Variable frequency drives Published 7 min read By Current Intel engineering team

Short answer

A phase-specific IGBT overtemperature trip means a measured or calculated device temperature reached its limit. When a second drive trips the same way, the cause is shared: loading, entered motor data, or intake air inside the enclosure. Compare output current with the drive's rated output current at the actual voltage and duty, and measure the air entering the drive fan with the enclosure closed.

On this page
  1. Read the trip as a protection limit, not a component verdict
  2. Check what the two drives share
  3. Sizing the check for a 200 hp drive on a 250 hp fan at 460 V
  4. Measure the air the drive actually breathes
  5. Staged procedure to isolate the cause
  6. The decision for each pattern
  7. Questions asked

A phase B IGBT overtemperature trip is the drive reporting that a measured or calculated device temperature reached its protection limit. It is not, by itself, proof that the drive has failed or that the motor has a phase B winding fault. When a replacement drive trips the same way on the same phase, the evidence points away from a defective unit and toward what the two drives share: the load they carry, the motor data entered at commissioning, and the air they have to breathe inside the enclosure. The two deciding quantities are the drive output current against its rated output current at the actual voltage and duty, and the temperature of the air entering the drive cooling intake at the time of the trip, measured with the enclosure closed.

Read the trip as a protection limit, not a component verdict #

Drives protect their power stage in two ways. A heatsink NTC sensor gives a measured temperature; one manufacturer documents the NTC trip for the G and H frames of its 400-series fan and pump drive at 120 degrees C, stated as plus or minus 2 degrees C. Other drives, including one documented DG1 model, calculate the device temperature from output current and switching frequency and trip when that calculated channel exceeds 125 degrees C for more than one second through an I2T-style accumulation.

A calculated channel is why the trip can name one phase: the phase carrying the highest instantaneous loss estimate reaches the limit first, and the phase label is an output of the calculation, not a diagnosis. It is also why a heatsink reading of 57 degrees C can coexist with an overtemperature fault. Typical heatsink trip levels sit at 90 to 100 degrees C and most drives are rated for 40 to 50 degrees C intake air, so a 57 degrees C heatsink is nowhere near a measured trip. The fault came from the other channel. Before anything else, pull the fault history and the manufacturer's fault table for that drive model and record whether the trip was measured or calculated and which quantity the display names.

For related motor-side thermal trips, the causes and checks differ; see why a VFD trips a motor overheat fault: causes and checks.

article:why-a-vfd-trips-a-motor-overheat-fault-causes-and-checks

Check what the two drives share #

Two drives tripping on the same indication shifts the investigation to shared conditions:

  • Load and sizing. The motor's nameplate full-load current against the drive's rated output current at the actual voltage and variable-torque duty. Horsepower labels alone do not establish a correct match.
  • Entered motor data. Calculated thermal channels scale from the base motor current and voltage entered at commissioning. Wrong base data distorts the estimate; see why a VFD motor overload current setting takes nameplate FLA.

article:why-a-vfd-motor-overload-current-setting-takes-nameplate-fla

  • Intake air. Air inside a closed MCC or enclosure runs far above room temperature. A 20 degrees C reading taken outside the enclosure, or after opening its door, does not describe what the drive saw at trip time.
  • Cooling path. Drive fan operation, clear intake and exhaust filters, and the top and bottom clearance the installation manual requires.
  • Output electrical conditions. Termination tightness on supply, output, cable and motor, and balance among all three output currents.

For the current-versus-rating question, why a drive still needs a minimum motor size below its rating covers the same rating arithmetic from the other direction.

article:why-a-vfd-still-needs-a-minimum-motor-size-below-its-rating

Sizing the check for a 200 hp drive on a 250 hp fan at 460 V #

The inputs, all examples to be replaced with your own nameplate and rating values: the motor is a 250 hp fan motor on 460 V three-phase, with a nameplate full-load current of 302 A, consistent with the NEC Table 430.250 value for 250 hp at 460 V. The drive is a 200 hp variable-torque unit with a rated output current of 240 A at 460 V, the Table 430.250 value for 200 hp.

The rule in words: divide the motor nameplate full-load current by the drive's rated output current at the same voltage and duty. If the result exceeds 100 percent, the motor demand exceeds the drive's continuous rating and the drive will run its thermal protection hot at full fan speed.

The arithmetic: 302 A divided by 240 A equals 1.26, so the motor demands about 126 percent of the drive's rated output current.

The result: the combination is undersized by roughly a quarter of the drive's rating. A variable-torque fan reaches its highest current near full speed, so this margin is not an acceleration transient the drive rides through; it is a sustained overload every time the fan runs near full volume.

The decision: if your own numbers show the motor FLA above the drive's rated output current, correct the sizing mismatch first, with a larger drive or a speed limit that holds current within the rating, before condemning drives or the motor. If the numbers show comfortable margin, move to the intake air measurement below.

Measure the air the drive actually breathes #

Measure the air entering the drive's cooling intake during representative loaded operation with the enclosure closed. Ambient outside the enclosure is not the drive's ambient: enclosure heat accumulation, including the drive's own losses, raises the intake temperature. A rough screening figure from one field discussion puts losses around 7 to 8 kW for a 200 hp drive at full load; treat that as a screening number only and use the specific drive's published loss data for enclosure cooling design.

For peak intake temperature, use maximum-temperature indicator labels placed in the airflow entering the drive cooling chamber, not in a remote corner of the enclosure. An instantaneous reading taken after opening the door misses the peak, because the internal temperature drops as soon as the door is open.

Compare the measured intake temperature with the drive's documented maximum rated intake air temperature, typically 40 to 50 degrees C for industrial drives, and apply any stated derating above it. For a deeper walkthrough of the heatsink family of trips, the field guide on troubleshooting VFD heatsink overtemperature faults covers the same measurement sequence, and the heatsink overtemperature knowledge-base page covers the equivalent trip on soft starters.

The deeper background on why a VFD's line breaker trips before the drive faults is a different mechanism; a heatsink thermal trip behaves differently.

article:why-a-vfd-s-line-breaker-trips-before-the-drive-faults

Staged procedure to isolate the cause #

  1. Capture the trip record. Record the exact fault text, the phase or device identifier, the time, the output current, the commanded speed and frequency, and any displayed temperatures immediately before the trip. Note whether the fan was holding steady speed or accelerating.
  2. Verify the trip definition. Get the fault table for that drive model and revision and establish whether the trip was a measured heatsink value or a calculated IGBT channel, and at what level.
  3. Check the loading. Read the motor nameplate voltage and full-load current and compare them with the drive's rated output current at your voltage and duty, as in the worked example above.
  4. Compare the entered motor data. Confirm the drive's entered motor voltage and current match the nameplate. Correct any mismatch and record the change.
  5. Measure intake air. With the enclosure closed and the fan loaded, measure air at the drive fan intake and compare with the drive's rated maximum intake temperature and any derating table.
  6. Inspect the cooling path. Confirm drive fans run, filters and passages are clear, and the required mounting clearances are present.
  7. Check the output electrical path. De-energize, lock out, and test for absence of voltage before opening any terminal box or panel; then inspect supply, output, cable and motor terminations and compare all three output currents under the same stable operating condition, using instruments rated for PWM drive output, since ordinary mains-class measurements mislead on a drive output.

The decision for each pattern #

A calculated channel trip on one phase, with output current above the drive's rating or entered motor data below the nameplate, is a sizing or commissioning problem: fix the data or the drive size, do not replace drives. A trip with comfortable current margin and intake air above the drive's rating is a cooling problem: restore airflow, clearance or enclosure cooling. A trip with correct current, correct data, and intake air inside the rating leaves an output electrical imbalance as the lead suspect, and that is the point to measure the three output currents and the motor. A phase-specific IGBT indication alone never proves a motor fault, and an RPM meter measures speed, not power quality; correlate speed with current, not with a power-quality verdict.

Where the same thermal logic applies to the phase currents the drive feeds, why a VFD trips a motor phase loss fault and what to measure gives the matching measurement set.

article:why-a-vfd-trips-a-motor-phase-loss-fault-and-what-to-measure

Questions asked

What temperature does a drive trip at for IGBT overtemperature?

It depends on the model. Some drives estimate the IGBT junction temperature from output current and switching frequency and trip when that estimate crosses a limit; one manufacturer documents an I2T trip when the estimated value exceeds 125 degrees C for more than a second. Heatsink NTC sensors on common medium-voltage frames trip near 120 degrees C, and typical heatsink trip levels run 90 to 100 degrees C. Read the trip level from that drive's own fault table.

The drive display reads 57 degrees C yet it trips on overtemperature. Is the sensor wrong?

Probably not. That 57 degrees C reading is likely heatsink or unit temperature, while the trip may come from a calculated IGBT channel that rises with output current. A heatsink has a large thermal mass and lags the junction estimate. Verify what quantity the display names, then judge the event against that same quantity measured under the same loaded, closed-enclosure conditions.

Can wrong motor data entered in a drive cause an IGBT overtemperature fault?

Yes. Drives that calculate device temperature scale the calculation from the base motor current and voltage entered at commissioning. If the entered full-load current does not match the motor nameplate, the estimate runs against the wrong base and can reach its limit early. Compare the entered motor voltage and current with the nameplate and correct any mismatch before judging the drive or motor.

Is a 200 hp drive on a 250 hp fan motor correctly sized?

Horsepower labels do not decide it; current does. At 460 V three-phase, a typical 250 hp motor has a full-load current near 302 A while a 200 hp drive is rated near 240 A of output current, about 126 percent of the drive's rating, and a variable-torque fan still draws full current near full speed. Compare the motor nameplate FLA with the drive's rated output current at your voltage and duty. If the motor demand exceeds the drive rating, the drive is undersized for the application.

Keep reading

  • Troubleshooting

    Why a VFD trips overcurrent the instant the motor moves

    A trip a fraction of a second after the shaft first moves is a motor-circuit fault until the meter proves otherwise: the 17 A drive holds a 1.75× margin over the motor's 9.7 A full-load current, so acceleration cannot explain it. Verify the nine-lead grouping, measure resistance between all three pairs with the drive disconnected, then check torque compensation — a bigger drive is last.

    Variable frequency drives

  • Troubleshooting

    VFD OC1 overcurrent fault during acceleration causes

    OC1 is an overcurrent during acceleration: output current passed the drive's protection limit while frequency and voltage were rising. Record when current peaks in the ramp, then separate ramp-and-load causes (short acceleration time, jammed shaft, wrong motor data) from electrical faults in the cable, windings or drive power stage.

    Variable frequency drives

  • Explainer

    Why a capacitor-run motor needs a special VFD

    A standard three-phase VFD will not run a single-phase capacitor motor usefully: the fixed run capacitor's reactance rises as output frequency falls, so the auxiliary winding loses its phase-shifted current and low-speed torque collapses. Use a drive documented for PSC or shaded-pole motors, or change to a three-phase motor.

    Variable frequency drives