Troubleshooting
Troubleshooting a line side fault on a soft starter
Short answer
A line side fault reports the three-phase supply arriving at the starter's line terminals: missing, unbalanced, or outside nameplate range. Measure all three line-to-line pairs at the terminals at rest and during the start before touching the starter — most of these faults are a lost phase, blown fuse, loose termination, or start-time voltage drop upstream.
On this page
A line side fault on a soft starter (the PSTB family reports it as Line Side Fault) means the three-phase supply actually arriving at the unit's line terminals — not the supply at the upstream board — is missing a phase, unbalanced, or outside the unit's nameplate voltage range. Measure all three line-to-line pairs directly at L1, L2 and L3, once at rest and once during the start that trips the unit, before you open the starter or order parts. Most of these faults are upstream of the unit: a lost phase, a blown input fuse, a loose or resistive line termination, or a voltage drop that appears only under starting current. Only a supply verified in range at the terminals while the fault is active points back at the starter itself.
What the fault is telling you #
The display is the symptom; the electrical condition is the cause. The starter monitors its incoming supply before and during operation, and this fault means that measurement failed — it does not by itself mean the starter is defective. Keep the family's other faults separated, because they point at different parts of the circuit:
- A motor connection fault points at the motor power path downstream: output cables, motor terminals, abnormal current during startup.
- An EOL trip is the electronic overload — motor current too high for too long.
- A shunt fault indicates shorted semiconductors.
Line side work therefore stays on the incoming side: breaker or isolator, input fuses, supply cable, line terminations, upstream contactor, and the feeding transformer. Confirm the exact fault list for your model and revision in the manufacturer's documentation before assigning a cause.
Measure at the line terminals, at rest and during the start #
A reading at the MCC bucket or the feeder board is not the measurement. A resistive joint between there and the starter reads normally at rest and sags only when current flows, so take both sets of readings at the starter's own terminals.
- Record the exact fault text and the moment it appears: at power-up, on the start command, mid-ramp, or during steady run.
- At rest, measure all three line-to-line pairs at L1, L2 and L3. One pair proves only that pair, and phase-to-earth readings do not establish the complete three-phase set.
- During the start, repeat the three measurements with a second meter or a recorder, ideally with a simultaneous reading upstream for comparison.
Timing tells you where to look:
- Fault at power-up, motor never moves. Absent supply, an open breaker pole, a blown fuse, or incoming voltage off the nameplate. Trace from the terminals back.
- Fault on the start command or mid-ramp. The path carries current only then: a resistive termination (V = I × R), an undersized or long supply cable, a bad upstream contactor pole, or a transformer that sags through the inrush. A phase lost only under load is also the shape of the failure phase-loss relays miss on an open-delta service — see why phase loss monitors miss single-phasing on an open delta.
- Fault during run, or intermittent. Utility disturbance or an intermittent connection. Record voltage through an event and compare the upstream and terminal readings.
The most useful pattern: both pairs that contain one phase sag together while the pair without it holds. The resistance is in that phase's conductor and terminations between the source and the starter. Judge the three readings the same way you would when setting voltage imbalance limits on a 480 V phase monitor, and compute the imbalance identically each time so the numbers trend. A joint that drops volts also burns watts — P = I² × R — which is the physics behind detecting voltage sags upstream of loose MCC connections.
Taking readings with the panel energized is energized work: use instruments rated for the voltage and your site's energized-work controls. Anything that opens the panel or touches a termination starts with isolation, lockout, and testing for absence of voltage. NFPA 70E, the standard for electrical safe work practices in the workplace (2024 edition), governs those steps; confirm the requirements in force at your site with the authority having jurisdiction and the equipment documentation.
Worked example: a 480 V starter faulting mid-ramp at 490 A #
Inputs — illustrative readings for a hypothetical 480 V, 60 Hz, three-phase installation; substitute your own meter values:
- At rest, at the line terminals: L1–L2 = 477 V, L2–L3 = 476 V, L3–L1 = 478 V.
- During the ramp: L1–L2 = 461 V, L2–L3 = 476 V, L3–L1 = 462 V.
- Clamp meter during the ramp: 490 A per phase, with the ramp held at its current limit — see converting a 350 kVA soft start limit to starting current for working that limit into amps.
Rule in words: a resistive connection drops V = I × R volts and dissipates P = I² × R watts, so terminal voltage only moves when current flows.
Arithmetic:
- At rest the three pairs average (477 + 476 + 478) / 3 = 477 V with a worst deviation of 1 V, about 0.2%: the source is healthy at no load.
- During the ramp, both pairs containing L1 fall by 16 V (477 − 461 = 16 and 478 − 462 = 16); the pair without L1 does not move.
- Implied resistance in the L1 path: R = 16 V ÷ 490 A = 0.033 Ω.
- Heat in that joint during the ramp: P = 490² × 0.033 = 240,100 × 0.033 ≈ 7,900 W — nearly 8 kW in a single termination.
- Imbalance at the terminals during the ramp: (461 + 476 + 462) / 3 = 466.3 V average, worst deviation 476 − 466.3 = 9.7 V, about 2.1% — against 0.2% at rest.
Decision: two pairs sharing L1 sagging while the third holds convicts the L1 path between the source and the starter, and 8 kW destroys a termination. Isolate and verify absence of voltage, then inspect and re-terminate the L1 lug, the L1 fuse and its holder, and the L1 contactor pole. Treat any pair that falls more than about 10 V — call it 2% of 480 V — below its at-rest reading while current flows as a resistive path on the shared phase. If all three pairs sag together and equally, the drop is in the common path instead: supply cable, upstream contactor, or transformer.
Supply-path checks in order #
Work from source to terminal and stop when you find it:
- Main breaker or isolator. All three poles closed and making; a partially tripped or failed pole loses one phase with no other symptom.
- Input fuses. All three, plus the clips and holders — one blown fuse is a missing phase.
- Line terminations at the starter. Look for discoloration, melted insulation and heat marks; re-terminate and torque to the value in the starter's documentation. Loose or dirty connections are the documented first check for the neighboring "operational current too low or lost on one or several phases" fault on these families.
- Supply cable. Damage, and a length or size that drops voltage only under starting current.
- Upstream contactor. Pole resistance and contact condition.
- Transformer. Output voltage and tap setting. If it cannot hold terminal voltage through the start, it is a sizing question — the method in sizing a transformer for a 200 HP across-the-line motor start applies, with the starter's current limit standing in for the across-the-line inrush.
- Utility supply. Record voltage through an event before calling the fault intermittent.
When to suspect the starter itself #
Only after all three pairs measured in range at the terminals while the fault was active. Then read the unit's own fault history and the manufacturer's fault table for the exact model before assigning an internal cause. The internal fault to expect is the shunt fault — shorted semiconductors — and the connection decides when it latches: on an in-line connection it appears when two or three phases are shorted, and connected inside-delta, when one or more is. If the documentation's checks point to shorted devices or internal sensing, follow them; a verified-healthy supply with a persistent fault is the one case where replacing the unit is on the table.
Keeping it from coming back #
- Record the three at-rest pairs at commissioning and trend them; a widening spread finds the failing joint before the fault does.
- Put line terminations on the thermal-scan and retorque schedule, not on the fault list.
- When dips trace to the source, an event recorder at the terminals turns "intermittent" into a timestamped record you can act on.
Questions asked
Is a line side fault the same as a motor connection fault?
No. A motor connection fault points at the path downstream of the starter — output cables, motor terminals, abnormal current during startup — while a line side fault points at the supply before it. A shunt fault is different again: shorted semiconductors, which an in-line connected unit flags on two or three shorted phases and an inside-delta unit on one or more.
Why does the fault appear only during the start and never at rest?
Because a resistive connection obeys V = I × R. At rest almost no current flows, so terminal voltage reads normal; during the ramp hundreds of amps flow and the same resistance drops enough volts to leave the unit's operating range. A transformer or supply cable too small for the starting current produces the same timing.
Can we just reset the starter and try the start again?
Not repeatedly. The unit is reporting a real supply condition, and every reset drives starting current back through the defect — the loose joint in the worked example dissipated nearly 8 kW. Clear the supply path first. Resetting also does nothing for the separate electronic overload trip, which clears only when current and time allow it.
Where do power factor correction capacitors belong with a soft starter?
Never between the starter and the motor. The manufacturer's documentation warns that compensation capacitors on the motor side cause current peaks that can damage the starter. Put correction capacitance on the line side of the starter, ahead of where the unit measures its supply.
Is one voltage reading, or phase-to-earth readings, enough to check the supply?
No. Check the full three-phase set as described above. On an open-delta service a phase can also be lost in a way monitors miss, so verify at the line terminals under the exact condition that produces the fault — at rest and during the start.