Current IntelPower LibraryShop main store

Troubleshooting

Why a drive trips ground fault with good megger readings

Variable frequency drives Published 6 min read By Current Intel engineering team

Short answer

A drive ground fault trip with good megger readings means the drive's leakage detection saw earth current that your low-voltage test never stressed. Isolate the drive, cable and motor, test the cable at roughly twice its rated voltage plus 1000 V, and repair whichever section fails; never megger through the drive.

On this page
  1. Why does a drive trip ground fault when the megger reads fine?
  2. What does the drive actually measure to call it a ground fault?
  3. Why does insulation pass a continuity test and still leak?
  4. What test voltage should you put on the motor cable?
  5. How do you isolate drive, cable and motor to find the fault?
  6. What do the readings tell you to repair?
  7. When can you restart after a ground fault trip?
  8. Questions asked

A ground fault trip on a drive with clean megger readings is not a contradiction: the drive and the megger hunt for the same leakage at completely different voltages, and the fault often conducts only under the drive's output voltage or a proper insulation-test voltage. This article gives the test voltage to use, the isolation sequence that separates drive, cable and motor, and the repair decision each reading points to. The worked numbers are examples; confirm acceptance limits against the equipment documentation and your authority having jurisdiction.

Why does a drive trip ground fault when the megger reads fine? #

A drive checks its output for earth current with every switching pulse, so it trips on leakage that a megger reading taken on cold, de-energized equipment never reproduces, because the two instruments apply entirely different voltages to the same insulation. The drive's detection is a protection function, not a measurement: its threshold is set to trip before leakage can damage the cable, the winding or the drive's own output stage, so a trip is real information even when the winding reads in the megohm range at rest. Record when the trip happens, because the timing narrows the search: before a run command points at wiring or the drive, at first acceleration points at moisture or a contamination track, and only after the motor warms points at insulation that breaks down under heat. The overlap with bench tests that look clean is covered in the article on a VFD ground fault trip when insulation tests pass.

What does the drive actually measure to call it a ground fault? #

The drive measures current leaving the phase conductors for earth and trips when that leakage crosses the threshold its manufacturer sets, which happens before the fault current grows destructive in most designs. The pickup level is a design value documented in that drive's own manual, not an industry-wide number, so the drive manual, not a generic table, is the reference for what the trip means on your model. Two consequences follow. If your installation uses an external relay on the earth path, its trip tells you something different depending on the element type; comparison of earth-continuity and earth-leakage relays walks through that distinction. And on an ungrounded or resistance-grounded supply, detection can behave differently or miss a single earth path entirely, which is its own failure pattern described in the article on drive ground fault detection on an ungrounded supply.

Why does insulation pass a continuity test and still leak? #

A continuity tester applies a few volts from an internal battery, and a moisture film or carbonized track that reads completely open at that voltage conducts readily at 460 V or at an insulation tester's kilovolt-level output. Insulation fails in two modes the low-voltage test cannot separate. A bare conductor strapped to ground reads as a dead short at any voltage, and continuity finds it in seconds. A weakened but unbroken dielectric — water in the terminal box, a carbonized path from an old overload, absorbed moisture in a stored motor — reads open at battery voltage and leaks only when stressed. That is the case an insulation tester exists for: megger testing finds leakage in isolated equipment by applying kilovolt-level DC and measuring what survives it. A clean continuity result proves only that no bare conductor touches earth; it says nothing about the dielectric.

What test voltage should you put on the motor cable? #

When the factory test voltage is unknown, test the cable at about twice its rated voltage plus 1000 V, which for a 600 V cable works out to 2200 V. Worked example: a shielded 600 V VFD output cable with the drive disconnected and the motor disconnected at its terminal box. 2 × 600 V + 1000 V = 2200 V, so set the insulation tester to its 2.5 kV range and read after 60 seconds, the conventional spot-test duration. On a 480 V cable the same formula gives 2 × 480 V + 1000 V = 1960 V, which still lands on the 2.5 kV range. Never apply that voltage through the drive: the output-stage semiconductors have no published withstand for it, and the drive manual's testing guidance assumes the load side is disconnected. For the motor winding itself, IEEE 43-2013 recommends a 500 V DC test on windings rated below 1000 V; where the motor manufacturer documents a different value, the manufacturer governs.

How do you isolate drive, cable and motor to find the fault? #

De-energize the circuit, lock it out and verify the absence of voltage, then disconnect the cable at the drive output terminals so the drive, cable and motor each get tested as a separate asset. The sequence:

  1. Record the exact fault text and trip timing from the drive's history before removing power.
  2. De-energize, apply lockout, and verify absence of voltage at the drive terminals; NFPA 70E, 2024 edition, covers the de-energize-and-verify process, and your local requirements may add to it.
  3. Disconnect the motor leads at the drive output terminals and at the motor terminal box so cable and motor are electrically separate.
  4. Continuity-test each cable conductor to earth and to the other phases to catch a bare conductor or a crossed phase.
  5. Insulation-test the cable phase-to-earth at the calculated voltage, one phase at a time with the others guarded to earth.
  6. Insulation-test each motor winding to the frame and winding-to-winding, and compare the three phase readings; the low one names the suspect phase.
  7. If cable and motor both pass, inspect the drive terminals and interior for moisture, conductive dust and corrosion, and follow the drive manual's earth-fault diagnostics for that model.
  8. Verify protective-earth conductor continuity separately; grounding integrity and insulation integrity are different checks with different instruments.

What do the readings tell you to repair? #

The section that fails its insulation test is the one you repair: a cable failure means repair or replacement of the cable, a winding failure sends the motor to repair, and two passing sections point the investigation at the drive itself. A cable that reads low phase-to-earth but passes continuity usually has moisture in a gland or a junction box, or insulation abraded against a sharp edge: dry it and retest before condemning the run, and replace it if the reading stays low. A winding below its acceptance level with the cable disconnected is a motor decision, and where you connect the tester changes what the reading sees — the article on insulation resistance testing from switchgear versus motor terminals explains why a test taken from the gear also sees the cable's fault. When both sections pass and the drive still reports earth fault, the fault is inside the drive; it goes to service or replacement per the manual.

When can you restart after a ground fault trip? #

Restart only after the repaired section passes its insulation test again, every termination matches the wiring documentation, and the enclosure is dry — then record the readings with date, tester, test voltage and temperature as the baseline your next session compares against. A moisture path that dries and now tests high can return with the next washdown or humidity event, so a downward trend across test dates is the early warning that beats the trip. One safety note: do not reset and rerun a drive that keeps tripping ground fault to see whether it clears — repeated re-energization of a leaking circuit heats the fault path and turns a moisture track into a burned conductor.

Questions asked

Can I megger a motor cable without disconnecting it from the drive?

No. The tester's output, 2200 V in the worked example above, exceeds what the drive's output-stage semiconductors are built to sit across. Disconnect all three output leads at the drive terminals, test the cable alone, then the motor alone, and use only the diagnostic methods the drive manual documents for the drive itself.

What is the lowest insulation resistance you accept on a 460 V motor winding?

IEEE 43-2013 recommends a minimum for most windings built after about 1970 of the rated kilovolts plus one megohm, so 0.46 kV plus 1 MΩ gives about 1.5 MΩ at 40 degrees Celsius. Below that, or with one phase far below its siblings, the motor stays out of service until it is dried, repaired and retested.

Why does the drive trip ground fault at start but test clean while stopped?

The leakage path needs voltage stress. A moisture film or a carbonized track on the cable or winding reads open to a continuity tester and to a cold insulation reading, but conducts once the drive applies output voltage. Isolate and test at full insulation-test voltage, then dry or replace the affected section before restart.

Should I raise the ground-fault threshold to stop repeat trips?

No. The threshold exists to trip before the leakage damages the cable, the winding or the drive's output stage. Raising it hides a real fault and invites a burned conductor; keep the manufacturer's setting and find the leakage with the isolation sequence instead.

Keep reading

  • Troubleshooting

    VFD ground fault at start with good megger readings

    A drive that trips ground fault only when the move command is applied, while cable and motor megger in the hundreds of megohms, has an intermittent leakage path inside the motor terminal box that a DC test cannot reproduce. De-energize, reterminate and reinsulate the leads, and dress them so the cover cannot pinch a phase against ground, and leave the ground-fault threshold and the fault itself armed.

    Variable frequency drives

  • Troubleshooting

    VFD ground fault trip explained when insulation tests pass

    A passed insulation-resistance test rules out steady phase-to-earth leakage but not the high-frequency charging current a PWM output drives through cable capacitance and EMC filters. Read the drive's own fault value before decoding it, verify broadband screen bonding at both ends, separate startup trips from trips after an hour or two of running, and use a lower switching frequency as a diagnostic. Other brands staying online proves nothing about the installation.

    Variable frequency drives

  • Troubleshooting

    VFD output phase loss fault: tracing the broken phase

    An output phase loss fault means the drive's current monitor sees one of the three phases at its U, V and W terminals drawing no current or far less than the others, so the break is almost always between the drive and the motor windings: the cable, a termination, output fusing, a contactor pole or the winding itself. Lock out, compare the three line-to-line resistances at both ends, and the readings name the broken phase.

    Variable frequency drives