Troubleshooting
Why a VFD trips overcurrent the instant the motor moves
Short answer
A trip a fraction of a second after the shaft first moves is a motor-circuit fault until the meter proves otherwise: the 17 A drive holds a 1.75× margin over the motor's 9.7 A full-load current, so acceleration cannot explain it. Verify the nine-lead grouping, measure resistance between all three pairs with the drive disconnected, then check torque compensation — a bigger drive is last.
On this page
- What the OC-r code does and does not prove
- Why inrush is the wrong suspect
- Working the case: 17 A drive against the 2 HP pump
- Check the nine leads before any parameter
- The decisive test: resistance between all three pairs
- Settings to touch only after the circuit passes
- Why the no-load 208 V reading proves little
- Questions asked
A drive that trips overcurrent a fraction of a second after the shaft first turns is telling you the motor circuit is faulty, not that the pump outran its drive. The 17 A rated output of this 4.0 kW unit sits about 1.75 times above the 9.7 A full-load current of the 2 HP three-phase pump it feeds, and no healthy acceleration on a working ramp spends that margin in half a second. Work it in this order: verify the nine-lead grouping and the splices, measure resistance between all three motor pairs with the drive disconnected, then look at torque compensation and acceleration time. A larger drive is the last move, and on this evidence it is the wrong one.
What the OC-r code does and does not prove #
The manual behind this drive labels OC-r a steady-state overcurrent, lists overload or a component failure as the cause, and points you at the motor load. That label is not a measurement. In this failure the motor never reaches any steady state — it trips within a fraction of a second of first movement. Treat the displayed code as the code, and verify the cause separately: the drive's own fault table and fault history for the exact model in front of you are the authority on what OC-r covers.
A trip this fast means output current reached the drive's protection threshold almost immediately after the inverter was told to energize the motor. Current that rises that quickly is the signature of a fault-level circuit — a phase-to-phase short, a wrong lead grouping, or a seized load — not of a pump that needs a longer ramp.
Why inrush is the wrong suspect #
Across-the-line starting current, locked-rotor current at several times full load, happens when full voltage at full frequency hits a stationary rotor. A drive never does that. It starts the motor at low frequency and controlled voltage, ramps both, and limits current along the way; controlling acceleration current is the drive's defining job.
There is therefore no 20 A or 30 A inrush figure to estimate from this nameplate, and any number offered would be invented. What the drive draws from the single-phase line at start is its own charging and load current, not motor locked-rotor current. If a genuine capacity question ever arises — a different motor, real overload duty — sizing a VFD for a three-phase motor on single-phase input covers the derating that single-phase service imposes.
Working the case: 17 A drive against the 2 HP pump #
The inputs, with units and sources:
- Drive rated output current: 17 A, three-phase output, 208–240 V; input 220 V single-phase, 48–63 Hz — the drive's rating as its documentation states it. Confirm in the manual that 17 A is continuous output current and not the input figure; on a single-phase-input drive those are different quantities.
- Motor full-load current: 9.7 A at 208 V and 9.1 A at 230 V, at 60 Hz and 3450 rpm — the pump motor nameplate.
- Motor service-factor amps: 11.6 A at 208 V and 10.6 A at 230 V — the same nameplate.
- Observed behavior: the shaft begins to turn, then OC-r within a fraction of a second.
The rule in words: a drive's continuous output rating must equal or exceed the motor's full-load current at the voltage actually supplied, and the margin between them is the ratio of the two.
The arithmetic:
- 17 A ÷ 9.7 A = 1.75 — margin over full-load current at the 208 V connection
- 17 A ÷ 9.1 A = 1.87 — at the 230 V connection
- 17 A ÷ 11.6 A = 1.47 — the tightest case, service-factor amps at 208 V
The result: the continuous rating stands between 1.47 and 1.87 times every current this motor can legitimately draw. The decision: a drive below about 1.0, rated output under motor full-load current, is undersized and justifies a bigger unit, and this one is nowhere near that line. A capacity shortfall cannot explain a trip a fraction of a second after first movement. Where the drive asks for motor rated current, enter 9.7 A for the 208 V connection — full-load amps, never service-factor amps.
Check the nine leads before any parameter #
The grouping described for the low-voltage connection — T4, T5 and T6 tied together, then T1+T7, T2+T8 and T3+T9 out to the three drive terminals — is the standard low-voltage arrangement for a nine-lead dual-voltage motor, in either a wye or a delta winding. Described and landed are different things. The splices were soldered and taped by hand, and the reference diagram the work followed mislabels the third line pair as L2 twice, so the diagram contains at least one error of its own. Walk wiring a nine-lead dual-voltage 3-phase motor from 460 V to 230 V against the motor's own lead markings, not memory, and confirm every numbered lead at the motor before trusting any splice.
Inspect the splice area physically: one strand escaping a solder joint, or tape pinched between two groups, is enough to short two phases of a 230 V winding. If the motor was moved between voltage connections in the past, rewiring a nine-lead dual-voltage motor from 440 V to 220 V for a VFD lays out the full lead map for that change.
The decisive test: resistance between all three pairs #
This procedure puts you at the drive terminals. De-energize the input, lock it out, verify absence of voltage at the input terminals, and follow the drive's documented DC-bus discharge procedure before touching anything — the bus holds a charge after power-off. NFPA 70E, 2024 edition, covers the de-energized-work and voltage-verification practices this step depends on; your site safety program and the drive manual govern the exact procedure.
With the supply proven off:
- Disconnect the motor conductors from the U, V and W terminals so nothing is measured through the drive electronics.
- Measure resistance group to group: T1+T7 to T2+T8, T2+T8 to T3+T9, and T3+T9 back to T1+T7.
- Null the meter's lead resistance, or record it and subtract — these readings are small and lead resistance distorts them.
- Compare all three readings and read the pattern:
| Pattern across the three pairs | What it points to | Action |
|---|---|---|
| All three equal and finite | A balanced, intact circuit | Move on to the parameter checks |
| One pair much lower than the other two | Phase-to-phase short in the cable or a splice, or a wrong grouping | Find it before any further start attempts |
| One pair open or far higher | Broken splice, misidentified lead, poor joint | Re-terminate and re-measure |
Once the balance is proven, check insulation from the winding to the frame with a megohmmeter at a test voltage the motor documentation allows for this winding, drive still disconnected. Then restart.
Settings to touch only after the circuit passes #
- Torque compensation (PN13 on this drive) and the frequency band it applies over (PN14): boost adds voltage at low frequency to break the load away, and set too high it pours current into a motor that is not moving. Set PN13 to zero or the manual's minimum and retest — if the start improves, the boost was working against you.
- Acceleration time (PN08, with PN29 as the second ramp): for a pump on a proven circuit, 15 to 20 seconds is a sound commissioning ramp. The ramp runs across the frequency span in use, so confirm how this drive defines the interval before comparing settings.
- Initial start frequency (PN02): keep it at the manual's default or lower — stepping a stationary rotor into a high start frequency creates instant high-slip current.
- Motor data: the parameter list for this drive shows no motor rated current or voltage entry, but if the full set includes them, set rated current to the 9.7 A nameplate figure and rated frequency to 60 Hz. Every drive that offers such a setting wants nameplate full-load values, not service-factor amps.
- Output limits (PN10, PN11, PN12): 60 Hz rated frequency, with the maximum and minimum set to the span the pump actually needs.
Why the no-load 208 V reading proves little #
Equal 208 V readings across UV, VW and UW with the motor disconnected show only that all three inverter legs switch. A conventional averaging multimeter on a PWM output reports something between the pulses, not a true output voltage, so it says nothing about loaded performance. Treat that check as a power-up confirmation, not evidence the drive can start this pump.
The decision, in order: prove the motor circuit with the three resistance readings, zero the torque compensation, set a 15-second ramp with correct motor data, and restart. If the drive still trips the instant the shaft moves on a proven circuit, the evidence points inside the drive or the motor, and measurement — not a larger drive — is the next step, because nothing in this margin supports buying capacity the motor does not need.
Questions asked
Can the motor's starting inrush still trip a 17 A drive?
Not the way it would across the line. The drive starts at low frequency and limits current itself, so the comparison that matters is 17 A of rated output against 9.7 A of full-load current, a 1.75× margin. A genuine capacity problem announces itself differently: current climbing during acceleration and a trip seconds into the ramp, not a fraction of a second after the shaft first twitches.
Where exactly do I take the three resistance readings?
At the motor's T-leads first, with the cable off the drive: T1+T7 to T2+T8, T2+T8 to T3+T9, and T3+T9 back to T1+T7. Then repeat at the drive end of the cable with the conductors lifted from U, V and W. Equal readings at the motor but a bad pair at the drive end isolates the fault to the cable or splices rather than the winding.
Is the current to program 10.7 A or 11.6 A?
Neither. One document quotes 10.7 A while the nameplate range is 11.6 to 10.6 A, so resolve it at the motor's own nameplate, which wins. The value a drive wants as motor rated current is full-load amps at the connected voltage: 9.7 A at 208 V or 9.1 A at 230 V here. Service-factor amps describe what the motor tolerates, not a protection setting.
The drive is fed from two separate single-pole breakers. Does that matter?
Yes. Two independently tripping breakers can leave one supply leg energized when the other opens, so the drive is never safely isolated on one leg. Feed it from one two-pole breaker, or a listed handle-tied pair where permitted, so both ungrounded conductors open together. NFPA 70, the National Electrical Code (2023 edition), governs branch-circuit disconnecting arrangements; confirm the local rule with the authority having jurisdiction.
Should I just buy a larger drive?
Not for this symptom. With 17 A of rated output against 11.6 A of service-factor current, a 1.47× margin, a capacity shortfall cannot explain a trip a fraction of a second after first movement. A larger drive on the same fault only trips later or at higher current while dumping more energy into the short. Prove the circuit first; the meter is cheaper than the drive.