Current IntelPower LibraryShop main store

Explainer

IEEE 1584 grounded vs ungrounded delta: picking K2

Electrical safety and codes Published 6 min read By Current Intel engineering team

Short answer

IEEE 1584 classifies a delta system by its intentional connection to ground, not by its winding shape. A corner-grounded or midpoint-grounded delta is grounded and takes K2 = -0.113; a bonding-only three-wire delta and any resistance-grounded system group with ungrounded and take K2 = 0, which raises the calculated incident energy by about 30% relative to the grounded choice. The coefficient pair belongs to the 2002 equations; the 2018 edition takes grounding as a model input instead.

On this page
  1. What the grounding coefficient does
  2. Classify the delta by its connection to ground
  3. Why equal phase currents prove nothing
  4. Working K2 for a bonding-only 480 V three-wire delta
  5. Pick the category, then record it
  6. Check the model against the plant
  7. Questions asked

IEEE 1584 does not read a delta system's grounding off its winding shape or its phase currents. It reads it off the intentional connection between a current-carrying conductor and ground. A corner-grounded delta or a midpoint-grounded delta is a grounded system and takes K2 = -0.113 in the 2002 empirical incident energy equations. A three-wire delta that carries only equipment bonding, and every resistance-grounded system including high-resistance grounding, lands in the ungrounded/impedance-grounded group and takes K2 = 0, the value that yields the higher incident energy. The coefficient belongs to the IEEE 1584-2002 formulation; the 2018 edition replaced those equations, so confirm which formulation your study software applies before entering anything. Below is the connection test, a worked comparison of the two coefficients, and the decision for each delta arrangement you will meet.

What the grounding coefficient does #

IEEE 1584-2002, the edition of the arc-flash hazard calculation guide that introduced K2, adds the grounding term to the base-10 logarithm of the normalized incident energy: K2 = 0 for ungrounded and impedance-grounded systems, K2 = -0.113 for grounded systems. Because the term sits inside a logarithm, the grounding choice multiplies the normalized incident energy, and the final number built from it, by a fixed factor no matter what the voltage, gap or clearing time turns out to be.

That factor is about 1.30: the ungrounded/impedance-grounded entry scores roughly 30% more incident energy than the grounded entry with every other input held equal. Misclassification is therefore not a rounding error. It shifts every result in the study at once, and always toward lower numbers when a system is wrongly entered as grounded. If you want the physics behind that direction, the knowledge-base page on why IEEE 1584 gives ungrounded systems higher incident energy works through it.

The 2018 edition retired this empirical formulation and its fixed coefficients; the current model takes system grounding as an input to its arc current and voltage calculations instead. The physical classification is the same, only the entry point differs.

Classify the delta by its connection to ground #

Arrangement at the source IEEE 1584 category K2
Corner-grounded: one phase solidly connected to ground Grounded -0.113
Midpoint-grounded: a winding midpoint connected to ground Grounded -0.113
Three-wire delta, equipment bonding only Ungrounded 0
Resistance grounded, including high-resistance grounding Ungrounded/impedance grounded 0
Reactor or other intentional impedance Ungrounded/impedance grounded 0

The distinction that trips most classifications is bonding versus system grounding. Bonding connects enclosures, raceways and metal parts to ground so a fault has a low-impedance return path and touch voltage stays low; it never connects a phase conductor to ground. A traditional three-wire delta with bonding and no grounded conductor therefore has no intentional system grounding connection, and the equations treat it as ungrounded.

A corner-grounded delta has one of its three phases deliberately tied to ground at the source. That is a solid connection, so it belongs with the grounded systems no matter that the windings are delta-connected. A resistance-grounded delta does touch ground, but the resistor deliberately limits ground-fault current to a fraction of what a solid bond would deliver, and the 2002 formulation groups it with the ungrounded side for exactly that reason; the worked method for calculating incident energy on high-resistance grounded systems follows the same grouping.

Why equal phase currents prove nothing #

A delta secondary and a wye secondary can deliver the same phase currents and the same three-phase fault current. That equality says nothing about grounding: the classification asks whether a current-carrying conductor is intentionally connected to ground, and through what impedance.

Two corrections to the reasoning that usually leads engineers astray on this point. First, the governing installation code does not demand that every distribution system be grounded: NFPA 70, 2023 edition, Article 250 permits defined systems to run ungrounded and calls for ground detection on ungrounded systems, and requirements vary by edition and local amendment, so confirm the applicable text with the authority having jurisdiction. Second, the arc-flash calculation already assumes a three-phase arc; the grounding term does not swap a ground fault into the model, it corrects the result for how the system behaves during that arc. Classify from the connection and let the equation do its own work.

Working K2 for a bonding-only 480 V three-wire delta #

The case the classification question turns on: a 480 V three-wire delta MCC with equipment bonding present and no grounded conductor anywhere on the secondary. The arithmetic works on the grounding factor alone; an absolute incident energy would also need the arc gap, working distance, arcing current and clearing time, which this example does not set. Both coefficients are the documented IEEE 1584-2002 values, and they are dimensionless, so the voltage label does not enter the ratio.

  • Correct classification: no intentional system grounding connection, so the panel is ungrounded/impedance grounded, K2 = 0.
  • Misclassification being checked: the panel entered as grounded, K2 = -0.113.
  • Rule in words: K2 adds to the base-10 logarithm of the normalized incident energy, so the ratio between the two entries is 10 raised to the difference between the coefficients.
  • Arithmetic: difference = 0 - (-0.113) = 0.113; ratio = 10^0.113 = 1.30; inverted, 10^(-0.113) = 0.77.
  • Result: the correct ungrounded entry yields 1.30 times the normalized incident energy of the grounded entry; the grounded entry gives 0.77 times the correct one.

Decision: enter this panel ungrounded, with the coefficient at 0. Entering the grounded value understates every result for the panel by about 23% (1 - 0.77), enough to drop a task one PPE category; the page on selecting arc-flash PPE by category and incident energy shows how directly that number turns into clothing. If the as-built check later finds a phase solidly connected to ground at the source, reclassify as grounded and rerun the study.

Pick the category, then record it #

  1. De-energize, lock out and verify absence of voltage before opening any panel, terminal box or source equipment to trace grounding connections.
  2. Trace the source winding on the single-line diagram and on the as-built equipment, and list every intentional connection between a conductor, a winding midpoint or a neutral and ground.
  3. A solid connection at a phase or a winding midpoint: grounded category, grounded coefficient.
  4. Equipment bonding only, no grounded conductor: ungrounded category, K2 = 0.
  5. A grounding resistor in the connection: ungrounded/impedance-grounded group, K2 = 0.
  6. A reactor or other impedance network: still the impedance-grounded group and the same coefficient, unless the connection is solid; the empirical set offers no third value between the two.
  7. Record the classification, its basis and the equation edition in the study file, so a reviewer can reproduce the entry.

Check the model against the plant #

Compare the model to the as-built installation before accepting results: the source winding connection, the installed grounding hardware, and whether anyone read a bonding conductor as a system grounding connection. That single reading error is what flips a three-wire delta into the wrong category. Confirm which equation edition the software applies: the fixed coefficient pair lives in the 2002 empirical set, the 2018 model takes grounding as an input, and the physical classification is the same either way. Clearing time usually moves a result far more than grounding does; the companion article on whether ground fault clearing time should set arc flash incident energy walks through that trade. The calculation feeds the incident energy analysis that NFPA 70E, 2024 edition, requires as part of the arc flash risk assessment, so treat every number as an estimate to be checked against the study inputs and the equipment documentation, and confirm the applicable requirements with the authority having jurisdiction.

Questions asked

Does IEEE 1584-2018 still use K2?

No fixed coefficient survives in the current edition. IEEE 1584-2018 replaced the 2002 empirical equations with a model that takes system grounding as an input to its arc current and voltage calculations, so you select grounded or ungrounded/impedance grounded on an input screen instead of typing a number. The physical classification does not change between editions; only the entry point does. Check the software's own documentation to confirm which formulation it applies before trusting either result.

Is a corner-grounded delta grounded for the calculation?

Yes. One phase conductor is intentionally and solidly connected to ground at the source, which is exactly the condition the grounded category describes. Use the grounded classification, and confirm the connection at the service equipment, because some plants show a corner-grounded delta on the original drawing after the system was later converted and left unmarked. The classification follows the connection that exists in the switchgear, not the one on the paper.

Why does a high-resistance grounded system stay in the ungrounded group?

Because the grounding resistor deliberately limits ground-fault current far below what a solid connection would deliver, the 2002 formulation groups every system that is not solidly grounded together, on the side of the pair that yields the higher incident energy. Converting an ungrounded delta to high-resistance grounding is still a worthwhile upgrade: it adds controlled, detectable ground-fault current where an ungrounded system has none. The conversion does not move the calculation into the grounded category.

What standard explains the grounding types themselves?

IEEE 142, the recommended practice for grounding of industrial and commercial power systems, 2007 edition, describes solid, resistance, reactance and ungrounded arrangements in far more detail than IEEE 1584 gives. Installation requirements sit in NFPA 70, 2023 edition, Article 250, which permits defined systems to run ungrounded and calls for ground detection on them. Confirm the edition your jurisdiction enforces before labeling any system on a study one-line.

Can I use the grounded category because three-phase faults dominate?

No. The incident energy model already assumes a three-phase arc for every calculation; the grounding term does not change that assumption, it corrects the result for how the system behaves during that arc. Classification is a property of the connection to ground, not of which fault current is largest. On a delta with no grounded conductor there is no system neutral to ground, and no phase-current measurement will create one.

Keep reading

  • Explainer

    Arc flash data collection on a utility fed 480 V switchboard

    Before anyone opens a utility-fed 480 V switchboard to collect arc flash data, request the utility transformer, protective-device and riser data and model the line side, because the customer side of the service point is usually the highest-energy point in the plant and the main disconnect does not lower it. If the estimate can exceed 40 cal/cm², take the inspection to a full planned shutdown with the utility's fuses open.

    Electrical safety and codes

  • Explainer

    Arc flash labels for a dual-source VFD cabinet

    If opening the cabinet can expose the line-side terminals of both drives, apply one bounding arc flash label: the largest calculated incident energy at an 18 in working distance and the highest nominal voltage present, whatever source each number comes from. Keep both source-specific calculations in the incident energy analysis report so the energized work permit uses the case that fits the task.

    Electrical safety and codes

  • Explainer

    DC arc flash under NFPA 70E: when calculation is required

    NFPA 70E does not exempt DC systems from arc flash assessment. For each DC source and each task on it, either apply the task tables where their stated conditions are met or perform a DC incident-energy analysis with a documented method — the maximum-power and detailed arcing-current methods of Annex D.8.1, added in 2012 and carried forward since — then label the equipment. Battery strings and UPS DC circuits are assessed task by task, never dismissed for low voltage.

    Electrical safety and codes