Explainer
Why SLG fault current exceeds three-phase on a Dyn1 transformer
Short answer
It is normal. On a Dyn1 transformer with a grounded wye secondary, the delta primary keeps the upstream system's zero-sequence impedance out of the ground-fault network while the source impedance still limits the balanced three-phase fault. A worked 1000 kVA, 480 V example shows the ground fault about 3 to 8 percent above the three-phase value.

On this page
A single-line-to-ground fault on the grounded wye secondary of a Dyn1 transformer can legitimately come out higher than the balanced three-phase fault, and the reading is not automatically a software error. The two fault types use different sequence networks: the delta primary blocks the upstream system's zero-sequence impedance from the ground-fault path, while that same upstream impedance still limits the balanced fault. On a 1000 kVA, 480 V Dyn1 bank fed from a 200 MVA source, the worked example below gives about 20,000 A three-phase against 20,600 to 21,600 A ground-fault, depending on the transformer's zero-sequence data.
The two faults see different networks #
For a three-phase fault, only the positive-sequence network is involved, and the current is the phase voltage divided by the positive-sequence impedance between the source and the fault:
I_3ph = E_phase / Z1
For a single-line-to-ground (SLG) fault, the positive-, negative- and zero-sequence networks connect in series, and the current is:
I_SLG = 3 × E_phase / (Z1 + Z2 + Z0)
With Z2 close to Z1, compare the two denominators: the ground fault wins whenever Z1 + Z2 + Z0 < 3 × Z1, which reduces to Z0 < Z1 when Z2 = Z1. Everything therefore turns on what each network actually contains for a delta-wye transformer, and IEC 60909-0, which covers the calculation of short-circuit currents in three-phase systems including line-to-ground faults, builds these networks the same way your study software does. For how the zero-sequence network is handled for other unbalanced fault types under that standard, there is a page on the IEC 60909 treatment of two-phase-to-ground versus SLG zero-sequence current that goes deeper.
What the delta primary does #
The grounded wye secondary supplies ground-fault current through its neutral; a delta winding cannot, because no neutral exists and the zero-sequence current has no return path through it. That is the subject of a separate article on why a grounded wye sources ground fault current and a delta does not. On a Dyn1 unit it has a second consequence: the zero-sequence current circulating inside the delta terminates the zero-sequence network at the transformer. The upstream system's generators, lines and source zero-sequence impedance never appear in Z0 for a secondary ground fault, even though their positive-sequence impedance appears in Z1 and limits the three-phase fault.
So the two fault calculations differ twice over. The three-phase fault sees the source impedance in series with the transformer impedance. The ground fault sees the source impedance in the positive- and negative-sequence branches but only the transformer in the zero-sequence branch. Whenever the source has any impedance at all, Z0 comes out below Z1, and the ground fault comes out above the balanced fault. The same impedance chain, worked through for the interrupting duty at the secondary terminals, is shown step by step in the article on calculating transformer interrupting current from impedance.
The zero-sequence impedance of the transformer itself adds a second effect. Three-limb core-type delta-wye units test with Z0 somewhat below Z1, because zero-sequence flux is forced through the tank and air paths; reference estimates place it near 85 percent of Z1. Shell-type construction and banks built from three single-phase units sit close to 100 percent. The 85 percent figure is an estimate for core-type construction, not a datasheet value: use the manufacturer's test report when you have one. The relationship between the utility's available duty and the value at the secondary terminals is covered in the article on available fault current versus secondary short-circuit current.
A worked example on a 1000 kVA Dyn1 bank #
These inputs are an illustrative example, not ratings of any particular transformer:
- Transformer: 1000 kVA, Dyn1, 13.8 kV delta primary, 480 V grounded-wye secondary, impedance 5.5 percent on its own rating
- Source: utility 200 MVA three-phase duty at 13.8 kV
- Both source and transformer impedance treated as purely reactive, R neglected
Transformer full-load secondary current:
I_FL = 1,000,000 VA / (√3 × 480 V) = 1,000,000 / 831.4 = 1203 A
Transformer impedance referred to the 480 V side:
Z_T = 0.055 × 480² / 1,000,000 = 0.055 × 0.2304 = 0.012672 Ω = 12.67 mΩ
Source impedance at 13.8 kV, referred to the 480 V side through the 28.75:1 ratio:
Z_S = 13,800² / 200,000,000 = 0.9522 Ω; reflected: 0.9522 / 28.75² = 1.15 mΩ
Three-phase fault current at the secondary terminals:
I_3ph = (480 / √3) / (12.67 + 1.15) mΩ = 277.1 V / 0.013824 Ω = 20,043 A, about 20,000 A
Without the source, the transformer alone would give 277.1 / 0.012672 = 21,873 A, so the upstream impedance knocks roughly 8 percent off the balanced fault.
SLG fault, first with Z0 = Z1 = 12.67 mΩ:
I_SLG = 3 × 277.1 / (13.824 + 13.824 + 12.672) mΩ = 831.3 / 0.040320 = 20,618 A
Already above the three-phase value, even with the transformer zero-sequence set equal to its positive-sequence impedance, purely because the delta excludes the 1.15 mΩ source term from the zero-sequence branch. Now with a core-type Z0 of 0.85 × 12.67 = 10.77 mΩ:
I_SLG = 831.3 / (13.824 + 13.824 + 10.771) mΩ = 831.3 / 0.038419 = 21,639 A
That is about 8 percent above the three-phase current. Every result here is an estimate that depends on the assumed duty and impedance data; check it against the manufacturer's test report, the governing code and the equipment documentation.
When the ground fault stays below #
The ordering flips in the other direction when something adds zero-sequence impedance at the secondary. A neutral grounding resistor is the common case: its resistance appears three times in the zero-sequence branch, so a for example 0.05 Ω resistor adds 0.15 Ω to Z0 and pulls the ground-fault current far below the balanced value. An ungrounded or high-impedance wye limits it further still. The condition to check is always the same one from the formulas: compare Z0, as actually seen by the fault, against the positive-sequence impedance that limits the three-phase fault.
Checking the software result #
Before you open any panel or cubicle to read nameplates or confirm connections, de-energize, lock out and verify absence of voltage; NFPA 70E, 2024 edition, governs that sequence, and the local authority having jurisdiction and the equipment documentation govern the details. Then:
- Confirm the transformer is entered as Dyn1 with the wye neutral grounding connection enabled, not floating or entered as delta-delta.
- Check where Z0 came from. If the program derived it from a default ratio, replace it with the manufacturer's test value when one exists.
- Confirm the source impedance appears in the positive- and negative-sequence branches but not in the zero-sequence branch for the secondary fault.
- Recalculate both faults by hand with the same impedance data, as in the example above. Your hand result should reproduce the software's ordering; if it does, the higher SLG current is the physics, not a modeling error.
The decision, for each case: on a solidly grounded Dyn1 secondary with an impedance behind it, accept the higher ground-fault number and use it for the neutral path and ground-fault protection coordination; with a grounding resistor or an ungrounded wye, expect the ground fault below the three-phase value, and treat any ground-fault current near the three-phase value as an input error.
Questions asked
Is a single-line-to-ground fault current above the three-phase value a software error?
Usually not. With the negative-sequence impedance close to the positive-sequence impedance, the ground fault exceeds the three-phase fault whenever the zero-sequence impedance seen by the fault is smaller than the positive-sequence impedance that limits the balanced fault. On a Dyn1 transformer the delta primary removes the upstream zero-sequence impedance from the ground-fault network, so that condition holds whenever the source has any impedance. Verify the winding connection and the transformer zero-sequence input before concluding anything else.
What zero-sequence impedance should I enter for a delta-wye transformer?
The value from the manufacturer's test report when one exists, stated on the transformer's own rating. Three-limb core-type delta-wye units typically test near 85 percent of the positive-sequence impedance because the zero-sequence flux closes through the tank, while shell-type and three single-phase banks sit close to 100 percent. If the study software filled in a default ratio, replace it with transformer-specific data before trusting the ground-fault result.
Does a neutral grounding resistor remove this effect?
It reverses it. A neutral resistor appears three times in the zero-sequence branch of the network, so a for example 0.05 ohm resistor adds 0.15 ohm to the zero-sequence impedance and drives the ground-fault current far below the three-phase value. That is the intent of resistance grounding, and the resistor's short-time current rating and the ground-fault protection pickup should both be coordinated with that reduced current.
Should equipment on the secondary be rated for the higher ground-fault current?
Phase equipment such as switchgear, panelboards and breakers carries a short-circuit current rating based on three-phase duty, and in this example the three-phase current is still the lower-bounded sizing number you would normally quote, so the ordering does not change the rating decision. The ground-fault result matters for the neutral path, the ground-fault protection settings and any equipment in the grounding circuit. Confirm both currents against the equipment documentation and the local authority having jurisdiction.

