Why arc-resistant switchgear doesn't lower calculated incident energy
Short answer
Arc-resistant construction redirects an internal arc's pressure and hot gases away from the worker; it changes none of the IEEE 1584 study inputs, so a 10 cal/cm² label stays 10 cal/cm². Only closed-door tasks such as breaker operation and racking can be reclassified under the NFPA 70E task tables, and intrusive work on exposed bus gets no credit at all.

On this page
- The study and the construction measure different things
- What IEEE C37.20.7 actually tests
- Worked example: a 10 cal/cm² lineup replaced with arc-resistant gear
- Where the credit actually lands: closed-door tasks
- Open-bus work gets no credit
- Field changes end the tested configuration
- The decision
- Questions asked
Replacing a switchgear lineup with arc-resistant gear does not lower its calculated incident energy. The IEEE 1584 study depends on fault current, clearing time, arc gap, working distance and enclosure dimensions, and arc-resistant construction changes none of those numbers: it redirects an internal arc's pressure, hot gases and expelled material away from the worker while the doors are closed and the exhaust path is intact. A lineup labeled 10 cal/cm² keeps that value after the replacement. What changes is the task classification: closed-door breaker operation and closed-door racking can be credited under the NFPA 70E task tables, and intrusive work on exposed bus cannot.
The study and the construction measure different things #
Incident energy is a calculated thermal exposure at a stated working distance, produced by the IEEE 1584, 2018 edition, model from the bolted fault current, the clearing time of the protecting device, the electrode gap, the enclosure size and the working distance. Arc-resistant construction is a mechanical design feature: pressure-rated enclosures, latches, shields and a planned exhaust route, verified by test.
The two records never interact numerically. The construction does not remove the arc or shorten its duration, so no input to the calculation moves when the designation appears on the nameplate. This is also why the question "how much energy does it divert" has no answer in the units of the study: the test standard, IEEE C37.20.7, evaluates whether the assembly contains and redirects the arc effects, using indicators such as externally placed cotton panels, and it does not produce a calorimetric reduction factor for the IEEE 1584 model.
What IEEE C37.20.7 actually tests #
IEEE C37.20.7, 2024 edition, is the recommended practice covering procedures for testing and evaluating the performance of metal-enclosed and metal-clad switchgear, rated through 52 kV, during internal arcing faults. The test establishes two accessibility types:
- Type 1: the gear must be arc-resistant at the front of the equipment only.
- Type 2: the gear must be arc-resistant at the front and at other designated surfaces, so a worker at the rear or side of the lineup also stands behind a tested face.
The result of a passed test is a documented rating with a documented configuration, not a generic property of the steel. When you evaluate a lineup, read the rating the way you would read it on any equipment: the arc-resistant rating on a low voltage MCC carries the same kind of type and condition information you need to see on switchgear. Ask the manufacturer for the type-test report and the listing documentation, and check that the report names the accessibility type and the exact tested arrangement before you credit anything.
Worked example: a 10 cal/cm² lineup replaced with arc-resistant gear #
The inputs. Your existing lineup carries an arc flash label of 10 cal/cm² at the study's working distance (the case you described). Say the study behind that label used a bolted fault current of 20 kA from the utility and transformer data, a clearing time of 0.25 s from the upstream relay and breaker curves, and the gap, enclosure dimensions and working distance from the manufacturer's drawings. Those current and time figures are example values; substitute your own from the study's input pages. The replacement is arc-resistant gear of the same rating, with the same upstream protection.
The rule. To first order, incident energy scales with the arcing current and the clearing time when the other inputs are fixed; more exactly, the IEEE 1584, 2018 edition equations are nonlinear, but they are deterministic: identical inputs give an identical output. The arc-resistant designation is not an input to the model.
The arithmetic.
E_new = E_old x (I_arc,new / I_arc,old) x (t_new / t_old)
= 10 cal/cm² x (20 kA / 20 kA) x (0.25 s / 0.25 s)
= 10 cal/cm² x 1 x 1
= 10 cal/cm²
The fault current is unchanged because the source impedance and transformer are unchanged. The clearing time is unchanged because the same upstream device clears the fault. Nothing else moved, so the new label is the old label.
The result. The replacement lineup is labeled 10 cal/cm², same as before. The only justification for a new number is a genuine input change: if the new lineup has different enclosure dimensions or a different gap, rerun the study with those dimensions and let the geometry, not the designation, move the value.
The decision. Keep the label. Reclassify only the closed-door tasks under the NFPA 70E task table, and leave the calculated boundary and PPE for open-panel work exactly as the study states.
Where the credit actually lands: closed-door tasks #
The task-based credit is real and it is documented. The 2009 edition of NFPA 70E, Table 130.7(C)(9), listed the operation and racking of a circuit breaker in arc-resistant switchgear, Type 1 or Type 2, with the doors closed, at the lowest hazard category. Two rules come with that entry, and they carry into how the current editions handle arc-resistant equipment:
- The door condition is part of the credit. The entry applies only with doors closed and the equipment in its tested, assembled configuration. Open the compartment and the credit is gone.
- A task category is not an incident-energy value. Category 0 in the 2009 table was a PPE category for a defined task, not a statement that the bus contains zero energy. Never write 0 cal/cm² on a label because the gear is arc resistant; the label carries the study result, and the task table carries the PPE decision. Category labels have changed since 2009, so apply the table in the edition your site has adopted, and confirm it with the authority having jurisdiction and the equipment documentation. The same door-closed logic governs the NFPA 70E table limits for operating switchgear breakers.
Open-bus work gets no credit #
Your instinct is correct: arc resistance protects non-intrusive work only. The moment a cover comes off and energized bus is exposed at the worker's location, the containment and exhaust path are no longer between the worker and the arc, and the task is ordinary energized electrical work. The study value applies in full, and the incident energy that applies to a LOTO voltage test on a breaker applies here too, because voltage verification is itself an open-panel task.
Insulated bus does not change this answer. Insulation lowers the probability that an arc initiates, which is a risk reduction worth having, but no calculation or task table credits probability, and some exposed metal always remains at terminations and breaker stabs. The decision: de-energize, lock out and verify absence of voltage before any intrusive work on an arc-resistant lineup, exactly as on any other lineup.
Field changes end the tested configuration #
The rating belongs to the complete assembly as tested. A field-cut opening, a replacement cover, changed fasteners, a blocked exhaust plenum or a retrofit viewing pane alters the pressure containment and the exhaust path, and the original test no longer speaks for that assembly. The same logic applies to temperature-monitoring retrofits: IR windows on arc-resistant switchgear and their C37.20.7 compliance have to be evaluated as an enclosure modification, not as a bolt-on accessory.
Before cutting or drilling the enclosure:
- Get the switchgear manufacturer's written requirements for the modification.
- Confirm whether the change needs a listing evaluation or a field inspection to keep the assembly's ratings.
- Verify that doors, latches, shutters, vents and the exhaust route remain in their tested operating condition afterward.
If the manufacturer will not support the modification, do not make it on gear whose arc-resistant rating you intend to credit.
The decision #
- Calculated incident energy: unchanged by the arc-resistant designation. Keep the study result until a real input changes.
- Closed-door operation and racking: credit under the NFPA 70E task table for arc-resistant switchgear, doors closed, using the edition your site adopts. This is a PPE and work-practice decision, never a label revision to zero.
- Any task on exposed bus: no credit. Full study value, full PPE, or de-energize first.
- Verification: the manufacturer's IEEE C37.20.7 type-test report and listing documentation, naming the accessibility type and tested configuration. Without them, treat the gear as ordinary switchgear in every respect.
Questions asked
Does insulating the bus make a lineup arc resistant?
No. Arc resistance is a tested property, and only a manufacturer's test report to IEEE C37.20.7 supports the term. Insulated bus lowers the likelihood that an arc starts, which no incident-energy calculation credits, and the bus is still energized whenever a cover is off.
Who verifies that switchgear is arc resistant?
The manufacturer, through a type-test report to IEEE C37.20.7, plus the listing documentation for the product line. Ask for both, and check that the report names the accessibility type and the exact tested configuration. A catalog description, a stronger door or an exhaust duct alone is not evidence.
What is the difference between Type 1 and Type 2 arc resistance?
Type 1 gear is tested arc-resistant at the front of the equipment only. Type 2 gear is tested at the front, rear and sides, so a worker at the rear of the lineup also stands behind a tested surface. A Type 1 lineup offers no tested protection to anyone positioned at its rear or sides.
Does remote racking reduce the calculated incident energy?
No. Remote or extended-shaft racking moves the operator away from the equipment, but the study number at the working distance does not change. It addresses exposure, not energy, so it is a work-practice and PPE decision made under your electrical safety program, not a revision to the label.
The replacement lineup is physically larger. Does the study change?
Yes, rerun it. Enclosure height and width and the arc gap are IEEE 1584 inputs, so different dimensions produce a different result in either direction. That change comes from geometry, not from the arc-resistant designation, which still contributes no numerical credit to the calculation.