Troubleshooting
Why a ground detector lamp brightens when a motor starts
Short answer
Brightening detector lamps at a motor start on an ungrounded system mean a high-resistance ground leak is dragging one phase toward earth: the dimming lamp marks the leaking phase, the brightening lamps mark the healthy phases, and a solid fault would push the healthy phases to line-to-line voltage. Log all three phase-to-ground and phase-to-phase voltages through the start, then megger motor and feeder separately at 500 V DC.
On this page
A ground detector lamp that brightens the moment a 20 hp cooling-tower fan starts is reporting a shift in the system's ground reference, not proof of arcing between phases inside the motor. On an ungrounded 480 V system the three lamps read phase-to-ground voltage, and a new high-resistance leak on one phase drags that phase toward earth: its lamp dims while the two healthy phases climb toward line-to-line voltage and their lamps brighten. Read the dim lamp, not the bright one. The decision: log all three phase-to-ground and all three line-to-line voltages from motor-off through the start with a recording meter, then de-energize, disconnect the motor leads and test motor and feeder separately with an insulation-resistance tester. A steady line-to-line supply with one phase-to-ground voltage sagging is a leak to find; only a line-to-line sag or unbalance points back toward the windings.
What the lamps on an ungrounded system actually read #
An ungrounded wye or delta system has no intentionally bonded neutral, so nothing fixes the phase-to-ground voltage except the equipment connected to it: the stray capacitance of cables and windings, and the detector lamps themselves. Each lamp hangs on one phase through a small isolation transformer whose secondary, a low voltage (120 V in the common arrangement), drives the bulb from the ground bus. Balanced and healthy, all three lamps see the same voltage, the line-to-line value divided by √3, and glow equally.
Brightness is a proxy for lamp voltage, not a calibrated fault-current reading, and the eye is poor at judging small differences in brightness, so a shift that looks dramatic can be a modest voltage change. Measure the secondary voltages at the detector transformers instead of comparing memories of glow. The lamps also indicate displacement only: they sense no fault current, unlike the relays behind locating a ground fault on a resistance-grounded system. Plants carry lamp sets because NFPA 70, the National Electrical Code, 2014 edition, section 250.21(B), required ground detectors on ungrounded systems; the requirement has moved between editions since, so confirm with your authority having jurisdiction what the edition enforced where you work asks for before adding or removing a set.
Why the brightness changes exactly when the motor starts #
The lamps are usually the largest resistance between any phase and earth, so the reference point sits where lamp current and stray capacitance agree. A leak of a few milliamperes, the same order as the lamp current itself, moves that point enough to see, which is why a fault no relay would ever notice shows up as a brightness change. A leak on one phase pulls that phase toward earth: its lamp dims and the other two brighten, and with two lamps dim the leaks sit on both of those phases.
The endpoint of that pull is a solid ground: with one phase firmly earthed it sits at 0 V to ground while the other two sit at line-to-line voltage to ground, 480/√3 ≈ 277 V each in balance, so the healthy lamps ride to √3 × 277 ≈ 480 V, 1.73 times normal. A high-resistance leak produces the same displacement, proportionally smaller.
The start itself does three things at once. Inrush current several times the running value dips the bus; a symmetric dip dims all three lamps together and is the supply, not a fault. Electromagnetic force and vibration at the moment of energizing can bridge a weak leakage path, in a damp winding, a wet terminal box or a contaminated cable entry, and cooling-tower duty is exactly where moisture lives. And the branch adds capacitance and leakage when its contactor closes, including anything hung on it: a control power transformer with damp windings is the classic hidden leak on a motor circuit.
A worked start capture #
Illustrative example with stated inputs, not a measurement from a specific plant: a recording true-RMS meter at the MCC of a 480 V ungrounded wye feeding a 20 hp fan motor. Motor off, the three phase-to-ground readings sit at 276, 277 and 278 V. Through the start, phase L1-to-ground falls to 187 V while L2 and L3 climb to 322 and 323 V, and all three line-to-line voltages hold between 477 and 481 V.
That is 90 V down on the leaking phase and 45 V up on each healthy one: 277 - 90 = 187 V, and 277 + 45 = 322 V. The line-to-line voltages barely move because a ground-reference shift does not disturb phase-to-phase voltage, and that steadiness is what clears the line-to-line supply of arcing. A real capture will not land on the exact two-to-one split, because stray capacitance and leaks on more than one phase distort it, so treat the asymmetry itself, one phase down and the other two up, as the diagnosis and treat the exact figures as an estimate to be confirmed by re-measurement.
Field procedure from first meter reading to megger #
- Baseline with the motor off. Log all three phase-to-ground and all three line-to-line voltages at the MCC with a true-RMS recording meter, plus the detector secondary voltages.
- Capture the start. Record through acceleration into steady running; a shift that exists only during acceleration and one that persists point to different mechanisms.
- Read the pattern. One lamp dim and two bright with steady line-to-line voltages is a ground leak on the dim phase; all three dimming together is the start dip; line-to-line unbalance is the one pattern that really does suggest trouble between phases.
- De-energize before opening anything. Lock out the feeder and verify absence of voltage at the load side before opening the motor terminal box, the practice NFPA 70E, 2024 edition, sets out for electrical work, and confirm the site procedure with your authority having jurisdiction.
- Separate the sections. Disconnect the motor leads at the terminal box so the motor and the feeder can be tested, and later blamed, individually.
- Test windings and cable. Megger each winding to the frame in turn, then the disconnected feeder cable phase-to-ground and phase-to-phase, keeping surge suppressors and electronic devices out of the test circuit.
- Reconnect and watch. Restore one section at a time and repeat the phase-to-ground measurement; the section that moves the reference is the one with the leak.
Insulation numbers for the megger #
IEEE Std 43-2013 recommends 500 V DC for insulation-resistance tests on windings rated below 1000 V, and its acceptance floor for most windings built after about 1970 is kV + 1 megohm, corrected to 40 °C. For a 480 V winding that is 0.48 + 1 = 1.48, about 1.5 MΩ; where the motor manufacturer's own criteria are stricter, they govern. Insulation resistance roughly halves for every 10 °C rise, so record winding temperature with every reading and compare cold to cold and warm to warm. Let the tester discharge the winding after each reading before handling the leads.
Phase-to-ground readings answer the lamps' question: where the leak is. The phase-to-phase direction of the same test answers the arcing question, and the page on phase-to-phase versus phase-to-ground insulation testing separates the two. A suspected winding-to-winding fault is convicted on its own evidence, per-phase winding resistance, running-current balance and the line-to-line capture from the start; the page on troubleshooting intermittent phase-to-phase arcing in distribution panels goes deeper on that failure mode.
The decision for each lamp pattern #
- One lamp dim, two bright, line-to-line steady: high-resistance ground leakage on the dim phase's branch. Run the sectioning procedure; the usual finds are a damp stator winding, moisture in the terminal box, a wet or contaminated cable entry, or the control power transformer tapped off that phase. Repair, then repeat the start capture and confirm the three phase-to-ground voltages return to near-equal.
- All three lamps dip during acceleration and recover: the start dip of the supply, not a ground event. There is nothing to chase in the detector.
- Line-to-line voltages unbalance or one pair sags during the start: winding-to-winding or connection trouble in the motor or its feeder. That fault never announces itself correctly through the lamps; take winding resistance and current balance.
- One lamp dark and staying dark: a solid ground on that phase. The system is now effectively earthed through the fault, and a second ground on another phase becomes an immediate phase-to-phase fault, so locate and clear it as a priority.
Repeat the original start capture after the repair and keep the before-and-after traces, insulation-resistance values, winding temperatures and connection states together: a repaired leak shows the three phase-to-ground voltages equalizing, and a pattern that returns with weather or vibration was never fixed. The lamp that brightens at the start is evidence with a direction. It clears the line-to-line supply, names the phase whose branch you megger first, and leaves the between-phases question to the tests built for it.
Questions asked
Does a ground detector lamp set protect anything?
No. The lamp set indicates, it does not trip. On an ungrounded system the first ground fault draws almost no current, so nothing opens and the process keeps running; the lamps exist so the leak is found and repaired before a second ground on another phase turns a nuisance into a phase-to-phase fault. Where automatic tripping is required, that is a ground-fault relay's job, not the lamps'.
All three lamps drift slowly with the seasons. Is that a fault?
Likely not. Humidity changes the leakage resistance and capacitance of the whole system, which moves all three lamps together or shifts them mildly and symmetrically. A fault is a persistent asymmetry: one lamp clearly dimmer or brighter than the other two at the same moment. Trend all three phase-to-ground voltages over time and act on asymmetry, not on slow drift that affects all phases alike.
Can I megger the motor through the starter without opening the load leads?
Not safely, and not usefully. Starter-mounted surge suppressors, phase monitors and control power transformers can be damaged by the tester's DC output, and they load the reading so a weak winding hides. Disconnect the motor leads at the terminal box, test the windings to frame, then test the feeder cable on its own. A low reading then identifies the damaged section instead of a whole branch in series.
At what leakage current should I stop running the motor?
An ungrounded system has no leakage threshold that trips anything. The lamps respond to shifts of a few milliamperes, so treat a persistent one-phase shift as a fault to locate and repair at the next planned outage, and escalate at once if a lamp goes fully dark or the shift keeps growing, because both track a leakage path whose resistance is falling toward a solid fault.