Troubleshooting
Why SKM shows zero fault current on the 480 V bus
Short answer
The zero is a result-field problem, not a calculation failure: ANSI Sym 3P Mom and ANSI Asym 3P Mom are momentary duty variables defined above 600 V, so they read 0 kA at a 480 V bus while ANSI 3P int populates. Confirm the bus is inside the study scope, then display the documented half-cycle symmetrical RMS low-voltage result and compare it with the breaker short-circuit rating.
On this page
- Why does SKM show 0 kA for fault current on this bus?
- Is SKM actually calculating the secondary bus?
- How do I get the fault-current datablock onto the one-line?
- Which result variable is the half-cycle fault current at low voltage?
- What should the secondary fault current be?
- Do I need the asymmetrical current for a low-voltage breaker?
- When should I take this to the software vendor?
- Questions asked
SKM is calculating your 480 V bus — you are reading medium-voltage result fields. ANSI Sym 3P Mom and ANSI Asym 3P Mom are momentary, first-cycle duty variables defined for systems above 600 V, so the study leaves them at 0 kA on a low-voltage bus instead of computing a duty they were never scoped for. ANSI 3P int populates because the interrupting calculation runs across the network, but it is not your half-cycle value. Confirm the bus is inside the study scope, then display the documented half-cycle symmetrical RMS low-voltage result and compare it with the breaker rating.
Why does SKM show 0 kA for fault current on this bus? #
Because the displayed variable is a medium-voltage quantity: the ANSI momentary fields apply above 600 V, and the study reports 0 kA for them on a low-voltage bus rather than calculating a duty the variable was never defined to hold.
This is a documented boundary, not a glitch. A GE application guide to the ANSI method applies the momentary rating only above 600 V and defines it as the RMS of the first-cycle asymmetrical current wave, checked against the closing and interrupting capabilities of medium-voltage breakers. The matching application rule multiplies the first-cycle current (E divided by ZM) by 1.6 and compares it with the momentary rating — a rule written for breakers rated 600 V and above, not for this gear. So the zero in a Mom field says nothing about available fault current: a transformer secondary at this level behind a typical distribution transformer has tens of kiloamperes available, as the worked example below shows.
Is SKM actually calculating the secondary bus? #
Yes — a populated ANSI 3P int value at that same bus proves the solver traced a path to it through both transformers, so the 0 kA you see is a field-selection problem, not a failed calculation.
Two transformers between the utility and the bus is not a limit for the solver; it needs a connected, energized path and complete component data. Work through this order:
- Open
Run > Balanced System Studies, selectSC and ANSI, and keep the method your project requires. - Click
Setupand confirm the bus scope: all buses, or a selected-bus list that includes the secondary. - Click
OK, thenRun, and read the calculation messages for anything affecting the path to that bus. - Check the model itself: utility short-circuit data, each transformer's kVA, voltage ratio and %Z, terminal connections, and the open or closed state of intervening switching devices.
- Rerun and confirm the target bus appears in the study output before changing anything on the one-line.
The source-search depth setting you suspected, quoted as "Bus. level away to find source", is not the fix here. With ANSI 3P int populated, the solver already found the source through both transformers, so leave the search settings alone and fix the displayed variable.
How do I get the fault-current datablock onto the one-line? #
With the one-line active, open Run > Datablock format and select BUS Fault Currents (A_FAULT); if the block does not appear, select the bus and turn on One-Line > Datablock > Visible.
A datablock reading 0 kA is not a missing datablock — it is a visible block whose chosen variable returns zero at that voltage level. Separate these four conditions before you change anything:
| What you see | Check first | What it settles |
|---|---|---|
| No datablock on the bus | Datablock format and One-Line > Datablock > Visible |
The block is assigned and shown |
| Datablock visible, a Mom field reads 0 kA | The variable's voltage-level applicability | Whether the field is defined at that voltage |
| No result for the bus in the study output | Bus scope, connectivity, study messages | Whether the study calculated the bus |
ANSI 3P int populated, Mom fields 0 kA |
The duty each variable represents | Which question the number answers |
A comprehensive bus fault-current report lists every variable the study computed at that bus, so compare it with your datablock before building a custom one. Custom datablocks beat the shipped formats here: you choose which variables appear, labeled with quantity and units.
Which result variable is the half-cycle fault current at low voltage? #
Use the ANSI first-cycle, half-cycle symmetrical RMS three-phase result from the low-voltage study — the quantity a low-voltage breaker's short-circuit rating is compared against — not the Mom fields and not ANSI 3P int.
SKM's A_FAULT documentation states the module calculates low-, medium- and high-voltage studies in compliance with the ANSI C37 standards; the low-voltage duty basis is C37.13, which covers low-voltage AC power circuit breakers. The documented application rule for that check: the breaker's short-circuit rating must be higher than the half-cycle symmetrical short-circuit current the software calculates. Find the exact variable name in your installed version's result-variable descriptions or the comprehensive report — versions differ, and guessing a variable name is how this problem starts. Then build or edit a datablock around that variable.
| Result variable | Behavior at the secondary bus | Engineering use |
|---|---|---|
ANSI Sym 3P Mom |
No usable value; reported on HV buses | Above-600 V first-cycle symmetrical duty |
ANSI Asym 3P Mom |
Displays 0 kA | Above-600 V first-cycle asymmetrical duty |
ANSI 3P int |
Populates | Interrupting duty on a later time basis; a path check, not a half-cycle value |
Confirm the edition of the C37 standards your project invokes with the equipment documentation and the authority having jurisdiction.
What should the secondary fault current be? #
For an example 1500 kVA transformer with a 480 V secondary and 5.75 % impedance on an infinite source, the half-cycle three-phase symmetrical current at the secondary terminals is about 31.4 kA, and SKM should land within a few percent of it.
The arithmetic, with every input stated (1500 kVA, 5.75 %Z, infinite primary source):
- Full-load current: 1500 × 1000 / (1.732 × 480) = 1,500,000 / 831.4 = 1804 A.
- Half-cycle symmetrical fault current: 1804 / 0.0575 = 31,380 A ≈ 31.4 kA.
The result is an upper-bound estimate to be checked against the governing code and the equipment documentation, because it neglects utility source impedance and everything between the transformer terminals and the bus. The hand method behind it is calculating transformer interrupting current from impedance, and conduit material and bolted faults in fault-current calcs shows what the downstream run does to the number. Impedance moves the answer directly: the same 1500 kVA unit at 5.0 %Z gives 1804 / 0.0500 = 36,100 A ≈ 36.1 kA.
Decision, on an illustrative switchboard rated 35 kA: a 31.4 kA half-cycle result passes with margin, and if the study result exceeded the nameplate rating the correction belongs in the protection design, not in the datablock. Read that nameplate with the equipment locked out and verified de-energized.
Do I need the asymmetrical current for a low-voltage breaker? #
No — the documented low-voltage check compares the half-cycle symmetrical RMS result with the breaker's short-circuit rating; asymmetrical momentary quantities belong to the above-600 V duty where the 1.6 multiplier lives.
Symmetrical RMS excludes the decaying DC offset; asymmetrical RMS includes it, and its value depends on the bus X/R and the evaluation instant. If your acceptance criterion explicitly demands an asymmetrical RMS or a peak value, take the X/R the study reports for that bus and apply the asymmetry basis of the standard invoked. Never convert by multiplying ANSI 3P int by 1.6 or any guessed factor: that factor belongs to the medium-voltage first-cycle check, and the interrupting result already sits on a later time basis.
When should I take this to the software vendor? #
Escalate when the installed result-variable list does not clearly expose the half-cycle low-voltage quantity: send SKM support the bus fault-current report, the exact duty definition you must satisfy, and the study settings, and ask for the documented variable mapping.
Before that, work through the installed help's result-variable descriptions and the comprehensive report — the quantity is computed; only its display name has to be found. Keep the vendor's mapping answer with the study record so the next reviewer does not re-solve the problem.
Questions asked
Does 0 kA in an ANSI Asym 3P Mom datablock mean the bus really has no fault current?
No. It means the variable is not defined at that voltage level, so the study leaves it blank. A low-voltage secondary behind a typical distribution transformer has tens of kiloamperes of available fault current. Display the half-cycle symmetrical RMS low-voltage result to see it, and keep the Mom fields for medium- and high-voltage buses.
Why does ANSI 3P int populate at low voltage when the Mom fields do not?
The interrupting-duty calculation runs across the network, so its variables report wherever the study computes them. The momentary variables are scoped to buses above 600 V, so they come back empty on a low-voltage bus. A populated interrupting value is a solid path check, but it answers a different question on a later time basis.
Can I multiply ANSI 3P int by 1.6 to get the momentary value?
No. The 1.6 factor belongs to the medium-voltage first-cycle application check, where E divided by the first-cycle impedance times 1.6 is compared with the breaker's momentary rating. The interrupting result is calculated on a later time basis, and the low-voltage check compares the half-cycle symmetrical current directly with the rating. Stacking the two produces a number with no standard behind it.
Do two transformers between the utility and my bus stop SKM from calculating?
No. The solver handles any number of transformations as long as the path is electrically connected, the switching states match the operating configuration, and the utility and transformer data are complete. In the case that prompted this article, the interrupting result populated normally through both transformers; only the displayed variable was wrong.
Which datablock format shows every fault result so I can pick the right variable?
Use the Bus Fault Currents (Comprehensive) format. The software's tutorial recommends it when the load-flow study was not available when the studies ran. Comparing the comprehensive report against your datablock shows exactly which variables return values at the low-voltage bus before you build a custom block.