Current IntelPower LibraryShop main store

Troubleshooting

Why a chiller VFD drops out when the second starts

Variable frequency drives Published 6 min read By Current Intel engineering team

Short answer

Before replacing a drive or protection module, capture which signal changes state first when the second chiller starts: a VFD undervoltage trip, lost contactor control power, an opened permissive, or a commanded staging stop. The article gives a capture procedure and a sag calculation that decides whether the shared supply is even a suspect.

On this page
  1. Capture the first signal that changes state
  2. Rule out the commanded stop first
  3. Decide whether the sag can trip the drive
  4. Control power and permissives
  5. The decision for each case
  6. Questions asked

The dropout is almost never a bad drive. When the second chiller in a pair starts, one of four things removes the first one: the drive trips on DC-bus or line undervoltage, the contactor loses control power, a permissive or interlock opens, or the plant controller commands the stop as part of its staging sequence. A handheld meter check and an inrush review cannot separate these, because the first three can happen within a couple of cycles and a meter averages over seconds. Capture the first signal that changes state, then fix that device. The procedure below gives you the first-out, and a sag calculation tells you up front whether the shared supply is even a suspect.

Capture the first signal that changes state #

Before you open any enclosure: de-energize, lock out and tag, and verify absence of voltage at the terminals you will touch. NFPA 70E, the 2024 edition, covers the test-before-touch work practices for electrical work near energized equipment; confirm the details with your authority having jurisdiction and the equipment documentation.

With the panels safe to open, run this sequence on one pair:

  1. Start one chiller and bring it to the load condition that produces the dropout.
  2. On the running chiller's drive input terminals, connect a power-quality recorder meeting IEC 61000-4-30 Class A, set to record RMS voltage every half-cycle and to trigger on a dip. A handheld meter will not see a two-cycle sag; the Class A recorder will, and its timestamp lets you line the trace up with the drive's fault history.
  3. Log the drive run command, each permissive and interlock, the contactor auxiliary contact state, and the contactor coil voltage.
  4. Start the second chiller.
  5. Read out the recorder and the logs, and identify the first signal that moved.

The first change separates the four cases. Everything after this point follows from it.

Rule out the commanded stop first #

If the logs show the run command disappear before anything else moved, the controller stopped the chiller on purpose. Load-matching schemes in chiller plants do exactly this: the drive carries the load alone, and when the second machine starts, the program sheds or shuts the first one as part of the staging sequence. The article on PLC-based chiller staging and rotation system design walks through how those commands are generated. Check the staging program before you touch hardware. If the stop is intended behavior, the fix is in the sequence, not in the electrical distribution.

A no-alarm, no-trip stop also points here, and so does a stop that repeats at the same load step on all three pairs: shared behavior across pairs usually means shared logic, not shared hardware failure.

Decide whether the sag can trip the drive #

If the drive's fault history shows an undervoltage flag stamped within the start event, the supply is a suspect, but a small calculated sag exonerates it, and the calculation takes a minute.

Worked example, with illustrative values you should replace with your own nameplate data:

  • Transformer: 1000 kVA, 480 V secondary, three-phase, 60 Hz, impedance 5.75% from the nameplate.
  • Transformer rated secondary current: 1000 kVA divided by (1.732 times 0.480 kV) = 1000 kVA divided by 0.831 kV = 1203 A.
  • Second chiller's drive line current during acceleration: 600 A (an example value; read the actual accelerating current from the drive's display or a clamp meter during a start).
  • Estimated dip at the shared bus: impedance times the ratio of accelerating current to rated current = 0.0575 times (600 A divided by 1203 A) = 0.0575 times 0.499 = 2.9%.
  • Bus voltage during the start: 480 V times (1 minus 0.029) = about 466 V.

That approximation treats the accelerating current as fully lagging, which is conservative for a drive input; the exact figure belongs in a proper sag study checked against the transformer's test report and the governing code. This article on calculating voltage drop when starting a second motor sets up that fuller calculation. The decision for the example: a dip of 2.9% leaves the bus within a few percent of nominal, far from levels that trip a healthy drive's DC-bus undervoltage protection. If the drive trips anyway, do not chase the transformer; the disturbance is either deeper than the steady-state calculation predicts or it is not a sag at all.

Two things produce deeper-than-calculated disturbances. One is the second chiller transferring to a bypass contactor or an across-line starter after acceleration: the closure transient and the waveform notching from the abrupt connection hit the running drive's input while its DC bus is carrying load, and this drive-to-drive interaction has its own signature, covered in the article on why a VFD DC bus overload fault appears when a soft starter starts. The other is coincidence: oil pumps, tower fans or other auxiliary motors across-the-line on the same bus that start at the same moment as the staged command. The Class A recorder trace answers both; compare its minimum RMS value and duration against the drive's documented undervoltage trip curve, which lives in that drive's manual for that model and firmware, not in any general number.

Control power and permissives #

If the recorder shows the bus solid and the drive shows no fault, but the contactor released anyway, the coil lost its supply or a permissive opened. Log the coil voltage through a start at the contactor terminals, not just at the panel. A control power transformer feeding several contactors sags on its own when a second coil pulls in, and a marginally sized unit or a loose connection on its secondary can release a running contactor at exactly that moment. How that secondary is grounded or left floating changes what you will measure, and the article on grounded versus floating control transformer secondaries in MCCs explains the difference. Check every permissive in the running chiller's rung too: a flow switch, a low-pressure cutout or an interlock wired across pairs can drop out on the transient even when the drive is untripped.

The decision for each case #

First-out evidence What it points to The fix
Drive undervoltage flag, recorder confirms a dip deeper than the calculation Real supply disturbance: bypass transfer notch, auxiliary motor start, or undersized transformer Remove the disturbance source; add a line reactor or filter only after the capture shows it helps
Drive undervoltage flag, recorder shows a solid bus Loose connection upstream of the drive or a marginal trip threshold Torque-check terminations and fuses from the breaker to the drive input, then compare against the drive's documented trip thresholds
No alarm, contactor coil voltage collapses Control power problem Resize or re-feed the control power transformer, repair the loose termination
No alarm, coil held, a permissive opens Interlock or chiller protection module dropping out Trace the opened contact to its source; do not replace the protection module before its indication is proven first-out
Run command removed before anything else Staging sequence Correct the program, not the hardware

After an undervoltage event, note how the chiller controller comes back: many protection modules hold a restart delay, and if auto-restart after undervoltage is configured, the timer groups that govern it are covered in the article on setting motor undervoltage auto restart timer groups.

Accept a correction only after the pair starts repeatedly, several cycles of start, stop and restart, with the running chiller's run command intact, its control power held, and no trip in either drive's fault history. Keep the event records from both the failed and the passing tests: if the fault returns months later, that first-out is the only thing that tells you whether you fixed it or moved it.

Questions asked

The running chiller stops with no alarm at all. Where do I look first?

Log the contactor coil voltage, the run command and every permissive through a start of the second unit. If the coil voltage collapses, the problem is control power: a control transformer that sags when the second coil pulls in, or a loose secondary termination. If the coil holds but a permissive opens, trace that contact to its source. A stop with no drive fault and no protection alarm is almost always control power or logic, not the drive.

Can the drive trip undervoltage when my meter shows almost no voltage drop?

Yes. A dip lasting one or two cycles will not register on a handheld meter, which averages over seconds. Use a power-quality recorder meeting IEC 61000-4-30 Class A, recording RMS every half-cycle with dip triggering, and match its timestamp to the drive's fault history. The threshold that trips the drive is in that drive's own manual, so compare against the documented curve rather than a general figure.

Is it normal for the first chiller to shut off when the second one starts?

In some load-matching plant designs, yes: the drive carries the load until the second machine starts, then the staging program deliberately sheds or stops the first one. Check the staging logic and the commissioning sequence before treating the event as a fault. If the program commands the stop, the behavior is intended and the correction belongs in the sequence, not in the electrical distribution.

I already checked the chiller inrush current and the transformer size. What did that miss?

An inrush check and a nameplate review prove steady-state numbers, not the transient. They miss a two-cycle dip from a bypass contactor closure, waveform notching reaching the running drive's input, a control transformer that sags when a second coil pulls in, and any staging command sitting in the plant controller. Those need a half-cycle recorder capture and a first-out log, not another steady-state measurement.

Keep reading

  • Selection guide

    Measuring VFD and soft starter current with the right meter

    Use a true-RMS clamp inside its stated AC-current band for VFD input current and for soft-starter current, where line and load are one series path. On the PWM drive output, trust only a clamp its maker rates for drive output, a current probe with an oscilloscope, or the drive's own current display. A frequency-counter range like the Fluke 325's 5–500 Hz says nothing about its 45–400 Hz current accuracy.

    Variable frequency drives

  • Explainer

    Why VFD input current can be higher than output current

    Higher input current than output current is normal on a six-pulse diode rectifier drive. The input current carries harmonic content that produces no usable power, so amperes cannot be compared across the DC link. Compare input and output active power instead, using P = √3 × V × I × PF on each side.

    Variable frequency drives

  • Troubleshooting

    Finding a 113 V drop between a VFD and the motor terminals

    The drop is real, it lives in the path between the drive lugs and the terminal box, and it works out to about 0.36 Ω per phase — enough to dissipate roughly 11 kW per phase if it is resistance. Verify the reading with a drive-rated meter, then find it with an infrared scan under load and a micro-ohmmeter on every joint; the motor is downstream of both measurement points and is not the cause.

    Variable frequency drives