Current IntelPower LibraryShop main store

Selection guide

Matching a soft starter current range to its power structure

Motors and motor starters Published 7 min read

Short answer

Match the power structure before anything else: a solid-state soft starter covers 90–520 A and an internal-bypass unit covers 108–480 A, both rated 200–690 V AC at 50/60 Hz. Size the starter so the motor's full-load current sits inside the span for the structure you actually have, then set the start modes.

On this page
  1. What do the current ranges actually cover?
  2. Which power structure does my starter have?
  3. Does the current range include starting current?
  4. How do I match the range to my motor nameplate?
  5. Will it accept my supply voltage and frequency?
  6. When should I pick solid-state instead of internal bypass?
  7. Can start modes or communication modules change the rating?
  8. What do I verify before energizing the new starter?
  9. Questions asked

Match the power structure first and the start modes last. In the Allen-Bradley SMC-50 series, solid-state power structure units span 90–520 A and internal-bypass units span 108–480 A of motor full-load current, everything rated 200–690 V AC at 50/60 Hz. No setting among the 17 start and stop modes moves those numbers: a motor outside the span for the structure you bought is a selection problem, not a configuration problem. Here is how to read the two spans, check them against the motor nameplate and the supply, and decide between the structures.

What do the current ranges actually cover? #

They are the spans of motor full-load current the Allen-Bradley SMC-50 series covers across its frame sizes, one for each power structure as stated above.

The spans belong to the power structure, not to the catalog as a whole. You cannot order a 500 A internal-bypass unit from this series, because that structure stops at the top of its span; the span floors mark where the smallest frames start. The number a span refers to is continuous motor full-load current — the figure on the motor nameplate — not the surge during the ramp.

A fully solid-state starter runs the motor on thyristor control the whole time and carries an IEC AC-53a utilization rating, the category for continuous SCR running of a squirrel-cage motor. An internal-bypass unit uses its SCRs to accelerate and decelerate, then closes a contactor around them for the run. That difference drives the structure choice later in this article.

Which power structure does my starter have? #

Read the nameplate or the catalog number before you plan anything else: a bypass unit contains a run bypass contactor that closes around the SCRs once the motor is at speed, while a solid-state unit leaves the SCRs in the circuit for the whole run.

Physically, the two are hard to confuse once identified: internal-bypass starters are typically much smaller and lighter than comparable units without run bypass, and they run cooler at full load because the SCR conduction losses drop out when the bypass closes. If reading the nameplate means opening the enclosure, de-energize the branch, lock it out under your site's NFPA 70E (2024 edition) program — the standard for electrical safe work practices — and verify absence of voltage with a rated meter before the cover comes off.

Does the current range include starting current? #

No — the span is continuous motor full-load current; the starting surge rides on top of it, typically 300–400% of motor rated current with a soft starter in the circuit, which the SCRs are sized to carry for the ramp time.

Reduced-voltage starting holds the ramp somewhere in that 300–400% band, a documented figure for this class of equipment. The current flows through the power section during acceleration while the span on the nameplate never changes. Long ramps on high-inertia loads stretch that SCR duty, so sizing a soft starter for a high-inertia blower without curves is its own exercise. If the constraint you are handed is a utility kVA cap instead of amps, converting a 350 kVA soft start limit to starting current shows the arithmetic.

How do I match the range to my motor nameplate? #

Put the motor's full-load current between the floor and the ceiling of the span for the structure you have, then set the overload to the nameplate FLA.

Start from the motor nameplate full-load current, not from horsepower. Where you only have horsepower, NFPA 70, the National Electrical Code, 2023 edition, Table 430.250, lists typical full-load currents for three-phase motors, and its 250 HP, 460 V entry is 302 A; that table value is an estimate for sizing, to be confirmed against the motor nameplate, the code as applied by the local authority having jurisdiction, and the equipment documentation.

Worked example — 250 HP, 460 V, three-phase squirrel-cage motor, 480 V supply.

  • Motor full-load current from Table 430.250: 302 A. Nameplate FLA (illustrative): 296 A.
  • Solid-state structure: 90 A ≤ 302 A ≤ 520 A, so it fits, with 520 − 302 = 218 A of headroom to the ceiling.
  • Internal-bypass structure: 108 A ≤ 302 A ≤ 480 A, so it fits too, with 480 − 302 = 178 A of headroom.
  • Starting current at a 350% ramp: 302 A × 3.50 = 1057 A through the SCRs during acceleration — duty on the power section, not part of the span.
  • Overload setpoint: 296 A, the nameplate figure, not the table figure and not the frame maximum.

Decision: both structures cover this motor, so the running profile picks the structure, not the amps. Run the same check on a 500 HP, 460 V motor — Table 430.250 gives 590 A — and it fails: 590 A sits above both ceilings, and nothing in the mode list or the module list changes that. That motor points to a larger starter family or a medium-voltage arrangement.

Will it accept my supply voltage and frequency? #

Yes if the supply sits between 200 and 690 V AC at 50 or 60 Hz — the series rating — so a 480 V or 600 V, 60 Hz system is inside it and a 1000 V or 2.4 kV system is outside it.

The voltage rating belongs to the series, not to the current span you pick: a small bypass frame and the largest solid-state frame carry the same voltage rating. Apply each frame within that span following its own installation documentation, including what it says about the control supply. On a 480 V system the voltage question closes in one look at the nameplate; above 690 V, this series is simply not the product class.

When should I pick solid-state instead of internal bypass? #

Pick solid-state when the thyristors must stay in the circuit for the whole run — continuous SCR control, long conduction periods, or the simplest power path with no bypass contactor — and internal bypass when the motor mostly runs at speed and enclosure heat and size matter.

What you are choosing Solid-state power structure Internal-bypass power structure
Motor full-load current span 90–520 A 108–480 A
Rated voltage 200–690 V AC, 50/60 Hz 200–690 V AC, 50/60 Hz
SCR conduction Start, run and stop Start and stop; bypass contactor carries the run
Full-load heat in the enclosure SCR losses continuously Drops when the bypass closes
Size and weight at similar current Larger and heavier Typically smaller and lighter
Best fit Loads that need thyristors in circuit continuously Continuous-running loads where heat and size drive the design

Commit by running profile. A fan or pump that ramps, runs for hours and stops rarely belongs on the bypass structure: once the contactor closes, the enclosure sheds only bypass-contactor and copper losses, and the smaller box helps a crowded lineup. A load that stays on SCR control — repeated ramps, a process that never settles at full speed — belongs on the solid-state structure with its AC-53a continuous rating, and it also takes the bypass contactor off the maintenance list.

Can start modes or communication modules change the rating? #

No — the 17 start and stop modes, the four special operating modes, the three hardware expansion ports and the optional communication modules are control and monitoring features; none of them moves the current span, the voltage rating or the overload capability.

Order the structure, span and voltage first, then choose behavior. The mode is picked from the load's torque and current needs using the product documentation, which defines each mode; the count alone tells you nothing about which one fits. The communication modules — the documentation for these controllers lists EtherNet/IP and DeviceNet among the supported networks — add monitoring and control paths through the three expansion ports, not amps.

Programming goes through an optional Parameter Configuration Module, a Human Interface Module, or PC software; Connected Components Workbench is the documented PC route. None of those interfaces changes a power rating. The built-in electronic motor overload is the one listed feature that touches the power circuit: it is real protection, and it gets set to the motor nameplate FLA, not to the frame maximum.

What do I verify before energizing the new starter? #

With the branch locked out, verify three things: the nameplate structure and span match the selection sheet, the overload is set to the motor nameplate FLA, and the supply voltage sits inside the series rating.

Then watch the first start. Measure the ramp with an instrument that reads the SCR waveform correctly — measuring VFD and soft starter current with the right meter covers which class of clamp meter to use — and confirm the bypass closes and the current settles at the motor's full-load figure. If it settles high instead, the motor and its load are the place to look: diagnosing a motor running over nameplate amps after soft starter bypass starts that hunt. Record the final settings so the next troubleshooter starts from known values.

Questions asked

Can a 500 A motor use the internal-bypass structure?

No. The internal-bypass power structure has the lower ceiling of the two in this series, and no mode or parameter changes that. A 500 A motor falls inside the solid-state span, so that is the structure to order, with the overload set to the motor's nameplate full-load current.

Does the built-in electronic overload replace the separate overload relay?

It can serve as the motor overload protection when it is programmed to the motor's nameplate full-load current — that is its documented job in this series. It does not replace the branch-circuit short-circuit and ground-fault protection ahead of the starter: that still comes from the fuses or breaker sized with the starter's documentation, which in a UL 508A industrial control panel also carries the assembly's short-circuit current rating.

Is 200–690 V AC one wide input range on every unit?

It is the rated voltage span of the series at 50/60 Hz. Each frame is applied within that span according to its own installation documentation, and the control supply must match what that documentation calls for. A 480 V or 600 V system sits inside the span; anything above 690 V, such as a 2.4 kV bus, needs a different product class.

How much starting current should I plan for through the SCRs?

Plan on roughly 300–400% of the motor's rated current during the ramp — the documented figure for reduced-voltage soft starting — against locked-rotor currents that can exceed six times full-load current across the line. For the 302 A motor in the worked example, a 350% ramp puts 302 × 3.50 = 1057 A through the starter during acceleration.

Why is the internal-bypass ceiling lower than the solid-state one?

The spans are what the series is built and offered in, with the bypass line topping out below the solid-state one. Nothing among the 17 start and stop modes or the module options stretches either number. If the motor needs more current than the bypass ceiling and you want the bypass, the requirement points you to the solid-state structure or to a larger starter family.

Keep reading

  • Explainer

    Motor starter vs contactor: using a starter as one

    A motor starter is a contactor with an overload relay added: the relay's normally closed contact opens the coil circuit on sustained overcurrent. A starter works wherever a contactor is called for, provided three checks pass — horsepower rating at the supply voltage, coil voltage, and the overload setting against the motor's nameplate full-load current. A NEMA Size 1 covers a 3 HP motor.

    Motors and motor starters

  • Selection guide

    Specifying soft starters for high-inertia blowers without curves

    Torque, not kilowatts, decides the start: at a 400% current limit on a motor with 800% locked-rotor current, torque falls to about 25% of DOL and a 15 s blower start stretches to four times that or stalls. Close the dampers, hold the limit near the square root of the load-torque fraction times the measured inrush (about 500% of full-load current here), buy duty to cover it, or specify a drive.

    Motors and motor starters

  • Explainer

    Converting a 350 kVA soft start limit to starting current

    A 350 kVA soft start limit is about 421 A of line current at 480 V: divide 350,000 VA by √3 × 480 V. The figure is apparent power, so no power factor enters the conversion, and it carries no duration — that comes from the torque-speed margin. The 12.5 kV fuse is a coordination problem; motor protection belongs at 480 V.

    Motors and motor starters