Current IntelPower LibraryShop main store

Troubleshooting

VFD output phase loss fault: tracing the broken phase

Variable frequency drives Published 7 min read By Current Intel engineering team

Short answer

An output phase loss fault means the drive's current monitor sees one of the three phases at its U, V and W terminals drawing no current or far less than the others, so the break is almost always between the drive and the motor windings: the cable, a termination, output fusing, a contactor pole or the winding itself. Lock out, compare the three line-to-line resistances at both ends, and the readings name the broken phase.

On this page
  1. What the drive is actually measuring
  2. De-energize before you open anything
  3. The output-path causes, in check order
  4. Resistance checks that name the broken phase
  5. Worked example: judging the winding readings
  6. What each result decides
  7. Fixes that hold
  8. Questions asked

An output phase loss fault means the drive has compared the currents in its three output conductors and found one that carries no current, or far less than the other two. The break is almost always in the path between the drive's U, V and W terminals and the motor windings: a blown output fuse, a loose termination, a broken cable conductor, an open contactor pole or an open winding branch. You trace it with resistance measurements taken in the right order, not by swapping parts: lock out, test the cable from the drive end, test the windings at the motor box, and the readings point at the broken phase directly. This article walks that sequence and gives the acceptance figures to judge the winding readings against.

What the drive is actually measuring #

The drive measures the current in each output phase and its monitor trips when one phase loses its current draw or draws significantly differently from the other two. The exact trigger threshold is written for each model in its fault table, so read the drive's fault history and the table for your model before assigning a cause; the same failure carries a different code number on every drive family.

Keep this fault separate from two others with similar names. An input-side missing phase concerns the supply feeding the drive and has its own causes and checks; the article on a missing phase fault on a single-phase supply covers that case. A ground fault is a different mechanism again, current leaving the conductor rather than failing to flow; the article on ground fault trips when insulation tests pass traces that one.

De-energize before you open anything #

Every check below is a de-energized resistance test. NFPA 70E, 2024 edition, covers electrical safety-related work practices and requires establishing an electrically safe work condition before opening a panel or terminal box: lock the drive out, test for absence of voltage at the input terminals, let the DC bus sit for the discharge time the drive manual states, then verify it reads dead before touching the output terminals or the motor box. Confirm the practice with your local authority having jurisdiction and the equipment documentation.

The output-path causes, in check order #

  • A blown fuse in the output fusing between drive and motor. Manufacturers name opened fusing between the motor and the drive as a direct trigger of this fault.
  • A loose or poor termination, at the drive's output studs, at any terminal block, or in the motor junction box. Field failure records put poor terminations at the motor terminal box at the top of the list for repeated single-phase burnout, and a joint that heats also drifts in resistance.
  • A broken or damaged conductor in the motor cable. Not every cable defect reads as an open circuit: a bad joint or damaged conductor can pass a cold resistance check yet drop voltage under load, which is a different measurement; finding a 113 V drop between a VFD and the motor terminals walks one trace like that.
  • An open or high-resistance pole in a contactor or disconnect between drive and motor.
  • An unbalanced or open motor winding: a broken winding branch or a bad joint inside the machine.
  • A wrong or damaged motor cable, or the cable screen not bonded as the manual requires; drive makers list an unconnected screen among the documented triggers.
  • A motor that is not connected at all, or one much smaller than the drive expects: the monitor needs to see each phase draw current, and an undersized, lightly loaded motor can draw too little.
  • On a closed-loop drive, a loose encoder coupling: the feedback error makes the control over-compensate and unbalances the output currents. Check it once the power path passes.
  • The drive's own output power stage. When cable, terminations, fusing and windings all test clean and the fault still returns, the fault documentation for this code class lists a power output stage fault, and that is a drive service decision, not a field fix.

Resistance checks that name the broken phase #

  1. Confirm the code. Open the drive's fault history and its fault table for your model; make sure the active code is the output phase loss treated here, not an input-side or ground fault code.
  2. Test the cable from the drive end. Disconnect the three motor leads at the motor terminal box and tie them together there. At the drive's U, V and W terminals, measure U-V, V-W and U-W: each pair now reads the out-and-back loop through two cable conductors, so the three readings should be small and equal, each about twice a single conductor's resistance. A high or open pair puts the break in one of that pair's two conductors.
  3. Split the cable from the output devices. A single open element in series between drive and motor, one blown fuse or one open contactor pole, shows the same pattern as a broken conductor: one normal pair, two open. Separate the tied conductors and measure each conductor end to end; check each fuse for continuity; check each contactor pole with its coil operated as the manufacturer's documentation describes.
  4. Test the windings at the motor box. With the cable leads separated and the nameplate connection links in place, measure the three line-to-line resistances and compute the imbalance.
  5. On closed-loop drives, verify the encoder coupling is tight.
  6. Repair, restore the connections, and run: the three output currents should read roughly equal on a clamp meter and the drive should pass the start without returning the fault.

Worked example: judging the winding readings #

Inputs: a 7.5 kW (10 hp), 460 V, three-phase motor, wye-connected per the nameplate, measured cold after lockout, cable leads separated, links in place. Readings: U-V = 2.80 Ω, V-W = 2.83 Ω, U-W = 2.85 Ω.

Imbalance % = (Rmax - Rmin) / Ravg x 100
Ravg        = (2.80 + 2.83 + 2.85) / 3 = 2.827 ohm
Imbalance   = (2.85 - 2.80) / 2.827 x 100 = 1.8 %

The benchmark is the winding-rewind industry's acceptance standard, whose clause 9.2.2.13 sets post-rewind resistance balance at 2.0% for lap windings and 3% for concentric windings. At 1.8%, this winding sits inside the lap-winding figure, so the windings are not the cause of the fault; move to the cable, the terminations and the output devices. Treat the result as an estimate to confirm against the equipment documentation and the motor's own test records where they exist: a reading that has drifted from a previous test outweighs any fixed percentage.

The open-circuit case is decisive without arithmetic. On a wye winding, one normal pair with two open pairs puts the break in the phase left out of the normal pair: if U-V reads 2.8 Ω and the other two pairs read open, the W branch or its terminal connection is broken. On a delta-connected winding the pattern differs: two pairs read about 1.5 times the healthy value and the third about 3 times, and the 3-times pair spans the open branch. Record the nameplate connection before comparing any readings.

What each result decides #

Reading Meaning Decision
Three equal loop readings from the drive end Cable and output devices continuous Go to the winding test
One pair normal, two open, motor tied A conductor or one series device is open in the phase left out of the normal pair Split cable from devices with individual conductor and fuse checks
One conductor end-to-end open or high Broken conductor or bad joint in the cable Repair or replace the cable, remake the terminations
A fuse open Output fusing opened Replace with the type and rating the coordination documentation specifies, and find why it opened before restarting
Three winding pairs balanced inside the lap-winding limit Windings not the cause Move back to cable, terminations and output devices
Two winding pairs open, one normal (wye) The phase left out of the normal pair is broken Check that terminal stud and jumper first, then the winding branch
Two winding pairs near 1.5x, one near 3x healthy (delta) The branch spanned by the 3x pair is open Send the motor out for the winding repair or rewind
Everything electrical passes, fault returns Unbonded cable screen, loose encoder coupling, or the drive's output stage Bond the screen and check the coupling; otherwise the drive goes to service

Fixes that hold #

Remake a suspect termination rather than just retightening it: cut back and re-terminate conductors that show heat discoloration, using the terminal hardware the box was designed for. Bond the motor cable screen at both ends exactly as the drive manual shows; an unbonded screen is a documented trigger for this fault class as well as a noise source. After the repair, record the three winding resistances and the date in the motor's file, because the next trace starts with a comparison against them.

And do not reset the fault and run to see whether it recurs. A three-phase motor with one phase carrying little or no current loads its remaining windings past their rating, and repeated single-phase operation is how motor terminal boxes burn. Find the break, repair it, then return the drive to service.

Questions asked

Why does the drive trip output phase loss right at the start?

Two common reasons: the motor is not connected, or it draws too little current for the monitor to see all three phases because it is much smaller than the drive expects. Manufacturers list a missing motor and an undersized motor among the probable causes. Check that the motor leads are landed and that the drive's motor data matches the nameplate before you suspect the cable.

What winding resistance imbalance is acceptable?

The rewind industry's acceptance standard sets post-rewind balance at 2.0% for lap windings and 3% for concentric windings, computed as the spread between the highest and lowest of the three line-to-line readings over their average. Below those figures a winding passes; any open pair fails outright. Where the motor has its own test record, a drift from that record outweighs the fixed percentage.

Can the motor cable screen really cause this fault?

Yes. Drive manufacturers list a wrong or faulty motor cable and an unconnected cable screen among the documented triggers, because the monitor's measurement depends on the output circuit behaving as expected. Terminate the screen at the drive as the manual shows, and check the cable is the type and length range the manual allows.

Can I just reset the fault and keep running?

No. The fault means a phase is carrying little or no current, and running a three-phase motor that way overloads the remaining windings; repeated single-phase operation is how motor terminal boxes burn. Find the break with the resistance checks, repair it, and then return the drive to service.

Keep reading

  • Troubleshooting

    Finding a 113 V drop between a VFD and the motor terminals

    The drop is real, it lives in the path between the drive lugs and the terminal box, and it works out to about 0.36 Ω per phase — enough to dissipate roughly 11 kW per phase if it is resistance. Verify the reading with a drive-rated meter, then find it with an infrared scan under load and a micro-ohmmeter on every joint; the motor is downstream of both measurement points and is not the cause.

    Variable frequency drives

  • Troubleshooting

    VFD ground fault at start with good megger readings

    A drive that trips ground fault only when the move command is applied, while cable and motor megger in the hundreds of megohms, has an intermittent leakage path inside the motor terminal box that a DC test cannot reproduce. De-energize, reterminate and reinsulate the leads, and dress them so the cover cannot pinch a phase against ground, and leave the ground-fault threshold and the fault itself armed.

    Variable frequency drives

  • Troubleshooting

    VFD ground fault trip explained when insulation tests pass

    A passed insulation-resistance test rules out steady phase-to-earth leakage but not the high-frequency charging current a PWM output drives through cable capacitance and EMC filters. Read the drive's own fault value before decoding it, verify broadband screen bonding at both ends, separate startup trips from trips after an hour or two of running, and use a lower switching frequency as a diagnostic. Other brands staying online proves nothing about the installation.

    Variable frequency drives