Current IntelPower LibraryShop main store

Explainer

Why a cam switch contact sequence comes before motor wiring

Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

A reversing cam switch's function marking is not its wiring diagram: an A300-marked switch is not the published three-phase reversing program. De-energize and verify, measure which of the 12 terminal pairs conduct in every handle position, record the installed jumpers, pull the exact motor's connection diagram, and only then derive the 230 V terminal assignments.

On this page
  1. The marking on the switch is not the diagram
  2. De-energize, then read every pair the switch can make
  3. A worked map from measured contacts to terminal assignments
  4. Get the motor's own connection diagram
  5. Land the leads, then prove the circuit before the first start
  6. Questions asked

Wiring a 115/230 V capacitor-start motor to a reversing cam switch cannot be done from the lead labels and the function code stamped on the switch body. The A300 marking on this 12-terminal switch names a factory contact program; it is not a connection diagram, and a published reversing diagram for a different program describes contacts this switch may not have. The working order is fixed: de-energize the circuit and verify the absence of voltage, measure which pairs of the twelve terminals conduct in every handle position with the installed jumpers recorded first, pull the connection diagram for the exact motor, and only then derive the terminal assignments for the 230 V, two-hot supply. Map the switch, match the motor, then wire.

The marking on the switch is not the diagram #

A cam switch body carries a short function code — this one reads A300 — that identifies which cam set the factory installed: which terminal pairs close in which handle position. The terminal count tells you nothing about that. Catalog wiring pages are published per function code, and the reversing function shown for three-phase motors under a different code, A401, closes different pairs than the program behind A300; applying that page to this switch is guesswork across the full supply voltage. Even the correct published page can mislead, because switches get altered in service: the jumpers already joining 7 to 11 and 5 to 9 merge four terminals into two nodes, and no catalog page knows that. The decision is that the meter decides what this physical switch does today, and a published diagram for the same code, if one turns up, serves only as a cross-check afterward.

De-energize, then read every pair the switch can make #

Before the cover comes off or a probe touches anything: NFPA 70E, 2024 edition, Article 120 covers establishing an electrically safe work condition — disconnect from the supply, lock and tag the disconnect, prove the meter on a known live source, then verify the absence of voltage at the switch terminals. Confirm the details with your authority having jurisdiction and the plant's electrical safety program.

Then map the switch dead:

  1. Disconnect both incoming conductors and every motor lead from the switch, so only the switch is under test. A winding or capacitor left hanging on a terminal creates false continuity paths.
  2. Photograph the wiring and write down the handle positions before moving anything. Record the jumpers first: 7 to 11 and 5 to 9 will read closed in every position, because they are wires, not contacts. Merge each jumpered pair into one node — 5 and 9 become one node, 7 and 11 become another.
  3. Size the job: 12 terminals give 12 × 11 / 2 = 66 possible pairs, and three handle positions turn that into up to 66 × 3 = 198 continuity readings. In practice most pairs read open on the first touch, and a sweep that holds one probe on terminal 1 while the other visits 2 through 12, then moves to terminal 2 against 3 through 12, and so on, goes faster than the count suggests.
  4. Use the continuity beeper or the low-ohms range of a general-purpose digital multimeter: a few ohms or less means the contacts touch. Log every closed pair per position.
  5. Run the whole table a second time. A worn cam contact that reads closed intermittently shows up between passes, and one flaky pair in the start circuit is enough to make the motor bump the wrong way or refuse to start.

Naming twelve anonymous terminals is the same meter work as identifying unknown terminals on a NEMA Size 1 motor starter. The continuity discipline itself is the one described in how continuity tests establish a cable's wire map, applied there to an instrument cable instead of a switch.

A worked map from measured contacts to terminal assignments #

The table below is an example of the format and the reasoning, built on the jumper pattern this switch carries. It is not the program behind the A300 marking — your meter, not this table, decides what your switch does.

Handle position Pairs that conduct beyond the jumpers
Off none
Forward 1–4, 3–6, 1–5, 3–7
Reverse 1–4, 3–6, 1–7, 3–5

Merge the jumpers and the reading simplifies: node A (5 and 9) touches terminal 1 in Forward and terminal 3 in Reverse; node B (7 and 11) touches terminal 3 in Forward and terminal 1 in Reverse; the pairs 1–4 and 3–6 conduct in both run positions.

Three facts fall out of that table:

  • The pairs stable across both run positions carry the run circuit. The first incoming line conductor lands on terminal 1, one end of the run winding on 4; the second line conductor lands on 3, the other run-winding end on 6. The run connection must be identical in both directions.
  • The pairs that swap carry the start circuit: the start winding, in series with its capacitor and centrifugal switch, lands one end on node A and the other on node B. The jumpers earn their keep here — each gives a swap node two landing terminals.
  • The off position must open everything: both incoming conductors and every winding end. A switch that breaks only one conductor leaves the motor live.

Then the short check, position by position: no conducting path may join the two line terminals directly, and no winding's two ends may join. This example table passes, because nothing bridges node A to node B in any position. A measured pair like 4–6 closed — the two run-winding ends shorted together — rejects the wiring outright, and any position joining the line terminals is a dead short across the supply.

The table cannot tell you which motor lead is which. That comes from the motor.

Get the motor's own connection diagram #

What is visible on this motor is leads T1 through T5 and T8, plus P1 and P2, with T1 routed through a manual reset and T5 routed through the starting capacitor. Visible routing is not a connection diagram. At the higher nameplate voltage, the two run-winding sections of a dual-voltage single-phase motor connect in series, and the lead-to-lead pairs for that connection come only from the diagram for the exact model: the nameplate diagram or the manufacturer's connection data for that catalog number. The standard single-phase terminal markings, T1 through T8 and the P leads, are laid out in motor-winding reference handbooks such as the EASA Electrical Engineering Pocket Handbook; let the model's own diagram govern and use the handbook to read it.

The P leads are the thermal protector. They connect as the diagram shows, in series with the line, and they stay there in both directions of rotation — reversing moves the start circuit, never the protector path. If only three conductors run back from the machine to the motor, the diagram tells you whether the protector, capacitor and centrifugal switch sit inside the motor's conduit box or must be wired outside it.

The manual reset is the protector's reset, and a protector that has just tripped stays open until the windings cool — the reason a thermal overload trips again right after reset.

Reversing itself is one job: rotation changes direction when the start winding's current direction, relative to the run winding, flips. That is the whole purpose of the swap pairs in the map, and the reason the run circuit must not change between the two run positions.

Land the leads, then prove the circuit before the first start #

With the leads landed per the diagram and the measured map, but the supply still disconnected, go position by position: continuity from each incoming line terminal through to its motor lead must match the map, and no position may connect one incoming line terminal to the other.

Ground the frame. NFPA 70 (the National Electrical Code), 2023 edition, Article 250 covers grounding and bonding: connect the motor frame to the equipment grounding conductor. On an older three-wire dryer-style receptacle circuit, confirm with the authority having jurisdiction whether that third conductor is an equipment grounding conductor or a bonded neutral before relying on it.

Then energize under controlled conditions, guards on and hands clear, and expect direction selection in both positions, a normal start, and the protector staying closed. Remove power immediately if direction, starting behavior or protection departs from the mapped sequence.

The decision, case by case:

  • A measured table that opens everything in off, holds the run circuit stable across both run positions, swaps the start circuit between them, and never joins the line terminals to each other: the switch is usable — derive the assignments exactly as in the worked example, against the model's own diagram.
  • A table that swaps the run circuit, bridges the line terminals in any position, or shows intermittent pairs: no motor gets wired to it until the switch is repaired or replaced.
  • A motor with no diagram for its exact model: nothing gets derived by guesswork — obtain the diagram, then wire.

Map first, diagram second, connections third. That order is the answer.

Questions asked

What meter reading counts as a closed contact?

Use the continuity beeper or the low-ohms range of a general-purpose digital multimeter with the switch isolated from the supply and the motor. A pair that beeps or reads only a few ohms is closed; a reading that stays at the meter's overload indication is open. Re-measure any pair that behaves differently between passes, because a worn cam contact can close intermittently, and one intermittent pair in the start circuit is enough to make the motor bump the wrong way or fail to start.

Why does reversing a capacitor-start motor swap only the start circuit?

The run winding's field simply follows the line; swapping its ends changes nothing about rotation direction, because both winding currents would flip together. Rotation follows which way the start winding's field leads the run winding's field. Swapping the start circuit's two line connections while leaving the run circuit untouched flips that relationship and reverses the shaft. That is why the contact map needs one circuit stable and one circuit swapped between the two run positions.

Can I use the catalog diagram for the switch's function code instead of measuring?

Only as a cross-check. The code identifies a factory program, but the switch in front of you may have been altered: jumpers such as the ones joining 7 to 11 and 5 to 9 change which terminals behave as one node, and a marking can be misread or the wrong cam set installed. Measure the physical switch first, then compare the measured table with the published diagram; wire to the measurement, not the code.

Does the starting capacitor move when the direction changes?

No. The capacitor stays in series with the start winding and its centrifugal switch; the swap happens upstream, where the circuit's two ends pick up one line conductor or the other from the switch nodes. Never land the capacitor on a node the map shows dead in one direction, because a start circuit without its feed in reverse will hum and not start, and the capacitor must never sit directly across the two line conductors.

Keep reading

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters

  • Explainer

    What a phase rotation tester tells you about motor direction

    A phase rotation tester fixes the order of the three supply phases at the points you connect, not the way a motor will turn. To predict direction before the first start, match that supply reading with a motor-rotation reading taken while the isolated shaft is turned in the required direction from a recorded viewing end, then land the leads in exactly that pairing. Any two conductors crossed anywhere downstream of the test point reverse the result.

    Motors and motor starters

  • Explainer

    Why a phase sequence relay blocks a motor reverse start

    A phase sequence relay blocks a reverse start because it measures the direction of the rotating field present at its terminals, so it needs no memory of the order that existed before an outage. Wire its output contact in series with the starter coil to block, or let it select between two interlocked contactors that re-swap two phases where the supply order can legitimately change.

    Motors and motor starters