Explainer
How a VFD works: rectifier, DC bus and inverter stages
Short answer
A VFD rectifies the incoming AC to DC — about 648 V DC on a 480 V supply with a six-diode front end — then switches that bus with IGBTs to build variable-frequency output. Speed follows N = 120 × f / P and torque follows the volts-per-hertz ratio. The worked example turns the 1.35 × line rule into a 648 V DC check you can make at the drive.
On this page
- The power path in three stages
- The rectifier: AC to DC at the line terminals
- The DC bus: smoothing, storage and the output ceiling
- DC bus voltage on a 480 V supply with a six-diode bridge
- The inverter: switching the bus into variable AC
- Speed follows frequency, torque follows volts per hertz
- Scalar and vector control
- Where the stages meet the meter
- Questions asked
A variable frequency drive controls an AC motor by doing two conversions in a row: it rectifies the fixed-frequency line supply to DC, then switches that DC back into AC at the frequency and voltage the speed reference calls for. Three stages do the work — rectifier, DC bus, inverter. On a 480 V three-phase supply with a six-diode front end, the bus sits near 648 V DC, speed follows N = 120 × f / P, and torque follows the volts-per-hertz ratio the drive holds between output voltage and frequency. Every trip you chase on the floor maps back to one of those stages. This article walks the power path in order, works the DC bus number for a drive on that supply, and ends with the control modes that sit on top of it.
The power path in three stages #
The rectifier takes the incoming AC and produces pulsating DC: general-purpose drives use a diode bridge, and larger drives may use thyristors (SCRs) so the bus charges under control instead of connecting abruptly. The DC bus smooths that pulsation with a capacitor bank and stores energy between line pulses. The inverter switches the bus voltage across the motor windings with IGBTs, building a pulse train whose fundamental is the frequency and voltage the control loop commanded. Each stage carries one number you can read: line voltage at the input terminals, bus voltage on the drive's DC monitor, and output current on the motor leads.
| Stage | Converts | Governing relation | Reference reading |
|---|---|---|---|
| Rectifier | line AC to pulsating DC | bus averages 1.35 × line-to-line RMS | 648 V DC on a 480 V supply |
| DC bus | pulsating DC to smooth DC | capacitors charge toward √2 × line-to-line RMS | up to about 679 V DC |
| Inverter | DC to variable AC | duty cycle sets voltage, pattern sets frequency | speed per 120 × f / P |
The rectifier: AC to DC at the line terminals #
Six diodes in a three-phase bridge form the standard front end. Each diode conducts when the line-to-line pair behind it holds the highest instantaneous voltage, so the bridge delivers six current pulses per supply cycle — the six-pulse connection behind the 1.35 bus factor.
Because conduction happens only near the voltage peaks, the drive draws current from the line in narrow pulses rich in harmonics rather than as a smooth sine. That pulsed draw is why conductors, reactors and fuses on the drive's line side are sized for a distorted waveform, and it is the problem a reactor is there to soften — choosing a line reactor or motor reactor for a VFD walks through that decision.
The DC bus: smoothing, storage and the output ceiling #
The bus capacitor bank filters the six-pulse ripple and carries the motor through the intervals when no rectifier pair is conducting. Its voltage is the ceiling on everything downstream: the inverter cannot build an output fundamental larger than the bus supports, so a sagging supply lowers the maximum motor voltage and, with it, the torque available at full speed.
The same bank is where deceleration energy lands. A high-inertia load driven down the ramp turns the motor into a generator; a diode front end cannot push that energy back to the line, so the bus climbs until you lengthen the deceleration ramp or a braking resistor burns the excess as heat. The drive's undervoltage and overvoltage protections both watch this bus, which is why a supply dip and an overhauling load can trip the same stage from opposite directions.
One safety rule belongs here: the capacitors hold a hazardous charge after the line disconnect opens — respect the discharge interval in the manual before touching the DC terminals.
DC bus voltage on a 480 V supply with a six-diode bridge #
Inputs, with their sources: supply of 480 V line-to-line RMS, three-phase, 60 Hz, measured at the drive's line terminals — a nominal plant value used as this example's case; front end of six diodes in a three-phase bridge — the standard construction on general-purpose drives, confirmed for your unit from its manual; the two bridge relations — average DC output equals 1.35 × line-to-line RMS (from 3√2/π = 1.35) and capacitor charge ceiling equals √2 ≈ 1.414 × line-to-line RMS.
Rule in words: a six-pulse diode bridge averages 1.35 times the line-to-line RMS voltage, while a capacitor-input bus charges toward the line-to-line peak and rides nearer that peak at light load, sagging toward the average as load and ripple rise.
Arithmetic, with the nominal 480 V input above:
- Average bus figure: 1.35 × 480 V = 648 V DC.
- Light-load charge ceiling: 1.414 × the same input ≈ 679 V DC.
- Scaling check: a 5 % low line of 456 V gives 1.35 × 456 V ≈ 616 V DC — a weak supply, not a failed rectifier.
- Lost input phase: the two healthy lines then feed the bridge as a single-phase pair, which averages 0.90 × RMS: 0.90 × the nominal value ≈ 432 V DC, exactly two thirds of the healthy figure.
Result: a healthy drive with a six-diode front end on that supply reads roughly 648 to 679 V DC on the bus — nearer 648 V under load, nearer 679 V at idle.
Decision: read the bus from the drive's own monitor parameter first; if you probe, use the DC measurement points the manual designates and a meter rated for the bus voltage. Bus in the 648–679 V band and scaling with your measured line voltage — the supply and rectifier are healthy. Bus near 432 V on a nominal line — one input phase is dead or its fuse has opened; check the input fuses and terminal tightness before condemning the drive. Bus that cannot reach the figure your line voltage predicts — suspect lost diode capacity or tired capacitors, and confirm against the nominal bus value the manual for your model states. Treat 648 V as the estimate your reading should land near, not a factory tolerance.
The inverter: switching the bus into variable AC #
Three half-bridges of IGBTs connect the motor phases to the positive and negative DC rails. The control loop times each switch so that, over one carrier period, the share of time a phase spends on the positive rail — its duty cycle — equals the voltage the loop wants, and the switching pattern's fundamental repeats at the commanded frequency. The motor's own inductance turns the pulse train into near-sinusoidal current: the motor is the filter.
Two practical consequences follow. The output is PWM, not a sine, so an average-reading meter reports nonsense on it — measuring VFD and soft starter current with the right meter covers what to use on either side of the drive. And each IGBT gate needs a driver that lifts the controller's logic-level signal to gate level and, on the high-side switches, follows a potential that swings between the DC rails; driving IGBTs from a 3.3 V DSP using discrete stages shows that interface problem and a discrete-stage solution.
Speed follows frequency, torque follows volts per hertz #
Synchronous speed obeys N = 120 × f / P, with N in rpm, f in Hz and P the pole count. A four-pole motor on 60 Hz runs 1,800 rpm synchronous; the same motor given a 45 Hz reference targets 1,350 rpm, and the induction machine runs slightly below either figure by its slip, set by the load.
Torque comes from air-gap flux, which is proportional to the volts-per-hertz ratio. The drive holds V/f constant from low speed up to the motor's base frequency, which is constant-torque operation. Above base frequency the output voltage is capped near what the bus supports, V/f falls, flux weakens, and torque falls roughly in proportion to speed — the constant-power, field-weakening region.
At low frequency the stator resistance consumes a large share of the small applied voltage, so drives add a voltage boost. Too little boost and the motor stalls on start; too much raises magnetizing current and can trip the drive on overcurrent — why a VFD trips overcurrent the instant the motor moves works that failure from the trip side.
Scalar and vector control #
Scalar (V/Hz) control sets output voltage as a fixed function of output frequency and never measures the motor's state. It suits fans, pumps and any load that needs no precise low-speed torque, and it is the mode that lets one drive run several motors together. On a fan or a centrifugal pump, torque falls with the square of speed and power with the cube — the source of the energy savings — while constant-torque conveyors and hoists give no such reduction and hold the drive near its current rating at low speed.
Vector (field-oriented) control runs a mathematical model of the motor and regulates the torque-producing and flux-producing current components separately, holding rated torque at low speed and responding faster to load steps. It depends on accurate nameplate data and a completed autotune: wrong motor data produces hunting and unexplained overcurrent that look exactly like hardware faults.
Where the stages meet the meter #
Diagnosis follows the power path. Input voltage low or unbalanced points at the supply and rectifier. Bus below the figure the worked example predicts points at a lost phase, an open fuse or weak capacitors. Bus climbing on deceleration points at regeneration — lengthen the ramp or add braking. Output current above the motor nameplate at commanded speed points at the mechanical load or bad V/f data. Reading the stages in order turns "the drive trips" into one measured quantity that crossed one limit, and every one of those quantities is available on the drive's own monitor pages.
Questions asked
Why does a VFD's input current read lower than its output current?
Power in equals power out plus small losses, but the voltages differ. At reduced speed the drive applies reduced voltage, so the motor can draw rated current while taking only a fraction of rated power; the line delivers that same power at full line voltage with less current. The diode front end also draws current in narrow pulses near the voltage peaks, which trims the RMS reading further. Size the feeder from input current; judge the motor from output current.
How long should you wait before touching the DC bus terminals?
Wait the discharge interval printed in the drive's manual before opening it; larger drives commonly specify several minutes. Then measure between the DC+ and DC- terminals and from each DC terminal to ground with a meter rated for the bus voltage, and open the drive only on readings near zero. The bus capacitors hold a charge that can be lethal after the line side is disconnected, because the bleed resistors take minutes, not seconds.
What does the drive's switching frequency setting change?
The inverter output is a train of pulses at the carrier frequency, and the motor's inductance smooths that train into usable current. Raising the carrier lowers audible motor whine and output current ripple; it also raises switching losses in the IGBTs, heats the drive and adds stress on long motor cables. Set it low for large frames and long cable runs, and raise it only where noise matters and the manual's derating rules allow.
Can one VFD run several motors at the same time?
Yes, in scalar V/Hz mode: every motor sees the same output frequency, each motor keeps its own overload relay, and the drive is sized for the sum of the connected motor currents. Vector control does not suit that connection, because its motor model assumes a single machine and cannot separate several motors' currents. Where combined accelerating current would exceed the drive's overload capacity, start the motors sequentially.