Why a motor current unbalance trip can show balanced phase currents
Short answer
When a protection relay trips on current unbalance and an independent logger shows the phases within 2%, the disagreement itself is the finding: the relay builds its unbalance quantity from its FLA base, CT scaling and its own definition, and an error anywhere in that chain trips on balanced current. Verify the settings arithmetic against the nameplate, compare relay metering with simultaneous independent measurements, and test supply voltage unbalance under load before condemning the motor.

On this page
A motor protection relay that trips on current unbalance while a data logger shows the three phase currents within 2% is not seeing something the logger missed: it is computing something else. The relay builds its unbalance quantity from CT secondaries, scaled by the CT ratio it holds, judged against thresholds derived from whatever FLA it holds, under its own definition of unbalance. An error in any link of that chain trips on perfectly balanced current, so the disagreement itself is the finding, and the order of work is fixed: the relay's event record and settings first, the CT circuit second, the supply third. The checks below use a reported wood-hogger installation, a 500 hp, 2300 V motor, with the settings arithmetic worked out.
Where a relay and a logger disagree #
Three mechanisms produce a trip the logger cannot see:
- A wrong base or scale. The relay converts each CT secondary to primary amps with the CT-ratio setting it holds and judges the phase spread against thresholds derived from its FLA setting. An FLA carried over from another motor, a mistyped ratio, or one phase's secondary partly shunted at the shorting terminal block all manufacture apparent unbalance while the true currents stay equal. This is the territory where what current-only motor protection can and cannot detect sets the limits: the relay knows only what its CTs deliver.
- A different definition. A logger's percent is usually the spread of three RMS magnitudes. The relay may instead take the largest phase deviation from the three-phase average, express it over FLA, or compute negative-sequence current, which responds to phase-angle unbalance that equal magnitudes hide. Both devices can be right about their own quantity.
- A different time window. A logger sampling every few seconds can miss the excursion a relay with a short delay caught, or can average across the event.
Checking the 10% and 20% settings against a 112 A FLA #
Inputs, all from the reported case:
- Nameplate FLA: 112 A (motor nameplate, 500 hp, 2300 V).
- Unbalance alarm at 10% of FLA and trip at 20% of FLA, written down as 12 A and 24 A (the settings sheet).
- CTs 150/5, a ratio of 30 to 1 (installation record).
- Phase currents within 2% at the recorded trip (data logger).
Rule: a percent-of-FLA threshold becomes amps when the percentage multiplies the FLA the relay holds, and each phase's secondary current is its primary current divided by the CT ratio.
Arithmetic:
- Alarm: 0.10 × 112 A = 11.2 A.
- Trip: 0.20 × 112 A = 22.4 A.
- The written amps imply another base: 12 A ÷ 0.10 = 120 A, and 24 A ÷ 0.20 = 120 A.
- Full-load secondary per phase: nameplate FLA ÷ 30 = 3.7 A.
- The logged 2% spread is about 2.2 A at full load, a fifth of the corrected alarm level.
Result: the written thresholds match a 120 A base, not the nameplate, so either the sheet is wrong or the relay holds the wrong FLA, and a relay with the wrong base, or with wrongly scaled inputs, alarms and trips on currents a logger rightly calls balanced.
Decision: read the relay's actual FLA, CT ratio and unbalance settings. If its FLA matches the 120 A base the arithmetic exposes, enter the nameplate value, restore the alarm at 11.2 A and the trip at 22.4 A, and confirm each secondary reads about 3.7 A at full load with an independent clamp before the unbalance element goes back in service. Stop there: no further raising of thresholds.
Verifying the measurement chain in order #
One safety point covers the list: any step that opens the relay compartment or touches the shorting block follows isolation, lockout and a verified absence of voltage under your site's procedure and NFPA 70E (2024 edition), the workplace electrical safety standard, and a CT secondary is never opened on an energized circuit, which is what the shorting block is for. The running checks below are metering only, with the permits your site requires for energized measurement.
- Pull the relay's event record. Motor protection relays of this class store the phase currents and the operated element at the trip, and the unit's manual documents what that record holds. Set the three stored currents beside the logger's values at the same timestamp: a large stored spread against a small logged one indicts the relay's input chain, small on both points to the relay's definition, and large on both says the unbalance was real.
- Read the settings from the relay itself, not the settings sheet: FLA, CT ratio, PT ratio, the unbalance definition, thresholds and delay. Every derived threshold scales with the FLA the relay holds, the same nameplate-first rule behind setting overload relays from motor nameplate full-load current.
- Compare metering at one instant under steady load: the relay's displayed phase currents, a clamp reading on each CT secondary at the shorting block, and an independent primary measurement. Equal secondaries with unequal relay readings put the fault in the relay's inputs or scaling; one low secondary puts it in that phase's shorting-block contact, terminals or wiring; faithful secondaries with unequal primaries say the unbalance is real.
- Measure all three phase-to-phase voltages at the motor terminals under load, on both sides of each PT, plus phase-to-ground, with a meter rated for the circuit. Compute unbalance the NEMA way, the largest deviation from the three-phase average over that average, and hold it to the Department of Energy recommendation of 1% at the motor terminals, with motor derating above it per the NEMA MG-1 curve the tip sheet cites. Equal voltage magnitudes still do not exclude angle unbalance.
- Log the three currents at light and at heavy load, with dry bark and with waterlogged bark. A spread that grows with load points at a connection or impedance in the supply path; a spread independent of load points at the measurement chain or the motor.
- Use the history. An earlier, larger motor on the same starter showed the same symptom, which points at what the two motors shared (supply, starter, CT circuit, settings) rather than at either motor. The method in diagnosing current imbalance across every motor on a service is the model.
When the unbalance is real #
Do not dismiss a real component. A voltage unbalance of a percent or two drives a current unbalance several times larger, and both grow with load, which is how waterlogged bark and more frequent trips can be one fact rather than two. The reported phase-to-phase voltage spread already exceeds the 1% recommendation, so until the supply is measured and corrected, derate the motor per the NEMA MG-1 curve and find the source: transformer taps, a high-resistance connection, or unbalanced single-phase loading upstream. A genuine unbalance is fixed upstream, never by a relay setting.
The decision for each case #
- Independent currents match the logger and the relay still tripped: the fault is in the relay's chain. Correct the FLA base to nameplate, clear the CT scaling or shorting-block defect, restore the thresholds derived above, and leave the element in service. A threshold raised to keep the process moving changes when the relay trips, not what it measures, and only narrows the margin for a genuine fault.
- Independent measurement confirms a spread beyond the trip setting under load: the unbalance is real. Bring terminal voltage unbalance back to the recommendation or below, derate until it is, and trace the upstream connection or impedance.
- Both records read small and trips continue: the relay is acting on a quantity the logger cannot see, phase angle or negative sequence. Measure phase angles or negative-sequence current with a power-quality analyzer and correct the supply, rather than swapping instruments again.
- A replacement relay that computes unbalance differently and adds stator-RTD thermal checking is a legitimate upgrade, but verify its FLA and CT scaling exactly as above first: a different algorithm fed the same wrong base trips the same way.
Questions asked
Why didn't raising the unbalance thresholds stop the trips?
A raised threshold moves only the trip point. If the relay's FLA base, CT scaling or a partly shorted CT phase is wrong, the computed unbalance stays large and still crosses the new setting, while the margin for catching a genuine fault shrinks. Trips that continue after the settings were increased are evidence the relay's quantity is wrong, not that the motor got worse.
Can a healthy motor draw unequal phase currents on a balanced supply?
Yes, a spread of a few percent is common. Stator laminations have directional magnetic properties, so the three phase impedances are never perfectly identical and equal voltages still draw slightly unequal currents. That is why unbalance trip settings sit well above a few percent and come from the relay manual and a protection study, not from the first spread someone reads.
What is the shorting terminal block for?
It shorts each CT secondary before the relay is removed, because an energized current transformer with an open secondary develops a hazardous high voltage across its terminals. The same contacts cause false trips when worn or left partly closed: a partially shorted phase reads low and manufactures apparent unbalance even though the primary currents are equal.
Does rotating the motor leads help find the cause?
Yes, as a controlled test under your site's isolation and commissioning procedure. Move each motor lead one position so every CT sees a different phase. If the apparent unbalance stays with the same relay input, the measurement chain is at fault; if it follows the lead to a different input, the supply or that motor phase is at fault. Restore and document the original phase identity afterward.