Troubleshooting
Finding a 113 V drop between a VFD and the motor terminals
Short answer
The drop is real, it lives in the path between the drive lugs and the terminal box, and it works out to about 0.36 Ω per phase — enough to dissipate roughly 11 kW per phase if it is resistance. Verify the reading with a drive-rated meter, then find it with an infrared scan under load and a micro-ohmmeter on every joint; the motor is downstream of both measurement points and is not the cause.
On this page
A 113 V line-to-line gap between the VFD output lugs and the motor terminal box at 180 A is not a metering curiosity. It implies about 0.36 Ω of series impedance per phase in the path between those two points, and if that impedance is resistance it is dissipating about 11.7 kW per phase — roughly 35 kW across the three. Drive-measurement guidance caps the drive-to-motor drop at 3% of output; this case sits at 24%. Nothing downstream of the terminal-box lugs can produce the reading, so the stator is not the suspect. The hunt is a loose or oxidized lug, a failing output contactor pole, a damaged filter or reactor leg, or a crimp that has lost strands — found with an infrared scan under load and a micro-ohmmeter, in that order, after the readings are confirmed with a drive-rated instrument.
The arithmetic that commits you #
The reported case: a 110 kW, 415 V, 188 A full-load motor on a 132 kW drive, pumping at about 180 A. At the drive output the line-to-line readings were 460 V, 464 V and 466 V (average 463 V). At the motor terminal box on the same run: 343 V, 370 V and 338 V (average 350 V). These are as-measured field readings; the verification step comes next, but the arithmetic they drive is what commits you.
Treat the path as a series circuit and assume balanced sine quantities — an estimate for diagnosis:
- Drop: 463 V − 350 V = 113 V, which is 113 ÷ 463 = 24% of the drive output.
- Per phase: 113 V ÷ √3 = 65.2 V. At 180 A the series impedance is 65.2 V ÷ 180 A = 0.36 Ω per phase.
- Heat, if that impedance is resistance: 3 × (180 A)² × 0.36 Ω ≈ 35 kW, about 11.7 kW in each phase.
- Scale check: 80 m of 70 mm² copper is 1.72 × 10⁻⁸ Ω·m × 80 m ÷ 70 × 10⁻⁶ m² ≈ 0.02 Ω per conductor. A healthy run is an order of magnitude below 0.36 Ω, so roughly 0.3 Ω in this path is unexplained.
- Direction: the two lowest motor-end readings, 343 V (R–Y) and 338 V (B–R), share the red conductor. Start on the red path — its conductor, both lugs, its contactor pole, its filter leg.
- Unbalance: at the motor end, (370 − 350.3) ÷ 350.3 = 5.6% deviation from the mean; at the drive end the same math gives 0.6%. The path creates the unbalance along with the drop.
Guidance published by instrument maker Fluke for drive measurements caps the drive-to-motor voltage drop at 3% and flags phase unbalance above 2% as a problem. Against 24% and 5.6%, the decision is made before any panel opens.
Confirm the number before you open anything #
The output of a VFD is PWM, not a sine wave. A general-purpose meter without true-RMS response and the bandwidth for drive output reads switching residue as voltage, and the same meter can read differently at each end because cable capacitance smooths part of that content before it reaches the motor. Use one motor-drive analyzer, or a multichannel scope with rated probes, at both ends at a fixed output frequency, all three line-to-line pairs, and read the drive's own displayed voltage at the same time. The same instrument discipline applies to current, as measuring VFD and soft starter current with the right meter covers.
The 460 V reading also fails a hard sanity check. A 415 V line rectifies to a DC bus of 1.35 × 415 = 560 V, and the largest sine fundamental the inverter can synthesize from that bus is 560 V ÷ √2 ≈ 396 V line-to-line; even six-step operation tops out near 437 V. A true 460 V fundamental is not available from that supply, so the drive-end reading carries switching content. If the real value there is near 396 V, the drop is nearer 46 V and the impedance nearer 0.15 Ω — about 15 kW if resistive. Every branch of that range still fails the ceiling five times over and still sends you on the same hunt.
While the drive data is in front of you, compare its motor pattern with the nameplate: a 460 V pattern on a 415 V, 60 Hz machine overfluxes it by 460 ÷ 415 ≈ 11%, which raises magnetizing current and winding temperature over hours. A second identical pump on the same bus showing the same creep makes the shared parameter set — or the shared bus — the first thing to rule out.
Why the stator is cleared, and what the phase roll proved #
The drop appears between two physical points. Everything that can create it — cable, lugs, splices, an output contactor, a filter or reactor — sits between those points; the stator is downstream of the terminal-box lugs and cannot subtract voltage from a measurement taken at them.
The test results agree. Better than 1000 MΩ to ground and coil-to-coil clears the insulation system, and the 0.08 Ω figure is a winding DC resistance, which clears a fully open winding. Two things that testing cannot do: an insulation test sees parallel paths to ground, never a series joint; and a partially open winding can carry load while dropping voltage. So re-measure DC resistance across all three line pairs and compare them with each other — on this delta machine each reading is one winding in parallel with the other two in series, and the three should match closely. Where you test insulation from also changes what the result covers, as insulation resistance testing from switchgear vs motor terminals sets out.
The phase roll — R to Y, Y to B, B to R at the box — keeps rotation, where swapping any two phases reverses a three-phase motor. It also relocates the small current unbalance, which did not stay with one winding: the asymmetry lives upstream of the box. At 2.4% — (187 − 182.7) ÷ 182.7 — that unbalance is marginal in any case; the drop is the fault, not the wobble.
Where kilowatts hide from a hand check #
A walk-down that finds nothing warm rules out less than it seems, because the candidates sit where a hand cannot: the lug under the terminal-block cover, a splice in the tray, an output contactor pole, the filter or reactor inside the drive cubicle, a crimp that has lost most of its strands. Under load a thermal camera sees what a hand misses — a 0.3 Ω joint at 180 A dissipates (180 A)² × 0.3 Ω = 9.7 kW and will be the brightest object in the frame. Scan at operating load, not at idle.
If no resistive hot spot shows anywhere in the path, the impedance is largely reactive and the prime suspect becomes the output filter or reactor: a failed component in one leg changes series impedance without glowing. What load reactors, dV/dt filters and sine filters on a VFD output each do determines what a bypass test changes, so know which one is in the cabinet before lifting it. Isolate and bypass it exactly as the drive and filter documentation directs, then re-measure motor-end voltage at load.
The sequence, in order #
- De-energize and verify before any hands-on work. Lock out the drive input, wait the DC-bus discharge time stated in the drive manual, and test for absence of voltage at the input and output terminals with a meter rated for the measurement category. Everything below that opens a panel, box or terminal follows this step.
- Confirm the voltages with one motor-drive analyzer at both ends at a fixed frequency, all three line-to-line pairs, alongside the drive's displayed output. Read the supply voltage and the drive's motor-data pattern against the 415 V, 60 Hz nameplate while you are there.
- Scan under load. Run at normal duty and thermal-image every point from output lugs through any contactor and filter to the terminal box. Scanning open, energized equipment is energized work: NFPA 70E, 2024 edition, sets the safe-work framework for it — qualified person, arc-flash boundary, PPE, energized-work permit — so confirm the requirements with your site program and the authority having jurisdiction before the camera comes out.
- Micro-ohmmeter every bolted joint with a 10 A or 100 A digital low-resistance ohmmeter, all three phases of each joint type. More than 20% deviation between phases fails the joint. Red path first.
- Bypass-test the output filter or reactor per its documentation and re-measure motor-end voltage at load.
- Test the cable. Insulation at 1000 V DC for 60 s, phase-to-phase and phase-to-ground, disconnected at both ends — then DLRO each conductor end to end, because insulation testing cannot find a series fault.
- Re-torque to the documented value with a calibrated wrench; typical published ranges for copper lugs run 35–40 N·m on M10, 50–60 N·m on M12 and 80–100 N·m on M16. Re-terminate anything discolored rather than tightening it.
- Re-check winding resistance across the three line pairs at the box; a climbing or unequal pair flags the joint or the winding.
- Run the motor uncoupled at nameplate voltage and frequency and record current and terminal voltage.
What the no-load run should show #
The direct answer to the decoupling question: a healthy motor of this size and pole count takes 25–35% of full-load current uncoupled at rated voltage and frequency — 47 to 66 A on a 188 A machine, at a power factor around 0.1 to 0.2, with slip close to zero. Then read the branches:
- 47–66 A with terminal voltage within about 2–3% of the drive reading: the motor is sound and the drop lives in the loaded path. Re-couple and confirm current back at the 167–170 A baseline.
- Well above 66 A: suspect the drive's motor data and V/Hz pattern before the machine — overfluxing shows up at no load first.
- More than about 5% current unbalance between phases: repeat the winding-resistance comparison before re-coupling.
Reading the inhibit message #
An inhibit is a displayed state, not a cause. Pull the drive's fault history and read the fault table for the installed model before assigning one — that table, not intuition, says what inhibited the drive. On drives of this power class the state commonly maps to a digital input configured as an external fault: a motor PTC thermistor, a winding or bearing temperature switch, or a plant interlock wired to that drive. Find the terminal in the wiring diagram and measure its state when the drive inhibits; the input asserts before the trip and names the sending device.
The thermal argument does not support an insulation cause: Class H permits a 180 °C hotspot, and the winding was measured at 92 °C in a 40 °C ambient. If a thermistor input is doing the inhibiting, suspect its sensor circuit, not the insulation system. The identical pump that trips without the message says the underlying condition — current rising as terminal voltage falls — is shared, while the annunciation is wired differently on each drive. Fix the drop and both pumps' behavior should follow.
The decision #
| Measurement | This case | Target |
|---|---|---|
| Drive-to-motor line-to-line drop | 113 V, 24% | 3% of output or less |
| Motor-end voltage unbalance | 5.6% | 2% or less |
| Line current at the duty point | 183–184 A | the 167–170 A baseline |
| Uncoupled current at rated voltage and frequency | untested | 47–66 A |
Stop scheduling production around the 8–10 hour trip. Somewhere between those two measurement points something is dissipating between 15 and 35 kW, cooking the joint it lives in and pulling current up as the terminal voltage falls. Open the red path first — the arithmetic already put you there — and work the sequence in order. If the scan and the micro-ohmmeter come back clean and the filter bypass changes nothing, treat the drop figure as a measurement artifact: re-verify with the analyzer, then chase the 11% overfluxing pattern or the pump hydraulics for the current rise. After any repair, clear all four rows of the table on the first full shift, with the uncoupled run before you re-couple.
Questions asked
How much voltage drop is acceptable between a VFD and the motor?
Field guidance for drive measurements puts the ceiling at 3% of drive output and flags phase unbalance above 2% as a problem. On a 463 V output, 3% is about 14 V; the case measured 113 V, roughly eight times over. Unbalance at the motor end came in at 5.6%, nearly triple the flagged level, while the drive end read 0.6% — the path created it, not the supply.
How much current should the motor draw uncoupled at no load?
Roughly 25–35% of full-load current for a four-pole machine of this size: 47 to 66 A on a 188 A motor, at rated voltage and frequency. Two-pole machines run lower; slower pole counts and smaller frames run higher. Well above that band, check the drive's motor data and V/Hz pattern before condemning the motor — overfluxing shows up first at no load.
Why does one pump show inhibit when the identical pump does not?
The inhibit state usually comes from a drive input configured as an external fault — a thermistor, a temperature switch, an interlock — wired to that one drive, or from a model-specific internal condition. Pull both drives' fault histories and compare the logged causes; a shared trip with different messages says the wiring differs, not the fault.
Can an ordinary multimeter read VFD output voltage?
Often not usefully. The output is PWM, and a meter must be true-RMS with bandwidth specified for drive output, or it reads switching residue as voltage — one reason a 415 V feed appeared to show 460 V it cannot produce. A motor-drive analyzer or a scope with rated probes, used at both ends, is the reference, and the drive's display of the fundamental it regulates is the cross-check.
Why did the current climb from 167 A with no load change?
Terminal voltage fell, so delivering the same pump torque at the same frequency takes more slip, and slip costs current: 167 A drifted to 184 A while grease, oil and alignment checks changed nothing. The extra current heats the rotor and stator, which is why the trip arrives after 8–10 hours rather than instantly. Restore the terminal voltage and the current follows it back down.