Troubleshooting
Why a synchronous motor trips on low power factor at motor start
Short answer
The trip is arithmetic, not a machine fault: an induction motor start draws roughly 15 Mvar at an estimated 0.2 power factor, and the synchronous motor supplies most of it because the generator path carries a short-circuit limiter's impedance. If the Mvar share stays inside the machine capability curve and the bus voltage holds, block or delay the power-factor element for the start window while keeping loss-of-field and out-of-step protection active.

On this page
A synchronous motor that trips on low power factor every time a nearby induction motor starts is not reporting a machine fault. The relay is reporting a real, brief reactive-power event: the induction motor start demands roughly 15 Mvar at an estimated 0.2 power factor, the generator path to that load carries the impedance of a short-circuit limiter, so the synchronous motor on the same bus becomes the stiffest source and supplies most of the Mvar. Its Q/P ratio then crosses the 0.7 inductive pickup by arithmetic alone. The decision is whether that Mvar share stays inside the machine capability curve and the bus voltage holds, in which case you block or delay the power-factor element for the start window, or whether limits are exceeded, in which case the start itself must change. The section below works the numbers, and the list at the end gives the data to collect and the decision path.
What the power-factor element is for #
A low power factor (device 55) element on a synchronous motor exists to detect loss of excitation and out-of-step conditions, per the IEEE Guide for AC Motor Protection (IEEE C37.96). A synchronous machine that loses its field falls into heavy lagging power factor as it absorbs reactive power from the system; the element catches that drop. A start-time reactive excursion is a different event: the field is healthy, the machine is deliberately supplying Mvar to a nearby load, and the element is reading the export as a lagging-power-factor condition. Confirm the relay's sign convention before any analysis, and verify from the event record whether the element saw lagging or leading power factor in the relay's polarity.
Fixes that do not clear this trip #
Each usual fix fails for a specific reason in this configuration: generator A in service, generator B out, and the synchronous and induction motors on the same synchronizing bus.
- Run the synchronous motor overexcited before the start. Already tried and the trip persisted. Extra pre-start excitation raises available Mvar but does not change how current divides between sources, and the field is still bounded by thermal and field-current limits.
- Start the induction motor with generator B online. Untested, so it cannot be relied on. With a limiter between each generator bus and the synchronizing bus, a second generator behind a second limiter does not lower the impedance seen from the induction motor terminals.
- Leave the relay alone because the start is brief. A 0.2 s delay is far shorter than a typical induction motor acceleration of several seconds, so the power-factor condition outlasts the timer. Read the actual start duration from a recorded start.
- Retune the excitation controller only. The element measures terminal active and reactive power. If the machine must carry most of the 15 Mvar, no excitation setting brings Q/P under the pickup.
How the reactive power splits #
An induction motor at speed is a decent power-factor load; at start it is almost pure reactance. That reactive current divides between sources roughly in inverse proportion to each path's impedance to the induction motor terminals. The limiter in series with generator A adds impedance to that path. The synchronous motor, sitting on the bus with only its subtransient and transient reactance behind it, is the stiffest nearby source, so it supplies the large share of the start Mvar while its active power stays at the mechanical load value. The generator AVR also responds more slowly than the machine's inherent current contribution, so the synchronous motor carries the first part of the start regardless of excitation setting.
Worked example: 15 Mvar of start demand against a 0.7 pickup #
Inputs, with sources: the reactive demand at start is about 15 Mvar at an estimated 0.2 power factor (the reported estimate for this induction motor); the relay element is set at 0.7 inductive for 0.2 s (the reported setting, adjusted per IEEE C37.96).
The rule in words: apparent power equals reactive power divided by the sine of the arccosine of the power factor, and the pickup corresponds to a Q/P ratio equal to the tangent of the arccosine of the pickup power factor.
The arithmetic:
- sin(acos 0.2) = 0.980, so S = 15 Mvar / 0.980 = 15.3 MVA
- P = 0.2 × 15.3 MVA = 3.1 MW, meaning the start load is about 98 percent reactive
- Pickup threshold: tan(acos 0.7) = 1.02, so the element trips when Q/P exceeds 1.02
- If the machine supplied the entire 15 Mvar, it would need P greater than 15 / 1.02 = 14.7 MW to stay above the threshold
Result: any synchronous motor operating below about 14.7 MW of active load and carrying most of the start Mvar trips by arithmetic alone, since its actual shaft load is far smaller.
Decision: the deciding quantity is the machine's share of the 15 Mvar compared against its available Mvar at the sagged voltage. If the share is inside the capability curve and the bus voltage holds, block the element for the start window. If not, the element is correctly flagging a threat to synchronism and the start must change.
Data to collect before changing anything #
- Synchronous motor terminal P, Q, power factor and voltage at the trip, from the relay event record or oscillography, compared against the 0.7 pickup and 0.2 s timer.
- The machine's capability curve at the terminal voltage during the start, from its datasheet, compared against its Mvar share of the 15 Mvar.
- Field current during the start, compared against rated field current and the field-forcing limit, from the excitation record.
- Minimum bus voltage during the start, compared against pull-out torque margin, which falls with the square of voltage.
- Generator A current and Mvar, compared against its rating and capability curve.
- Induction motor start duration, compared against the element's time delay.
- Limiter impedance and both source impedances, from the limiter datasheet and the short-circuit study.
The decision path #
- Pull the relay event record from the last trip and record P, Q, power factor, voltage and timer behavior.
- Compare the machine's Mvar share against its capability curve at the sagged voltage.
- Run a load-flow and motor-start study with generator A only, including the limiter impedances, and read the bus voltage and the Mvar sharing during the start.
- If voltage and Mvar stay inside limits, block the low power factor element for the start window using the induction motor breaker status or a start-permissive signal, or extend the delay beyond the recorded start duration plus margin. Keep the loss-of-field and out-of-step elements active so genuine excitation loss and pull-out are still covered.
- If voltage or Mvar limits are exceeded, reduce the demand: a reduced-inrush start method on the induction motor, or shunt capacitors for the start. Capacitor output falls with the square of voltage, so the sagged-voltage Mvar is well below nameplate, and a capacitor bank needs a switching-transient and resonance study before installation. The reactive output versus voltage relationship is worked through on the capacitor Mvar output versus voltage page. For how active and reactive power divide at a synchronous source, the MW versus MVAR control page covers the same quantities this element measures.
Genuine loss-of-field protection should permit operation anywhere inside the machine capability curve. An element that trips well inside that curve during a motor start is serving the wrong purpose, or was set without regard to the start.
One safety note: de-energize, lock out and verify absence of voltage before opening any panel, terminal compartment or relay case to pull records or change settings, per NFPA 70E, 2024 edition, and confirm the work rules with your authority having jurisdiction.
Why one generator and two differ #
With generator A alone, the source impedance from the generator side includes the limiter plus one generator's reactance, and the synchronous motor wins the current sharing. Paralleling generator B lowers the equivalent source impedance on the bus side only if the limiter impedance is not in series with the added path. Model both limiter impedances in the study before counting on the second generator; the reported case never tested it.
Questions asked
Why not just raise the excitation on the synchronous motor before the induction motor start?
Pre-start overexcitation was tried in the reported case and did not clear the trip. Extra excitation raises the Mvar the machine can deliver, but it does not change how start current divides between sources: the induction motor still draws from the lowest-impedance path, and the field is bounded by thermal and field-current limits.
Does starting with generator B online fix it?
Only if the second generator path is lower impedance than the synchronous motor's path. That configuration was never tried in the reported case, so it cannot be relied on without a study that models both limiter impedances.
Is a 0.2 s delay long enough for a motor start?
No. An induction motor acceleration typically lasts several seconds, far longer than the 0.2 s timer. Read the actual start duration from a recorded start and set the blocking window or the extended delay from that measurement plus margin, keeping loss-of-field and out-of-step protection in service.
What decides whether the trip is a nuisance or a real warning?
Compare the machine's Mvar share of the start against its capability curve at the sagged terminal voltage, and compare the minimum bus voltage against pull-out torque margin, which falls with the square of voltage. Inside both limits, the element is misapplied for the start and can be blocked. Outside either limit, the start itself must change, for example with a reduced-inrush method or capacitors sized for the sagged voltage.
