses turn insulation the way a megger stresses groundwall. On the job behind this article the motor was swapped and the trips stopped, which verifies the motor was the variable, but with no resistance record taken the exact defect was never identified.
Rule out a stalled start #
The fan had sat unused since 2004 and was windmilling backward before recommissioning; it was verified at standstill before the failed starts, which removes reverse rotation for those specific attempts. Standstill checked once is not standstill at closure, so confirm the shaft is stopped immediately before each test start. With the machine isolated, turn the train through by hand and feel for bearing roughness, belt or coupling drag, and rubbing. A start that never accelerates holds locked-rotor current for as long as the contactor holds it in, and every protective element opens that eventually. Long acceleration on a high-inertia load is a separate coordination problem, covered in overload relay settings for high-inertia starts.
What the code lets you change #
NFPA 70, the National Electrical Code (2023 edition), Article 430 and Table 430.52 set the maximum rating or setting of a motor branch-circuit short-circuit and ground-fault protective device, expressed as a percentage of full-load current. Editions and local amendments move these percentages, so confirm the requirement with the authority having jurisdiction and the equipment documentation before changing anything. Three numbers matter on this circuit:
- An inverse-time breaker for this motor is capped at about 250 % of full-load current: 89 A × 2.5 = 222.5 A. That column does not govern an adjustable magnetic element.
- The exception route for instantaneous-trip breakers permits a higher setting where the motor demonstrably will not start, up to 1700 % of full-load current: 89 A × 17 = 1513 A.
- Magnetic trip units of this class commonly adjust up to 10 × frame: 10 × 150 A = 1500 A.
Decision for this circuit: 10 × = 1500 A. At a −20 % tolerance the real pickup is 1500 A × 0.8 = 1200 A, above the 1157 A worst-case peak, so the start holds; 1500 A is 16.9 × full load, inside the 1513 A ceiling. The overload relay stays as the running protection, because the magnetic element protects against fault current, not overload.
Diagnostic sequence step by step #
De-energize the circuit, apply your lock, and test for absence of voltage before opening the breaker, the starter or the motor terminal box; every step below assumes that isolation.
- Record the breaker manufacturer, model, frame, trip unit and dial position, and confirm what the multiplier multiplies: frame, trip rating, or another reference the documentation names.
- Obtain the time-current curve for that exact trip unit and write down the instantaneous band and its stated tolerance.
- Photograph the motor nameplate: full-load current, locked-rotor code letter, design letter, voltage, connection. The code letter converts to locked-rotor kVA per horsepower through Table 430.7(B) of the same standard, for an inrush estimate.
- Compute the nominal pickup, both tolerance edges, and expected starting current at 6 × and 13 × full load.
- With isolation verified, rotate the driven train by hand, and confirm the fan is at standstill immediately before the test start.
- Record one start with a clamp meter or analyzer that has an inrush function: first-cycle peak, current decay, time to reach full load.
- Disconnect the motor from the starter, megger each winding to ground, then measure the three winding resistances with a micro-ohmmeter and compare them.
- Change one thing at a time and record the same measurements after each change.
Three outcomes, three decisions #
| What the recording shows | What it means | Decision |
|---|---|---|
| Peak clears the band, current decays toward full load, trip lands in the first cycles | Pickup set too low for this motor's inrush | Raise the magnetic setting to 10 × (1500 A on this frame) within the Table 430.52 limits and retest; leave overload protection to the overload relay |
| Current holds near locked-rotor value and the shaft never reaches speed | Stall: bound bearings, dragging train, insufficient torque or low terminal voltage | Fix the mechanics or the supply; do not raise the pickup to mask a stall |
| Motor accelerates, then current climbs or phases run unbalanced before the trip | Shorted turns the megger cannot see | Confirm with a micro-ohmmeter imbalance and a surge comparison test; repair or replace the motor, the swap being what cured the original fan |
On the numbers as recorded, this fan started at 680 A against a pickup that can sit as low as 675 A on a unit still inside its published band. That is a coin flip on every closure. Start with that arithmetic, not with the salvage history of the breaker.
Questions asked
Does a single trip take a circuit breaker out of specification?
No. A breaker rated for the circuit is built and tested to interrupt fault-level current and still hold calibration, so one start-duty trip within its rating is normal service, not damage. What does call for inspection is unknown service history, as with a salvaged unit, or an interruption near the interrupting rating. Follow the manufacturer maintenance guidance before trusting either.
Will a phase-to-phase megger test find a turn-to-turn fault?
No. That test checks the insulation between two separate windings. A turn-to-turn fault lies inside one winding, where the turns form a single copper path at nearly the same potential, so the DC test voltage never stresses it. Shorted turns show up as a lower phase resistance on a micro-ohmmeter, and a surge comparison test stresses turn insulation directly.
What instrument records the first-cycle inrush?
A clamp meter or power quality analyzer with an inrush function, or a high-speed recorder on a current transformer. The instrument must capture the peak asymmetrical current in the first cycles, not a smoothed average: a meter averaging over 100 ms will read something like the rms start value in this case and never see the 1000 A-class peaks that decide the trip.
Why did replacing the motor fix it when the megger read good?
Because the megger only cleared the groundwall insulation. The replacement motor either had healthy turn insulation or a lower locked-rotor characteristic, which the code letters on the two nameplates would show, so its start stayed below the real pickup of the breaker. The swap proved the original motor was the variable; without a micro-ohmmeter or surge test the exact defect stayed unidentified.