Setting a soft starter current limit without overheating the motor
Short answer
Set the soft starter current limit from the accelerating torque the load needs, not from the starter's duty figure. Estimate the limit as locked-rotor current times the square root of required torque over locked-rotor torque, check that current, dwell time and starts per hour against the starter's duty table, then verify every start with a measured peak current and acceleration time. At a 300% limit a typical design B motor develops only about a third of its full-load torque.
On this page
Set a soft starter's current limit from the torque the load needs to accelerate, not from the duty figure in the starter's catalog. That duty figure — one common rating reads 300% of full-load current for 30 seconds, ten starts per hour — says how long and how often the thyristors can carry starting current. It does not say what your motor needs. Induction-motor torque falls with the square of applied voltage, so a limit at 300% leaves a typical NEMA design B motor with about a third of its full-load torque: enough for some fans, short of a loaded pump. Work the limit out from the motor's locked-rotor data and the load's starting torque, check the result against the starter's duty table, and verify each start with a measured peak current and acceleration time before calling the setting commissioned.
What the current limit actually controls #
A soft starter regulates motor voltage through thyristor firing angle. At line frequency, torque scales with the square of applied voltage, and near standstill the locked-rotor current scales roughly with voltage. At a current limit, then, the motor delivers approximately:
T_limit ≈ T_LRA × (I_limit ÷ I_LRA)²
with both current and torque referenced to the motor's locked-rotor values. Read locked-rotor current and locked-rotor torque from the motor's datasheet. NEMA MG-1, the standard for motors and generators, defines how this data is reported, and typical NEMA design B figures are locked-rotor current of 6 to 7 times full-load current and locked-rotor torque near 150% of full-load torque. Use the values for the actual motor, not the typical ones.
The square is what surprises people. Hold a design B motor at 300% of full-load current with a locked-rotor current of 6.5 times full-load: the voltage fraction is 3.0 ÷ 6.5 = 0.46, the torque fraction is 0.46² = 0.21 of locked-rotor torque, and at 150% locked-rotor torque that is about 32% of full-load torque. Stator heat scales the same way: copper loss runs at current squared, so 300% held at the limit means nine times rated stator copper loss for every second the start lasts.
What the duty figure tells you and what it does not #
A duty rating bundles three numbers: a starting current as a multiple of full-load current, a duration per start, and a repetition rate. It describes the thyristors' thermal budget, so it caps how long and how often you may hold starting current — including a limit set above the rating's own current figure. IEC 60947-4-2 is the product standard for semiconductor motor controllers such as soft starters; editions differ and manufacturers establish duty ratings against it, so take the installed model's ratings from its own documentation and confirm any code question with the local authority having jurisdiction.
The decision follows directly: if the load needs a limit or a dwell the published duty point does not cover, the starter is undersized. Fit a starter duty-rated for the calculated current, time and frequency, or use a drive. Setting the limit past the duty figure and hoping is not a thermal budget.
Size the limit from the accelerating torque #
Take the load's torque at its worst speed point — standstill for a pump or fan, whose torque rises with speed — and check the full speed range for a constant-torque load such as a conveyor or a compressor started loaded. Add an accelerating margin: about 30% of full-load torque at the worst point is a workable commissioning target, because supply dip during the start and torque ripple consume anything thinner. Then run the same physics in reverse:
I_limit ≥ I_LRA × √((T_load + T_margin) ÷ T_LRT)
with all three torque terms on one basis — fractions of full-load torque work well. The result is an estimate: it rests on the locked-rotor approximation and datasheet tolerances, so treat it as the first setting and let the measured start confirm it. A load that needs near-full torque from zero speed — a loaded conveyor, a compressor starting under pressure — is beyond reduced-voltage starting at any setting; it needs unloading or a drive.
Worked example: one 40 hp motor on a fan and on a pump #
These inputs are illustrative, not a measured machine: 40 hp, 460 V, three-phase, 60 Hz, nameplate full-load current 46 A, locked-rotor current 6.5 × 46 = 299 A, locked-rotor torque 150% of full-load, 1770 rpm.
Full-load torque: 5252 × 40 hp ÷ 1770 rpm = 119 lb·ft, so locked-rotor torque is 1.5 × 119 = 179 lb·ft.
Case 1 — fan, inlet vanes closed. Load torque at rest: 25% of full-load = 30 lb·ft. Required at standstill: 25% + 30% margin = 55%. Limit: 299 × √(55 ÷ 150) = 299 × 0.606 = 181 A, about 3.9 times full-load current. Set 400% (184 A), which delivers (184 ÷ 299)² × 179 = 68 lb·ft, or 57% of full-load torque, at 16 times rated copper loss. Decision: set 400% only if the model's duty table covers 400% for the measured dwell at your start frequency; if its duty stops at 300%, this fan needs a higher-duty starter.
Case 2 — pump loaded at zero speed. Load torque: 40% of full-load = 48 lb·ft. The tempting shortcut — setting the limit at the 300% duty figure, 138 A — gives (138 ÷ 299)² × 179 = 38 lb·ft, or 32% of full-load torque. That is below the load's 48 lb·ft, so the motor sits at limit current, heating, and does not accelerate. The calculation gives 299 × √((40 + 30) ÷ 150) = 299 × 0.683 = 204 A, about 4.4 times full-load current. Decision: against a starter whose duty ends at 300%, this pair is mismatched — specify a starter duty-rated near 440% of full-load current (about 204 A) at this dwell, or a drive, then verify the first start.
Commissioning sequence #
- Collect the data: nameplate full-load current, locked-rotor current and torque, and the load's breakaway torque. If your starting data arrives as kVA rather than amps, convert it first, as in converting a soft start kVA limit to starting current.
- Compute the limit from the formula above at the worst speed point, with the 30% margin.
- Check that current, an estimated dwell and your starts per hour against the installed starter's duty table. If the table does not cover them, change the hardware before energizing anything.
- Set the ramp and the pedestal. In current-limit mode the ramp is secondary: when current reaches the limit, the starter holds voltage steady until current falls back below the setpoint, so the load sets the pace. Raise the pedestal, the initial voltage, until the shaft breaks away within about a second of the start command.
- Plan the measurement before the first start: read current from the starter's own display where it has one, or clamp one phase with a clamp-on ammeter where the conductor is accessible. Where a test needs covers off, de-energize first, lock out and tag out, and verify absence of voltage at the terminals before touching anything.
- Start once and record three numbers: peak current, time to full speed, and whether breakaway was prompt. Peak at the set limit with brisk acceleration means done.
- Set the overload from nameplate full-load current, following setting the overload relay from motor nameplate full-load current, and choose a trip class that fits the measured acceleration time, following reading overload relay trip classes and curves.
- Repeat the starts you actually need and keep the count inside the duty table's starts-per-hour at the applied current and time. After any tripped or incomplete start, let the motor cool substantially and read the trip history before resetting, following diagnosing a soft starter fault or alarm before resetting it.
What a bad first start tells you #
| What you measure | What it means | What to do |
|---|---|---|
| Peak current at the set limit, brisk run-up | Commissioned start | Record current, time and count; hand over |
| Current pinned at the limit, shaft stopped or creeping | Motor torque below load torque | Raise the limit only if the duty table allows; otherwise re-size the hardware |
| No shaft movement, current below the limit | Pedestal voltage too low for breakaway | Raise the pedestal until breakaway inside about a second |
| Current spike above the limit at breakaway | Pedestal or kick-start too aggressive | Trim the pedestal, shorten any kick-start boost |
| Acceleration eats most of the allowed dwell | Margin too thin or load heavier than the data | Recompute with measured load torque and check the motor's thermal state |
The mismatch case deserves its own line: a motor pinned at the current limit that barely creeps is a torque deficit, not a control fault, and it is exactly the situation in why a large motor stalls when the soft starter hits current limit. Every second at that dwell accumulates heat in a motor whose shaft fan is barely turning, so stop, recompute, and either raise the limit within the duty table or change the hardware.
Questions asked
Does a longer ramp time reduce motor heating?
No. Heating follows current squared multiplied by time, so a ramp that dwells near the current limit longer adds heat rather than saving it. The load needs the same kinetic energy to reach running speed either way; a limit set too low converts that energy into prolonged stator and rotor loss. The economical setting is the lowest limit that still accelerates the load briskly, confirmed by a measured acceleration time well inside the starter's allowed dwell.
How do I get locked-rotor amps from a NEMA code letter?
Take the kilovolt-ampere per horsepower band the letter stands for in NEMA MG-1, multiply by the motor's horsepower, then divide by 1.732 times the line voltage in kilovolts. A 40 hp code G motor at the top of its 5.6 to 6.3 band gives 6.3 × 40 = 252 kVA, and 252 ÷ (1.732 × 0.46 kV) = about 316 A of locked-rotor current. Use that value in the limit calculation.
Can the current limit be set above the starter's duty figure?
Many models let you set the limit well above their standard-duty current, but the duty table still governs: it pairs each starting current with an allowed duration and repetition rate. If the table publishes your current, dwell and starts per hour, the setting is usable. If it does not, the starter is not rated for that start. Fit a higher-duty model or a drive instead of running an unpublished duty.
How long should you wait between soft starts?
Wait per the starts-per-hour figure that matches the duty you actually ran, not the catalog maximum. A stalled or crawling start is the worst case: the rotor sits still, the shaft fan delivers no airflow, and the heat stays concentrated in the motor. After an incomplete start, let the motor cool substantially, check the thermistor or thermal protection status where fitted, and find the cause before the next attempt.