Why high resistance grounding can raise calculated incident energy

Electrical safety and codes Published 7 min read By Current Intel engineering team

Short answer

High resistance grounding caps a line-to-ground fault at a few amperes, so that arc cannot sustain — a genuine risk reduction. IEEE 1584-2018 still scores a three-phase arc, and its grounded-system correction is withheld from HRG buses, so the calculated incident energy can come out slightly higher than for the same bus solidly grounded. Use the calculated value for the label and PPE; no edition of the standards grants formal credit for HRG.

On this page
  1. What high resistance grounding does to a ground fault
  2. What the IEEE 1584-2018 calculation models
  3. Severity on the label, likelihood in the program
  4. Worked example: the resistor and fault power on a 480 V HRG bus
  5. Reading a study that comes back higher on the HRG bus
  6. Questions asked

High resistance grounding caps a line-to-ground fault at a few amperes, so an arcing line-to-ground fault cannot deliver enough power to hold itself across the gap and self-clears. The arc flash calculation does not score that event. IEEE 1584-2018 models a three-phase arcing fault, and the grounded-system correction that lowers the calculated arcing current applies to solidly grounded systems only, so a high-resistance-grounded or ungrounded bus can calculate slightly higher incident energy than the same bus solidly grounded. Both facts are true and they describe different events. Use the calculated three-phase value for the label and the PPE: neither IEEE 1584-2018 nor NFPA 70E, 2024 edition, nor OSHA's work-practice rules grants formal credit for high resistance grounding on that number. Confirm the current editions with your authority having jurisdiction.

What high resistance grounding does to a ground fault #

An HRG system connects the source neutral to ground through a resistor, sized so a line-to-ground fault draws a few amperes — a design choice, normally picked above the system's capacitive charging current so the ground-detection relay can see a real fault. The first ground fault therefore draws its small limited current, trips nothing, and raises an alarm while the crew finds and clears it in an orderly way. That alarm-and-locate behavior is the operating reason plants buy HRG.

The physics follows from the limit. A fault confined to a few amperes at the line-to-neutral voltage can push only a small amount of power into an arc, orders of magnitude less than an arcing fault carrying kiloamperes, so the arc cannot hold itself across the gap. It self-clears instead of escalating into the phase-to-phase or three-phase event that does the damage, and most faults begin as line-to-ground events, which is exactly the escalation path HRG cuts off. NFPA 70, the National Electrical Code, 2023 edition, permits high-impedance grounded neutral systems under Article 250.36 only where qualified persons service the installation and ground-fault detection with alarm stays in service; confirm the article's details with your authority having jurisdiction and the equipment documentation.

What the IEEE 1584-2018 calculation models #

Incident energy under IEEE Guide 1584, 2018 edition, comes from a model of a three-phase arc burning inside an enclosure. The arcing current is derived from the bolted three-phase fault current, the system voltage, the conductor gap and the box size, and the grounding configuration enters as a correction to the arcing current: when the system is modeled as grounded, the method reduces the corrected arcing current. A high-resistance-grounded or ungrounded system takes no reduction, so its arcing current — and with it the calculated incident energy — comes out slightly higher. The 2002 edition made the same split more crudely: it divided systems into grounded and ungrounded and put impedance-grounded systems in the ungrounded case.

The resistor's few amperes are invisible next to the kiloamperes of a three-phase arc, so HRG neither limits nor feeds the modeled event. That is why why single-line-to-ground fault current does not change the arc flash result holds generally, and why the SLG risk and the three-phase severity need separate answers rather than one number. For how the grounded-versus-ungrounded correction is picked on a delta system, see choosing the IEEE 1584 grounded-versus-ungrounded coefficient on a delta system.

Severity on the label, likelihood in the program #

The label carries severity: incident energy in cal/cm² at a working distance, the consequence if the modeled three-phase arc happens at that spot. HRG acts on likelihood. The common initiating event is a line-to-ground fault; on an HRG system it stays a few-ampere alarm and never grows into the three-phase event the label prices. Probability and consequence are different engineering quantities, and a calculation returns one number for one of them — which is why the label number can rise while the system gets safer.

No edition of the governing documents moves that credit onto the label. NFPA 70E, 2024 edition, Article 130.5, makes the incident energy analysis the basis for the label's incident energy and the PPE selection, and its arc flash risk assessment estimates the likelihood of occurrence for a task without any rule that high resistance grounding lowers the required PPE or the calculated value. IEEE 1584-2018 has no HRG term in the model. OSHA addresses arc-flash hazards through the electrical safety-related work practices rules of 29 CFR 1910 Subpart S, and those rules add no credit mechanism either. Confirm all three with your authority having jurisdiction and the current editions before you build a program around them.

Current limitation does earn modeled credit when it acts on the phase current: a current-limiting Class L fuse lowers the arcing current the method computes, and the energy falls with it — when a Class L fuse actually cuts arc flash energy shows where that holds. HRG limits only the ground current, so the three-phase model has nothing to credit.

Worked example: the resistor and fault power on a 480 V HRG bus #

The inputs, each illustrative and typical of the case: a 480 V, three-phase, wye-connected service; a line-to-neutral voltage of 480 V ÷ √3 = 277.1 V; a design ground-fault current of 5 A, chosen in the few-ampere class above the system's charging current; and continuous duty, because the resistor must hold a bolted ground fault while the crew locates it.

The rule, in words: the grounding resistor's resistance equals the line-to-neutral voltage divided by the design ground-fault current, and its dissipation during a solid fault equals the line-to-neutral voltage multiplied by that current.

The arithmetic: R = 277.1 V ÷ 5 A = 55.4 Ω, and P = 277.1 V × 5 A = 1385.5 W, about 1.4 kW.

The result: every bolted line-to-ground fault on that bus is capped at 5 A and can deliver at most about 1.4 kW into the fault path, regardless of how many tens of kiloamperes the source can push into a three-phase fault. Treat this as a design estimate and check the installed resistor's rating plate and the governing code against it.

The decision follows a clean threshold. An event bounded at 5 A and about 1.4 kW is the small one — too little power to sustain an arc at the line-to-neutral voltage — and that is the SLG risk reduction HRG is bought for. An event carrying kiloamperes at the same bus is the three-phase event the study models, and the label's incident energy belongs to it. The threshold works as a field check too: if a ground fault on a system you were told is resistance-grounded pulls tens of amperes, the neutral grounding path is not limiting, and the alarm-and-locate practice is not safe to assume. Verifying the resistor means opening its enclosure or the switchgear, and that work needs an electrically safe work condition first — de-energize, lock out and verify absence of voltage, as NFPA 70E, 2024 edition, Article 120 requires — before anything is opened.

Reading a study that comes back higher on the HRG bus #

When the HRG case calculates more energy than the solidly grounded comparison, work through these:

  • Check the grounding input against the field. The model needs the true source configuration — solidly grounded wye, ungrounded delta, or HRG through a resistor or grounding transformer — because that flag decides whether the arcing-current correction applies. An input marked grounded on an HRG bus understates the result.
  • Confirm you are comparing like events. Both numbers are three-phase results; the HRG number is higher because the correction is absent, not because the model found a bigger fault.
  • Expect a modest difference. The correction nudges the arcing current slightly and does not change the hazard class. If the HRG case doubles the energy, suspect a wrong working distance, clearing time or bus input before crediting the grounding.
  • Keep severity and likelihood separate. The label carries the calculated incident energy and the PPE that follows it; the study documentation records the grounding scheme as risk information for the electrical safety program.

The decisions, by case. On a solidly grounded bus, the label carries the three-phase result with the grounded-system correction applied. On an HRG bus, the label carries the three-phase result without that correction — use the higher calculated value and do not lower it for the grounding scheme. On a line-to-ground fault through the resistor, the event is the small one the calculation never scores: follow the alarm-and-locate procedure, and treat the tracing itself as energized work under your electrical safety program's rules.

Questions asked

What happens if a second ground fault occurs while the first is still on the system?

A fault on a second phase completes a phase-to-phase path, and the current is then limited only by the impedance between the two fault points, not by the grounding resistor. That is why plants run high resistance grounding with an alarm-and-locate turnaround measured in hours, and why some controls trip selected feeders once two ground faults are detected at once. Keep the first fault from becoming the second.

Does the higher calculated energy mean the HRG system is more dangerous?

No. The higher number is the three-phase event scored without the grounded-system correction — a modeling convention, not evidence that the resistor added energy. The system's total risk profile improves because the likeliest initiating event stays small and alarmed. Present severity from the label and likelihood from the grounding record, and the picture is consistent for reviewers and crews alike.

How do you test a grounding resistor?

De-energize the system, establish an electrically safe work condition, and measure the resistor bank with an ohmmeter against the design value; open paths and corroded elements only show up this way. The resistor is rated to carry its fault current continuously, so a damaged element is a real failure mode. Follow the resistor manufacturer's documented test guidance and your site's switching procedures.

Can the arc flash label mention the high resistance grounding?

NFPA 70E, 2024 edition, lets the label carry information beyond its required items, and many plants note the grounding scheme next to the incident energy data. The note is informational: it records why the system is likelier to stay alarmed rather than escalate, and it changes nothing about the listed incident energy, working distance or PPE category. Keep the grounding record in the study documentation too.

How does a pulsing HRG control help find the fault?

When a ground fault alarms, many HRG controls briefly short out the grounding resistor on a timer, which makes the ground-fault current step between two values. A technician follows the feeders with a clamp ammeter and finds the one whose current pulses at the same rate. This happens near faulted equipment on a live system, so apply the work practices of NFPA 70E, 2024 edition, and the control vendor's documented procedure.

Keep reading

  • Explainer

    Why single line to ground fault current does not change arc flash

    Changing transformer or generator grounding from low-resistance to solid moves the single line to ground fault current sharply and leaves three-phase bolted fault current untouched. Because IEEE 1584 incident energy is calculated from the three-phase current and the protective device's clearing time, arc flash results do not change; only ground-fault relay settings and coordination need rework.

    Electrical safety and codes

  • Troubleshooting

    Checking a delta high leg arc flash calculation's numbers

    The 9.127 kA at the panelboard checks out against the 11.33 kA infinite-source terminal limit once utility impedance is counted. The 73 cal/cm² hinges on clearing time: the referred bolted current clears the 600 A primary breaker in 0.033 s, but IEEE 1584 sets device time from the arcing current, which falls below the 3,600 A pickup into the thermal band — so the label is credible until the study file shows otherwise.

    Electrical safety and codes

  • Explainer

    IEEE 1584-2018 fault current range limits above 600 V

    Above the 600 V band edge the IEEE 1584-2018 model was verified only to 65 kA of bolted fault current, so a 690 V bus at 70 kA sits outside the documented range by 5 kA. Run the range check, keep the IEEE result as a labeled out-of-range sensitivity case, cross-check the Ralph Lee method, and use the higher incident energy for PPE until an engineer signs the method decision.

    Electrical safety and codes