Reading overload relay trip classes and curves

Motors and motor starters Published 8 min read

Short answer

No. A thermal overload relay carries a single inverse-time I²t characteristic with no instantaneous element, anchored by its trip class: the class number is the maximum trip time in seconds at 6× the setting. For coordination, approximate it with t = 36 × C / M², read the class from the datasheet rather than the relay label, and leave short-circuit clearing to the upstream breaker or fuse.

On this page
  1. Does a thermal overload relay have a breaker-style trip curve?
  2. What does the trip class number on an overload relay mean?
  3. Is the trip class printed on the overload relay label?
  4. How do I approximate the curve from the class number?
  5. How do I check the class against a real motor start?
  6. How do I verify an installed relay against its curve?
  7. Which faults does the overload relay actually clear?
  8. Questions asked

A thermal overload relay has no breaker-style curve. There is no long-time region, no short-time pickup and no instantaneous leg — just one inverse-time characteristic fixed by the trip class, where the class number is the maximum trip time in seconds at 6× the dial setting. Class 10 trips in 10 s at 6×, Class 20 in 20 s, Class 30 in 30 s. For coordination work the whole overload region can be approximated with t = 36 × C / M², with C the class and M the multiple of setting, and the class comes from the relay's datasheet, not its label. Short-circuit clearing is not the relay's job at all; that belongs to the upstream fuse or breaker.

Does a thermal overload relay have a breaker-style trip curve? #

No. The relay has a single inverse-time region and no instantaneous element of any kind; its entire characteristic is anchored by the trip class, which fixes the trip time at 6× the setting — 10, 20 or 30 seconds by class.

Heater elements and bimetals respond to I²R heating, so the time to reach trip temperature falls roughly with the square of the current multiple. That shapes one smooth inverse-time curve covering the overload region only: from just above the setting up to locked-rotor current. A thermal-magnetic breaker, by contrast, stacks a long-time region under a fixed-pickup instantaneous magnetic region, which is why its published characteristic is a family of regions rather than one band.

Reading a trip against that shape separates thermal events from start mismatches. A trip after minutes at 1.1× to 1.5× setting is a running overload: sustained mechanical load, voltage unbalance, or a dial set wrong. A trip within seconds of every start is a start-current-versus-class mismatch, not a defective relay — the classic Class 10 relay on a load that accelerates slowly.

What does the trip class number on an overload relay mean? #

The class number is the maximum trip time in seconds at six times the relay setting, from a cold relay: Class 10 trips in 10 s at 6×, Class 20 in 20 s, Class 30 in 30 s.

Two standards define this. UL 508, the industrial control equipment standard that carries US practice going back to NEMA ICS-2, states the class at 600% of the current setting. IEC 60947-4-1, which covers contactors and motor starters including their overload relays, lists classes 10A, 10, 20 and 30 and proves the class at 7.2× the setting from cold: Class 10A in 2–10 s, Class 10 in 4–10 s, Class 20 in 6–20 s, Class 30 in 9–30 s. The same standard fixes the low end of every curve: no trip at 1.05× the setting, trip within two hours at 1.2×.

Confirm the edition in force and any local amendment with the authority having jurisdiction and the relay's documentation, and treat the manufacturer's curve sheet for your exact catalog number as the tiebreaker between the two definitions. Some datasheets also print normal and tighter tolerance bands for the same class; the tighter band narrows the spread but keeps the class anchor.

Is the trip class printed on the overload relay label? #

Not reliably. The relay face carries the current range or heater element code and the dial scale; the class belongs to the relay model, so it comes from the datasheet or trip-curve sheet for the exact catalog number.

What you need Where it lives
Trip class (10A, 10, 20, 30) Datasheet for the exact catalog number
Trip time at 6× setting The class number, in seconds
Current setting Dial or heater code, set from nameplate full-load current
Cold and hot bands Manufacturer trip-curve sheet
Governing requirements UL 508 and IEC 60947-4-1

The dial is a separate job from the class: it follows the motor nameplate full-load current, the procedure covered in setting overload relays from motor nameplate full-load current.

How do I approximate the curve from the class number? #

Anchor one point and assume constant I²t: t = 36 × C / M² seconds, where C is the class and M is the current multiple, a formula that returns the class number exactly at M = 6 and holds reasonably down to about 2× setting.

The 36 is 6². The result is derived from the class anchor, not read from any manufacturer's curve, so treat it as an estimate. Evaluated, it gives:

M = I / Isetting Class 10 Class 20 Class 30
2× 90 s 180 s 270 s
3× 40 s 80 s 120 s
4× 22.5 s 45 s 67.5 s
6× 10 s 20 s 30 s

Below about 2× the real curve flattens toward its two-hour conventional points and the formula no longer represents the relay: at 1.2× a Class 20 sheet allows up to two hours where the formula returns about eight minutes. The estimate also assumes a cold relay; a relay that has been carrying load trips sooner at the same multiple, and published sheets print separate cold and hot bands. The hot band is the one that matters for restarts.

How do I check the class against a real motor start? #

Compare the acceleration time with the formula's trip time at the starting-current multiple: at 6.5× a Class 10 relay gives about 8.5 s, so any start that needs longer trips mid-acceleration and the class is wrong for the load.

  1. Record the relay catalog number and pull its class and published curve from the datasheet.
  2. Set the dial to the motor nameplate full-load current; that value is Isetting.
  3. Get the starting current and acceleration time from the motor and load data, then compute M = Istart / Isetting.
  4. Compute t = 36 × C / M² and compare with the acceleration time; the start must finish well inside the cold trip time.
  5. Overlay the relay curve on the upstream breaker or fuse curve: the relay trips first in the overload region, and the upstream device clears everything above the relay's withstand.
  6. Where the two curves sit closer than the formula's error, replace the estimate with the manufacturer's curve data.

Worked example (illustrative inputs). Motor nameplate: 460 V, three-phase, 60 Hz, full-load current 65 A. Load: high-inertia fan, estimated starting current 6.5 × 65 A = 422.5 A, acceleration time 14 s.

M = 422.5 / 65 = 6.5

Class 10: t = 36 × 10 / 6.5² = 360 / 42.25 = 8.5 s. A 14 s start trips 5.5 s before the fan reaches speed, so Class 10 is the wrong relay here.

Class 20: t = 36 × 20 / 42.25 = 720 / 42.25 = 17.0 s, a 3 s cold margin. Class 30: t = 1080 / 42.25 = 25.6 s, an 11.6 s margin.

Decision: for cold starts only, Class 20 is adequate. If this fan restarts hot after an overload or process trip, take Class 30, because the hot band of a Class 20 sheet will sit close to a 14 s acceleration. The motor's own hot safe-stall time, from its data sheet, must exceed the class time at locked rotor, or the slower class trades nuisance trips for cooked windings. Choosing a class for loads like this is the same problem worked through in setting overload relays for high-inertia motor starts.

How do I verify an installed relay against its curve? #

De-energize the starter, lock it out and test for absence of voltage first, then inject a test current at a chosen multiple into the relay from cold and compare the measured trip time with the published band.

Pass the test current through the relay terminals on a thermal unit, or into the current-transformer secondaries on an electronic one, at a fixed multiple of the dial setting. At 6× the trip must land inside the class window — for a Class 20 relay, 6–20 s per IEC 60947-4-1, against 20 s maximum at 6× under UL 508. Check one intermediate point, 3×, against the cold band, then repeat hot to see the shorter hot-start time. A relay that trips outside its published band is a failed device; replace it rather than adjusting the dial to mask it. After any motor change, confirm the dial still matches the new nameplate full-load current.

Which faults does the overload relay actually clear? #

Only overloads: sustained current above the setting up to locked-rotor level. Every fault above that region is cleared by the upstream fuse or breaker, because the relay has no instantaneous element and a contactor cannot interrupt short-circuit current.

IEC 60947-4-1 formalizes the split as coordination types. Type 1 accepts contactor damage on a short circuit provided nothing endangers persons outside the enclosure and parts are replaced afterwards; Type 2 limits damage to light contact welding, and it holds only with the specific upstream fuse or breaker listed in the manufacturer's coordination table for that starter. Pick the type the installation needs, then use the documented device pair rather than a near-equivalent.

Phase loss sits in between. Overload relays provide phase-failure protection through a differential mechanism that speeds the trip when one phase carries less current, but a lightly loaded single-phased motor can stay under the dial setting and overheat without tripping. A motor that cooks at or near rated current — unbalance, blocked cooling — fails with no trip at all, the pattern covered in why motors burn up with no overload trips on 480 V.

Questions asked

Can I fit a Class 30 relay where a Class 20 is installed?

Yes, when the only problem is start duration. A slower class tolerates a longer acceleration, and running protection barely moves, because both classes must trip within two hours at 1.2× setting. First check two limits: the motor's own hot safe-stall time must be longer than the class allows at locked rotor, and the upstream breaker or fuse must still clear short circuits before the relay's withstand is exceeded. The class changes the start window, not the short-circuit story.

Do electronic overload relays use the same trip classes?

Yes. The classes apply to electronic relays too; they model the motor's thermal state instead of heating a bimetal, so measured trip times land closer to the published nominal, and many offer a selectable class plus separate phase-loss and stall detection. For coordination the class anchor still fixes where the curve sits, so the same t = 36 × C / M² estimate works for a first pass.

Why does the relay trip faster on a hot restart than the formula says?

Stored heat. The formula assumes a cold relay, and a bimetal that has just carried full load starts partway to its trip temperature, so the same starting current trips it sooner. Published curve sheets print separate cold and hot bands; size the class so the acceleration time fits inside the hot band whenever the motor restarts before it cools.

Will a single-phased motor always trip the overload relay?

Not always. A heavily loaded motor that loses a phase draws more current in the remaining lines, and the relay's differential trip bar speeds the trip. A lightly loaded motor can stay under the dial setting and overheat without tripping at all, which is why electronic relays add dedicated phase-loss detection and why a phase-loss event should not be ruled out just because the relay never tripped.

Keep reading

  • Selection guide

    Setting overload relays for high-inertia motor starts

    Set the current dial at the motor's nameplate full-load current and buy starting time with the trip class, not with a higher setting: Class 10 holds starts up to about 7 s at 600 percent, Class 20 to about 14 s, Class 30 to about 21 s. Longer starts need reduced-current starting, not a bigger relay.

    Motors and motor starters

  • Troubleshooting

    Why raising a magnetic overload setting won't fix a hard start

    No. Raising the dashpot pickup toward the 125% ceiling a 1.15 service factor permits adds no starting torque; it only lets the motor sit at locked-rotor current longer while its running protection shrinks. Find which device opened — breaker instantaneous element or overload relay — and fix what makes the start hard; in the case behind this article, an over-filled fluid coupling was the whole problem.

    Motors and motor starters

  • Selection guide

    Selecting overload and jam protection for a reversible motor

    Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.