Current IntelPower LibraryShop main store

Troubleshooting

Why one 120 V leg rises under load on the other leg

Power quality and harmonics Published 7 min read By Current Intel engineering team

Short answer

No. A voltage rise on the unloaded 120 V leg of a 120/240 V service usually comes from ordinary drop in a shared neutral, not from a bad connection. Measure both legs and the line-to-line voltage at one point, unloaded and again with a test load on one leg: if the 240 V drop is about half the 120 V drop the circuit is normal, and a clear departure points to excess resistance on the neutral or the hot side.

On this page
  1. Why does the other leg go up when a load starts?
  2. Is a small rise on the unloaded leg normal?
  3. How do I run the loaded-versus-unloaded voltage test?
  4. What do the drops tell me: neutral side, hot side, or normal?
  5. How do I find which section has the excess resistance?
  6. When should I stop using the circuit?
  7. Questions asked

No. A rise on the opposite 120 V leg does not by itself prove a bad neutral. In a center-tapped single-phase three-wire circuit the two legs share one neutral, and the neutral's voltage drop adds to the unloaded leg while it subtracts from the loaded one; sound wiring does this too. Normal and defective are separated by a comparison, not a single reading: at one point, measure both legs and the line-to-line voltage unloaded, then again with a known test load on one leg. A 240 V drop of about half the loaded leg's drop means the neutral is doing its job; a clear departure means excess resistance, and the direction of the departure tells you which side it sits on.

Why does the other leg go up when a load starts? #

The rise is the neutral conductor's own voltage drop showing up on the unloaded leg: a load on one leg sends its return current down the shared neutral, and that drop adds to the opposite leg's voltage while it subtracts from the loaded leg's voltage.

Illustrative example: an unloaded center-tapped circuit reads 120 V on each leg and 240 V line-to-line. A load on leg A draws enough current to lose 10 V around the whole loop, and with line and neutral conductors of equal size and length the loss splits evenly: 5 V in leg A's hot conductor, 5 V in the neutral. Leg A at the receptacle reads 120 − 5 − 5 = 110 V. Leg B reads 120 + 5 = 125 V, because the neutral's drop lands on it in the rising direction. The line-to-line reading falls by the hot's share alone: 240 − 5 = 235 V. For a resistive load the current, the drops and the supply voltages are essentially in phase, so plain arithmetic reproduces what the meter shows.

Is a small rise on the unloaded leg normal? #

Yes: as long as the line-to-line reading falls by about half the loaded leg's leg-to-neutral drop, the rise is ordinary conductor resistance, and a 2 V fall with a 1 V line-to-line fall at a receptacle is a normal pattern.

The code context is a recommendation, not a limit on this effect. NFPA 70, the National Electrical Code, 2023 edition, governs branch-circuit and feeder conductor sizing in Articles 210 and 215, and the informational notes with 210.19(A) and 215.2(A) recommend sizing so branch-circuit drop stays within 3 percent and feeder plus branch together within 5 percent, for reasonable efficiency of operation. Five percent of 120 V is 0.05 × 120 V = 6 V, leaving about 114 V at the farthest outlet as the outer recommended value. Confirm how your authority having jurisdiction treats those notes; they are not the pass/fail for the test below.

Two conditions change the expected ratio. The half-drop rule assumes the neutral is the same size as the hots from the test point back to the transformer; on a service with a reduced-size neutral, expect a normal result nearer 40 percent and judge the circuit by where the ratio changes between test points. And the loaded leg's own sag is the half that hurts equipment: a branch that dips far enough at start can stall a motor, as in why a single phase motor stalls on start at 200 V.

How do I run the loaded-versus-unloaded voltage test? #

Take six readings at one point with a meter rated for that measurement category: both leg-to-neutral voltages and the line-to-line voltage with the circuit unloaded, then the same three with a steady resistive test load of about 10 to 15 A on one leg.

  1. Switch off the other leg's loads as far as practical, so its current adds no drops of its own.
  2. At the test point, record unloaded leg A to neutral, leg B to neutral, and leg A to leg B.
  3. Plug the test load into leg A; a 1500 W resistive heater is a good choice. Confirm its current with a clamp meter or a plug-in meter.
  4. Without moving the meter, record the loaded leg A, leg B and line-to-line voltages.
  5. Compute each drop as the unloaded reading minus the loaded reading.
  6. Carry the three drops into the comparison in the next section.

Those steps use plug-in receptacles only. Repeating the test inside a panel, meter base or other enclosure is different work: de-energize, lock out and test for absence of voltage before removing any cover, and leave loaded measurements in an open enclosure to a qualified electrician following the energized-work procedures and PPE that NFPA 70E, 2024 edition, the standard for electrical safety requirements in employee workplaces, sets for that task.

What do the drops tell me: neutral side, hot side, or normal? #

The ratio decides it: with equal-size conductors the 240 V drop should land between roughly 40 and 60 percent of the loaded leg's drop, and a value clearly outside that band means excess resistance: under it on the neutral, over it on the loaded hot.

Same-point result under the test load Where the excess resistance sits Decision
Line-to-line drop about half the leg drop (40 to 60 percent) Nowhere beyond ordinary conductor drop Leave the circuit in service; the rise is normal
Line-to-line drop clearly under 40 percent of the leg drop The neutral path back to the transformer Locate and repair the neutral connection or conductor
Line-to-line drop clearly over 60 percent of the leg drop The loaded hot conductor Locate and repair that line's connection or conductor

The band is a screening judgment for this comparison, not a code limit. Three worked examples show how it reads, each a hypothetical input set.

Normal: unloaded readings are 120.0 V on leg A and 240.0 V line-to-line; with the heater drawing 12.5 A they are 118.0 V and 239.0 V. Drops: 120.0 − 118.0 = 2.0 V and 240.0 − 239.0 = 1.0 V, a ratio of 1.0 V ÷ 2.0 V = 50 percent. As resistance: hot conductor 1.0 V ÷ 12.5 A = 0.08 Ω; neutral (2.0 − 1.0) V ÷ 12.5 A = 0.08 Ω. Equal, exactly what equal-size conductors should give; leave this circuit alone.

Bad neutral: the same unloaded readings and the same heater, but loaded readings of 114.0 V and 239.5 V. Drops: 6.0 V and 0.5 V. Half of 6.0 V would be 3.0 V; the measured 0.5 V is 8 percent, far under the band. Resistance: hot 0.5 V ÷ 12.5 A = 0.04 Ω; neutral 5.5 V ÷ 12.5 A = 0.44 Ω, eleven times the hot. That excess is in the neutral path; go find it.

Bad hot conductor: loaded readings of 114.0 V and 236.0 V give drops of 6.0 V and 4.0 V, a ratio of 67 percent, with hot resistance 4.0 V ÷ 12.5 A = 0.32 Ω against a neutral's 2.0 V ÷ 12.5 A = 0.16 Ω. The excess sits in leg A's own conductor.

How do I find which section has the excess resistance? #

Repeat the identical test at points working back toward the transformer: the wiring between the last point that shows the normal ratio and the first point that shows the abnormal one contains the excess resistance, and that is the section to open and inspect.

The usual hiding places, in rough order of frequency:

  • The neutral's termination on the panel neutral bus, and neutral splices in receptacle chains.
  • Service-neutral splices and meter-base terminations, where oxidation on aluminum conductors raises resistance.
  • Corrosion where the run passes a wet or outdoor section.
  • An undersized neutral in part of the run, which behaves like excess resistance even when new.

Repair means cleaning and reterminating to the manufacturer's specified torque, or replacing the damaged conductor section, not replacing the neutral on the strength of a voltage rise alone. Then repeat the original test at the same point with the same load: the ratio should return to the band and the opposite leg's rise should shrink to match the loaded leg's drop.

When should I stop using the circuit? #

Stop using it when the swings are large or erratic: a leg climbing well above its nominal voltage, or lights brightening sharply whenever another appliance starts, is the signature of a neutral that is open or about to open.

With the neutral open, the two legs become a series divider across 240 V, and the lighter-loaded leg can rise toward it, taking out lamps and electronics on the way. That case is beyond a screening test: de-energize the circuit and get the neutral repaired before it is used again. The decisions, in one place:

  • Half-drop pattern within the band: ordinary conductor drop; leave the circuit in service.
  • Ratio clearly under the band: excess resistance in the neutral; locate and repair it before it fails.
  • Ratio clearly over the band: excess resistance in the loaded hot; locate and repair it.
  • Large or erratic swings: treat it as an open neutral; keep the circuit de-energized until repaired.

Questions asked

How big a test load gives a readable result?

Use a steady resistive load around 10 to 15 A at 120 V, for example a 1500 W heater. A small load like a lamp may move the leg only a few tenths of a volt, which hides a marginal connection. Record the actual current with a clamp meter or plug-in meter so each voltage drop can be converted into a resistance estimate.

Does the test work on a multiwire branch circuit with a shared neutral?

Yes. A shared-neutral multiwire branch circuit behaves like a small service: the shared neutral carries only the imbalance, so equal loads on the two legs cancel and the rise disappears. Run the test with the other leg's loads off, or their drops mix into your readings and distort the ratio.

Can the same comparison be used on a 208Y/120 three-phase service?

No. On a three-phase wye system each phase-to-neutral voltage responds to drops in its own phase conductor and in the neutral, and 208 V line-to-line does not stand in the same relation to the phase-to-neutral voltage, so the half-drop rule does not carry over. Apply the comparison only to single-phase three-wire center-tapped circuits.

What should be recorded before calling in an electrician?

Record the test point, the test load and its current, and all six voltages: both legs and the line-to-line reading, unloaded and loaded. Add every upstream point where the test was repeated and the ratio it gave. That record shows the next person which section changed the pattern without repeating the whole survey.

Keep reading

  • Selection guide

    Split core current transformer selection for power meters

    The meter input decides: a 5 A or 1 A secondary split core CT feeds a low-impedance current input and must stay shorted, while a voltage-output split core needs a high-impedance input. Then match the ratio to the load, add meter burden to lead resistance against the rated VA, and take class, window and insulation from the datasheet.

    Power quality and harmonics

  • Troubleshooting

    When swapped voltage leads change three-phase kW readings

    Neither set is trustworthy. With 242 V line-to-line and balanced line current, three-phase apparent power is fixed at 4.19 kVA; the displayed 2.31 kVA and 5.01 kVA both miss that value, so the element-to-phase pairing is wrong in both cases. Re-connect the analyzer per its three-phase, three-wire diagram, confirm the power triangle closes, then record the reading.

    Power quality and harmonics

  • Troubleshooting

    Tracing 480 V voltage swings that burn up welders

    515-520 V line-to-line on a 480 V system is 7.3-8.3% above nominal, past the ANSI C84.1 Range B service ceiling of 508 V, and it is a steady-state regulation problem until a transient capture proves otherwise. Measure line-to-line at the distribution panel, at both sides of the 480/480 isolation transformer, and at the welder terminals, then fix the tap or regulation at whichever stage the readings indict. Surge protective devices will not lower it.

    Power quality and harmonics