Current IntelPower LibraryShop main store

Explainer

Why an Upstream Instantaneous Setting May Not Cut Arc Flash

Electrical safety and codes Published 7 min read

Short answer

Setting an upstream 4.16 kV feeder relay and a 480 V incomer both to instantaneous shortens clearing only when the upstream pickup detects the fault and its breaker interrupts it first. On a 480 V bus fed through a transformer, the upstream relay often already picks up on the reflected fault current, so the change adds nothing; every intentional delay, including ride-through delays for transformer inrush, lands directly in the arcing time and raises incident energy.

On this page
  1. What an instantaneous element actually changes
  2. The upstream relay may already see the low-voltage fault
  3. Line side and bus side are different fault locations
  4. Every delay lands in the arcing time
  5. Example: does the feeder pickup see the bus fault through the transformer?
  6. Checking the maintenance setting before you rely on it
  7. What the standards ask you to show
  8. Questions asked

Flipping both relays to instantaneous feels like the obvious fix for a hot 480 V bus, and it often does nothing. An instantaneous element clears faster only when its pickup detects the fault and its own breaker interrupts it before any other device does. On a 480 V bus fed through a 4.16 kV/480 V transformer, the upstream feeder relay usually already sees the reflected fault current, so enabling its maintenance group changes no clearing time at all. What actually moves incident energy is arcing time, and every intentional delay you add — 0.01 s of coordination margin, 0.2 s of transformer inrush ride-through — lands in it. This article shows you how to tell, from your own study, which relay sets the clearing time at each fault location, and what a delay costs.

What an instantaneous element actually changes #

An instantaneous element trips with no intentional time delay once measured current exceeds its pickup. The pickup is a detection threshold, not a ceiling on fault current: the source impedance and the transformer impedance decide how much current an arc draws. A 10 kA available fault delivers 10 kA whether the pickup sits at 5 kA or at 2 kA, and once the pickup is already below the available current, lowering it further changes neither the arcing current nor the arcing time, so it changes no incident energy either. What an instantaneous element buys is speed, and only through time: it removes the time-delay band between pickup and trip. If the fault current already sits deep in the instantaneous region of the normal setting, the relay was never waiting there, and the maintenance setting has nothing to remove.

Arcing time in an IEEE 1584-2018 calculation is the total clearing time: the relay or trip-unit decision time plus the breaker's own opening and interruption time. A pickup change can only shorten the first part. If the decision part is already a few cycles, only a faster breaker, a current-limiting fuse or light-based arc sensing shortens the total.

The upstream relay may already see the low-voltage fault #

On a bus fed from a medium-voltage feeder through a transformer, a bus fault reflects to the feeder side scaled by the transformer's voltage ratio. If that reflected current is above the feeder relay's phase instantaneous pickup, the feeder has picked up on every low-voltage bus fault since the day it was set, and its breaker's time is already inside the study's normal-case clearing. Enabling its maintenance group then removes nothing. The study, not intuition, tells you which relay picks up and which breaker interrupts first at each fault location — the same question behind what clearing time applies to a transformer secondary arc. Pickup also depends on where the fault sits relative to the CTs, so it is worth reading how instantaneous current pickup depends on fault location before you assume the incomer covers the line side.

Line side and bus side are different fault locations #

When a lineup shows high incident energy on both the line side and the bus side of the incomer, those are two different cases in the study and they can have two different clearing devices. The incomer relay responds only to current its CTs measure, so a fault on the line side of those CTs is invisible to it and falls to the medium-voltage feeder. Trace each labeled location to the relay that detects it and the breaker whose contacts interrupt it before you touch a setting.

That mapping also identifies the one case where enabling the upstream instantaneous genuinely helps: a fault the incomer cannot see, where the feeder's time delay is what the incident energy is made of. There, speeding the feeder is the whole game.

Every delay lands in the arcing time #

Incident energy scales linearly with arcing time at a given arcing current, so any intentional delay adds its full value to the result. A fault that would clear in one cycle, 0.017 s at 60 Hz, clears in 0.217 s behind a 0.2 s ride-through delay — thirteen times the incident energy at the same current. A 0.01 s delay is smaller but not free; keep it only where the study shows a coordination need worth the energy it adds.

For the transformer inrush problem, the cleaner answer is operating discipline, not delay: do not energize the transformer while the maintenance group is active, and the inrush never meets the fast pickup. If pickup sizing does have to account for energization, size it against the inrush you can actually close in — with several transformers on one feeder that is the sum, as sizing a pickup against parallel transformer inrush explains. And remember that breaker operating time is part of arcing time, so a fast trip initiation from a light- or current-based arc-flash sensing element helps only as much as the breaker behind it lets it.

Example: does the feeder pickup see the bus fault through the transformer? #

The inputs, from the case's coordination model: available three-phase fault current at the 480 V bus of 10 kA (this worked example's figure; use your study's own number), and a transformer rated 4.16 kV primary and 480 V secondary.

The rule in words: for a balanced three-phase fault, the current the primary feeder carries equals the secondary fault current multiplied by the secondary voltage and divided by the primary voltage.

The arithmetic: 10,000 A × 480 V ÷ 4160 V = 1154 A.

The result: the medium-voltage feeder sees about 1154 A for that bus fault.

The decision: any feeder instantaneous pickup set below 1154 A already picks up on this fault, so enabling its maintenance group cannot shorten the clearing time of a low-voltage bus fault — the incomer breaker is the first to interrupt and it sets the incident energy at that location. If the pickup sits above 1154 A, the feeder never detects the fault and the same conclusion holds. Only a fault the incomer's CTs do not measure leaves the upstream element something to speed up. Per-phase fault types on a delta–wye transformer reflect at ratios other than the simple voltage ratio, so run each fault type in the model instead of scaling this one number.

Checking the maintenance setting before you rely on it #

Check the pickup against the minimum modeled fault at each location the group protects, not only the maximum — the minimum case decides whether the relay detects the fault at all. Then check it against the largest motor or motor-group starting current that can flow while the group is active: a maintenance instantaneous set below that inrush nuisance-trips the first time someone starts a big motor during the switch, the same trap described in motor start peaks versus instantaneous breaker settings. Remote load faults on the bus can also exceed a low pickup, so include them in the model.

Commission the change the same way you would any protection setting: confirm in the relay that the maintenance group is actually the active setting group, identify it unambiguously on the gear — a labeled selector and an indication light beat a note in a procedure — and record the before and after incident energy results in the study file. One reported case dropping to Category 2 tells you the method works when the numbers line up; your own minimum fault, starting cases and coordination decide your numbers.

Settings work on a live lineup is energized electrical work: de-energize, lock out and verify absence of voltage before opening any cubicle, and follow NFPA 70E, 2024 edition, for any task that must stay energized.

What the standards ask you to show #

NFPA 70E, 2024 edition, requires an incident energy analysis that reflects the protective settings actually installed, so a settings change means rerunning the affected fault locations and relabeling. IEEE 1584-2018 supplies the calculation model: it takes the arcing current from the system, the arcing time from the device that interrupts — breaker operating time included — and applies a two-second cutoff on the assumption that a person can move away from the arc, which is not permission for slow clearing where the task pins you in place. Requirements differ by country, edition and local amendment, so confirm both with your authority having jurisdiction and the relay manufacturer's documentation.

The decision, case by case. For a low-voltage bus fault the incomer sees and clears, enable the incomer maintenance group and leave the upstream feeder alone. For a line-side fault the incomer cannot measure, the medium-voltage feeder maintenance instantaneous is the only fast option — set it with no intentional delay and bar transformer energization while it is active. For any proposed delay, compute the arcing-time ratio it adds before accepting it, and keep it only against a coordination need the study demonstrates.

Questions asked

What pickup should the maintenance group use?

Set it below the minimum modeled fault current at every location the group is meant to protect, and above the largest motor or motor-group starting current that can flow while the group is active. Check remote load faults on the low-voltage bus too, because a low pickup can see them. The minimum case governs sensitivity; the maximum case only names the predicted clearing device.

Why did nothing change after we enabled the upstream instantaneous group?

Either the feeder pickup was already below the fault current reflected through the transformer, so it picked up on those faults all along, or the study's clearing device for that location was never the feeder breaker. Read the clearing-device entry the study reports for each fault location before concluding that the settings change failed.

Does lowering the instantaneous pickup reduce incident energy?

No. The pickup decides when the relay detects a fault, not how much current the arc draws. Once the pickup is below the available fault current, the arcing current and the clearing time are unchanged, so the incident energy is unchanged. Speed, not extra sensitivity below the fault level, is what cuts energy.

Do panels need new labels after a settings change?

Yes. NFPA 70E, 2024 edition, expects the incident energy analysis to reflect the protective settings actually installed, so rerun every fault location whose clearing device changed and apply updated labels before anyone works to the old numbers. Editions and local amendments differ, so confirm the labeling requirement with your authority having jurisdiction.

Keep reading

  • Selection guide

    When a Class L fuse actually cuts arc flash energy

    A current-limiting Class L fuse reduces arc flash incident energy only when the calculated arcing current at the fuse exceeds its current-limiting threshold, roughly 20 to 50 times its rating for large time-delay sizes. Below that threshold the fuse clears on its time-delay curve and can leave incident energy far above a static-trip breaker, so fuse size, arcing current and coordination get checked separately.

    Electrical safety and codes

  • Explainer

    How an overdutied breaker changes your arc flash study results

    A 25 kA breaker with 32 kA available fails the interrupting-rating requirement of NEC 110.9, but it voids an arc-flash result only where that result credits the breaker with clearing the modeled arcing current. In that case, take the clearing time from the next upstream device, rescale the incident energy, relabel, and replace the breaker.

    Electrical safety and codes

  • Explainer

    What clearing time applies to a transformer secondary arc

    An arc ahead of a transformer secondary main breaker is cleared upstream, so the label's clearing time comes from the primary device's total-clearing curve read at the arcing current reflected to the primary (I_pri = I_arc × V_sec / V_pri), capped at 2 s where the curve is slow or unverified. The quoted 32,000 A assumes an infinite utility source; get the real fault duty, because lower current means longer clearing time.

    Electrical safety and codes