Current IntelPower LibraryShop main store

Troubleshooting

Why a large motor stalls when the soft starter hits current limit

Motors and motor starters Published 8 min read

Short answer

Log shaft speed against current at the stall. A reading near 214 rpm (one-seventh of the 1500 rpm synchronous speed) or 115 rpm (one-thirteenth), with 3-4 current-envelope teeth per second at the 1809.5 A limit, is induction-motor crawling aggravated by SCR harmonics, not a rotor fault. Raise the current limit and shorten the dwell; the paralleled transformers made it worse by stiffening the source.

On this page
  1. Read the stall as a speed-and-current event
  2. The crawl speeds to log first
  3. Worked example: checking the 3.5 MW fan start against the crawl speeds
  4. Why the second transformer made starts worse
  5. Ruling out the mechanical suspects
  6. Changes that clear a crawl-limited start
  7. Questions asked

The motor runs smooth for the first ten seconds of the voltage ramp, then vibrates and stops accelerating the instant the soft starter reaches its 470% current limit. That timing is the diagnosis. When a machine stalls only after current limiting engages, and the current and voltage envelopes grow 3-4 sawtooth teeth per second, log shaft speed before touching anything: a stall near one-seventh of synchronous speed - 214 rpm on this 1500 rpm machine - is induction-motor crawling aggravated by SCR harmonics, not a rotor fault. The fix is starter-side: more current headroom and less dwell in the crawl band. The paralleled transformers made it worse by stiffening the source.

Read the stall as a speed-and-current event #

One synchronized record settles this: shaft speed, motor current, motor-terminal voltage and vibration on a shared timebase, plus the starter's event log. In this case the nameplate reads 3.5 MW, 6 kV, 50 Hz, 1485 rpm and 385 A; the starter is set for a voltage ramp of roughly 10 s, a 50 s start and bypass at about 80% speed. Terminal voltage went from 6.4 kV to 6.0 kV through the ramp, the motor ran smooth, and the teeth appeared only once current reached the preset limit. Each start was stopped manually at about 20 s.

What each record answers:

  • Shaft speed at the stall - which torque component the motor has settled on.
  • Tooth rate against shaft speed - whether the modulation happens once per revolution.
  • Terminal voltage across the whole start - whether voltage collapse explains anything. Here it does not: 6.0 kV at the terminals of a 6 kV machine is nameplate voltage, and a stall at nameplate voltage is a torque problem, not a supply problem.
  • The starter's event log - when the limit engaged and what the starter recorded about it. Pull the log before resetting anything, the way diagnosing a soft starter fault or alarm before resetting it works through the alarm record first.

The crawl speeds to log first #

Induction motors carry parasitic torque curves that come from slotting and flux harmonics. The seventh harmonic rotates forward with its own synchronous speed at one-seventh of the fundamental's, and its torque peaks just below that speed; the thirteenth behaves the same way at one-thirteenth. Designers fight this with unequal stator and rotor slot counts and with rotor skew, which suppress the effect but never remove it. When accelerating torque is thin, the motor climbs to the harmonic peak, fails to punch through the dip just above it, and parks there.

A current-limited soft starter is a poor companion to that curve. Holding a fixed limit forces the SCRs to fire late, the chopped voltage is rich in harmonics, and harmonic torque grows with harmonic current. Meanwhile the driven load stretches the start: a 15,000 lb impeller with a WR2 of 66,000 lb-ft2, dampers closed. Closed dampers remove the air load but none of the inertia, so the machine spends seconds at a time exactly where the harmonic dip lives. That inertia is also why specifying soft starters for high-inertia blowers without curves sizes the start from torque and time rather than from nameplate class alone.

The candidates to log, as fractions of synchronous speed:

  • one-seventh of synchronous speed - the seventh-harmonic crawl
  • one-thirteenth of synchronous speed - the thirteenth-harmonic crawl

The worked example below puts this machine's numbers on both fractions.

Worked example: checking the 3.5 MW fan start against the crawl speeds #

Inputs, each with its source:

  • Motor nameplate and data sheet: 3.5 MW, 6 kV, 50 Hz, 1485 rpm, 385 A rated current, 2300 A locked-rotor current.
  • Starter settings record: constant-current control, voltage ramp of about 10 s, current limit at 470% of rated current, programmed start of 50 s, bypass contactor closing at about 80% speed.
  • Observed on the failed starts: terminal voltage 6.4 kV falling to 6.0 kV during the ramp; 3-4 envelope teeth per second once the limit engages; no further acceleration; manual stop at about 20 s.
  • Driven load: fan with dampers closed, 15,000 lb impeller, WR2 of 66,000 lb-ft2.

The rules in words: synchronous speed is 120 x frequency divided by pole count; the crawl candidates are one-seventh and one-thirteenth of synchronous speed; the limit in amperes is the setting times rated current; a once-per-revolution modulation appears at shaft speed divided by 60, in hertz.

The arithmetic:

  • 1485 rpm at 50 Hz fits a four-pole machine: Ns = (120 x 50) / 4 = 1500 rpm, with 1% slip at full load.
  • Seventh-harmonic crawl: 1500 / 7 = 214.3 rpm, modulating at 214.3 / 60 = 3.57 per second.
  • Thirteenth-harmonic crawl: 1500 / 13 = 115.4 rpm, modulating at 115.4 / 60 = 1.92 per second.
  • Current limit: 4.7 x 385 A = 1809.5 A.
  • Locked-rotor draw: 2300 / 385 = 5.97, so the motor pulls about 597% of rated current when line-started.

The result: the observed 3-4 teeth per second are once-per-revolution rates of 180-240 rpm (3 x 60 to 4 x 60), and the seventh-harmonic crawl at 214.3 rpm sits inside that band. The thirteenth at 115.4 rpm would tick about twice a second, which these traces do not show. These figures are estimates from nameplate data; the motor data sheet's torque curve and a measured speed close the case.

The decision: put a non-contact tachometer on the shaft during the next start attempt. A steady reading within about 10 rpm of 214 rpm, teeth locked to rotation, confirms seventh-harmonic crawl - treat the rotor as sound and fix the start, not the machine. A reading near 115 rpm does the same for the thirteenth. Any other stall speed, with no speed-locked teeth, sends the investigation to the mechanical and control rows below.

Why the second transformer made starts worse #

Two identical 13/20 MVA transformers now run in parallel, each 10.5% impedance at 20 MVA with its own 6% current-limiting reactor, sharing about 5 MW of other load. Two identical impedances in parallel halve, to roughly 5.25% on the same base from the pair, so the bus holds up and the observed dip stays small where the single dedicated unit sagged far deeper. To predict that dip rather than measure it, the calculation in estimating voltage sag from motor inrush current converts source impedance and inrush into the expected depression.

Better voltage made the start worse, and the crawl mechanism says why. Against the stiff pair the motor would pull its full locked-rotor current, so the starter fires its SCRs late to hold the limit - small conduction angles, rich harmonics, strong seventh-harmonic torque. Against the weak single unit the sag itself held current down, the starter ran closer to full conduction, and the start went through. A stronger source producing a failed start is the signature of a harmonic-torque stall, not a supply problem. Confirm it by comparing the recorded conduction angle, or a harmonic snapshot taken from the metering CTs and PTs, between the two configurations.

Ruling out the mechanical suspects #

The mechanical checks below mean opening a coupling guard or a terminal box on a 6 kV machine: lock out the supply and test for absence of voltage before starting. NFPA 70E, 2024 edition, the US standard for electrical work practices, and your site program set the procedure and the protective equipment; confirm what applies with the authority having jurisdiction and the equipment documentation, and take every start-time electrical reading through the installed metering transformers.

What you see What it points to Deciding check
Shaft parks near a crawl speed, teeth locked to rotation Harmonic crawl under SCR phase-back Tachometer reading during the stall
Vibration with no speed-linked current teeth Balance, alignment or bearings Vibration spectrum during a start; bearing defect frequencies run far above 3.6 Hz
Suspected axial rotor movement Thrust or clearance problem - unproven here Measure axial float and thrust clearance with the motor locked out; do not infer it from sound or current traces
Teeth appear only while the current loop is active Starter control interaction Starter event log and the manufacturer's review of the firing method for this model
Thermal capacity trending toward a limit over repeated 20 s starts Start duty exceeded Starter thermal model against the data sheet's starts-per-hour and start-duration limits

The suspected axial movement was never established here - ears and current traces together are not an axial measurement. A crawl shakes the whole machine at rotational frequency with nothing mechanically wrong, which is why the speed reading, not the vibration, decides.

Changes that clear a crawl-limited start #

  1. Raise the current limit. The setpoint sits well below what the motor itself draws when line-started, and each step of limit lets the starter apply more voltage - torque rises with the square of motor-terminal voltage. Check the data sheet's permitted start current and duration, and the starter's rating, before moving it.
  2. Spend less time in the crawl band. A shorter ramp, or a current ramp that starts high, carries the machine through 150-250 rpm quickly instead of parking it there. A long voltage ramp into a current-limited plateau is close to the worst shape for a motor with a seventh-harmonic dip.
  3. Bring in the starter manufacturer. The envelope teeth can be current-loop interaction, and the firing method is documented for the model; the manufacturer's application group is the right path for that and for any change to the start-time and bypass-speed program.
  4. Interim configuration. The single dedicated transformer started this motor before, and running that arrangement while the limit and ramp are reworked is defensible - but it trades motor voltage for harmonic content and is a workaround, not a repair.

With the limit raised and the dwell shortened, the motor should pass the one-seventh point without parking. If it still stalls at the same speed under the new settings, the crawl diagnosis was wrong and the mechanical row of the table is next.

Questions asked

How do I measure shaft speed during an aborted start?

Aim a photo tachometer at reflective tape on the shaft end, or use a stroboscope, from outside the guards. Non-contact only: nothing gets held against the shaft of a running 6 kV machine. If the drive end has a key phasor, log that instead. Mark the same timebase as the current trace so the tooth rate and rotational speed can be compared directly.

Couldn't the vibration still be axial rotor movement?

It could, which is why the speed reading decides. A rotor shuttling on its thrust face also pulses once per revolution, but a crawl shakes the machine at rotational frequency with nothing mechanically wrong, and bearing or thrust defects show frequencies far above the 3.6 Hz heard here. Measure axial float and thrust clearance with the motor locked out before condemning either.

Why did one transformer start the motor and two fail?

The weak source sagged enough that the starter's SCRs ran nearly wide open, so the harmonics that feed crawl torque stayed small. Paralleling roughly halved the source impedance, the bus held near nameplate voltage, and the starter had to fire late to hold the limit, adding chopping and harmonic torque until the motor parked. Comparing the recorded conduction angle between the two configurations confirms it.

Can the 470% limit be raised without damaging the motor?

The motor itself draws about 597% of rated current on a line start, so 470% is a starter choice, not a motor limit. What bounds the change is thermal duty: the data sheet's permitted start duration at that current and its starts-per-hour limit, plus the starter's own rating. Step the limit up inside those numbers and shorten the time spent below 250 rpm.

What if the stall speed is nowhere near either crawl point?

Then crawling is the wrong diagnosis for your machine. Work the other rows: a vibration spectrum for balance and bearings, axial float and thrust clearance with the motor locked out, and the starter's event log for control interaction. A stall that comes with falling terminal voltage across many speeds points back at the supply instead.

Keep reading

  • Selection guide

    Setting overload relays for high-inertia motor starts

    Set the current dial at the motor's nameplate full-load current and buy starting time with the trip class, not with a higher setting: Class 10 holds starts up to about 7 s at 600 percent, Class 20 to about 14 s, Class 30 to about 21 s. Longer starts need reduced-current starting, not a bigger relay.

    Motors and motor starters

  • Troubleshooting

    Why a single phase motor stalls on start at 200 V

    The motor stalls because 200 V at its terminals leaves about 69% of rated starting torque — torque varies with the square of voltage — and the primed pump needs more than that. Recover the margin by starting against a throttled discharge, cutting the 20 V feeder drop with a step-up/step-down transformer pair, or converting to a three-phase motor and a drive sized for single-phase input.

    Motors and motor starters

  • How-to

    Choosing a start capacitor for a 1/4 HP 120 V motor rewind

    Install 160 µF, inside the 100-200 µF range for this size, as the start capacitor on the 56-turn, 22 AWG start winding of a 1/4 HP, 4-pole motor, then verify by measuring start current and switch opening. The winding impedance, not the horsepower, fixes the value.

    Motors and motor starters