Why three single-phase transformers don't add fault currents

Protection: breakers, fuses and SCCR Published 6 min read By Current Intel engineering team

Short answer

No. Three 75 kVA single-phase units wired as a bank behave as one 225 kVA three-phase transformer for fault duty: take the bank's secondary full-load current and divide by its percent impedance. The 15 kA you get by adding three 5 kA figures is not the three-phase value, because the drawing's figure was a single-phase contribution on a different voltage and fault basis.

On this page
  1. What the figure on the drawing actually reports
  2. Add the kVA, not the fault currents
  3. Worked example: three-phase fault duty of a 225 kVA bank at 480 V
  4. What the connection changes, what the source takes away
  5. Put a number on your own bank
  6. Questions asked

No — three 75 kVA single-phase transformers wired into a three-phase bank are one 225 kVA three-phase transformer to a fault calculation. The units add their kVA; their separate fault-current figures never line up at the fault as three parallel sources. A 15 kA answer built from three 5 kA contributions fails on both ends: the bank's three-phase duty comes out well below that, and the drawing's figure turns out to be a single-phase contribution on the faulted winding's own voltage and fault basis, not one share of a three-phase fault. The way through is to calculate the bank as the one transformer it is — bank kVA, secondary line-to-line voltage, percent impedance — which the worked example below does at 480 V.

What the figure on the drawing actually reports #

The confusion in this case had two layers. The drawing listed 5 kA, that number was read as one unit's contribution to a three-phase fault, and a first pass at the bank calculation came out much higher than expected. Both symptoms had one root: a quantity built on one basis was carried onto another. Before any arithmetic, pin the drawing's figure down:

  • Fault type: a single-phase contribution, a phase-to-phase value and a balanced three-phase value are three different currents on three different circuits. These drawings called out the single-phase contribution only.
  • Voltage basis: a single-phase figure rides on the faulted winding's own voltage, not on the bank's line-to-line voltage.
  • Point of measurement: at the transformer secondary terminals, or downstream where conductor impedance has already trimmed the current.
  • Impedance basis: each nameplate percent impedance belongs to that unit's own winding kVA and winding voltage, and it means nothing without them.

A single-phase fault stays on that basis once the bank is built: its magnitude follows the faulted winding, the return path, and the sequence-network connections the winding arrangement creates. The phase-to-phase and three-phase values are separate quantities with their own networks. No one of the three comes from adding the others.

Add the kVA, not the fault currents #

Three 75 kVA units, connected and rated to operate together, make a 225 kVA three-phase bank — the kVA adds because the units share one load. For fault duty the bank behaves as one transformer of that combined rating, and that is the transformer whose impedance belongs in the calculation.

The impedance itself does not change when the bank is built. A nameplate reading 5% on its own winding base still reads 5% when three identical windings form the bank: the kVA triples, the voltage scales with the connection, and the ratio between them stands still. What fails is carrying a single-phase winding's impedance through a three-phase formula on the wrong base — the answer moves, and in the case behind this article it came out high. The page on bank kVA and impedance worked out from single-phase units walks that conversion step by step.

If the three nameplates disagree, take the lowest percent impedance when you need the maximum the bank can deliver: the lowest-impedance winding lets the most current through, and every duty figure should survive that case. Even on matched bases, summing fails on the physics — the three winding currents do not arrive in series at one fault point, so the sum represents no current that exists. The bank's three-phase fault current comes from one calculation on the whole bank.

Worked example: three-phase fault duty of a 225 kVA bank at 480 V #

Inputs, each with its source:

  • Bank rating 225 kVA — three 75 kVA units from the case, added as above.
  • Secondary voltage 480 V line-to-line, three-phase, 60 Hz — an assumed example value, the common North American plant voltage, taken because the case gave none. A different secondary voltage rescales the current and changes nothing about the method.
  • Percent impedance 5% on each unit's own 75 kVA base — a typical dry-type nameplate value, inside the 4% to 10% range such transformers commonly carry; the real number comes off the nameplate.
  • Fault basis: balanced three-phase bolted fault at the secondary terminals, with the upstream source treated as unlimited, which makes the result a transformer-limited ceiling.

The rule, in words: a three-phase transformer's full-load current is its kVA times 1000 divided by 1.732 times the line-to-line volts, and the transformer-limited fault current is that full-load current divided by the percent impedance written as a decimal — the same division that calculating transformer interrupting current from impedance works through.

The arithmetic:

  • Full-load current: I = (225 kVA × 1000) ÷ (1.732 × 480 V) = 225,000 VA ÷ 831.4 V = 270.6 A
  • Transformer-limited fault current: I = 270.6 A ÷ 0.05 = 5412 A

Result: the bank's transformer-limited, three-phase, terminal fault current is about 5.4 kA symmetrical — not 15 kA, and not three of anything. It is a ceiling: a real utility source and the connecting conductors can only pull the available current down from there.

Decision: every device on that secondary needs a short-circuit current rating at least equal to the current available at its terminals. NFPA 70, the National Electrical Code, 2023 edition, sets that expectation for interrupting ratings in 110.9 and calls for the available fault current at service equipment to be field-marked in 110.24 — confirm the obligation with the local authority having jurisdiction and the equipment documentation. Whether the terminal ceiling or the refined value belongs in that check is the question which bolted fault current to use for breaker duty and arc flash settles. The number is an estimate built on the nameplate impedance and the unlimited-source assumption; check it against a current short-circuit study before it lands on a one-line drawing.

What the connection changes, what the source takes away #

That ceiling answers exactly one question: a balanced three-phase fault at the terminals with an unlimited source behind the bank. Two things move the value the downstream equipment actually sees.

The source. A utility service carries its own impedance, and the conductors between the transformer and the board add more; both only reduce the available current. Working source impedance into the low-side fault current turns the terminal ceiling into the value at the board.

The fault type. The three-phase magnitude runs on the positive-sequence network alone and never touches the connection. A ground fault also needs the zero-sequence path, which the winding arrangement and the neutral grounding decide: an ungrounded delta secondary returns almost nothing through the bank, while a bonded wye neutral completes the loop through one winding and its impedance. Motors running on the secondary feed the fault for the first few cycles on top of the transformer's share. The bank calculation supplies one term of the duty check, not the whole check.

Put a number on your own bank #

  1. De-energize the bank, lock out and verify the absence of voltage before opening any termination compartment to read nameplates or trace the connection; NFPA 70E, 2024 edition, covers the safe work practices for that verification, and the local authority having jurisdiction and your site rules govern the details.
  2. Record each unit's kVA, winding voltages and percent impedance from the nameplate or datasheet.
  3. Confirm the connection on both sides and the secondary line-to-line voltage the bank actually delivers.
  4. Add the kVA ratings to get the bank rating.
  5. Divide bank kVA times 1000 by 1.732 times that line-to-line voltage for the secondary full-load current.
  6. Divide the full-load current by the percent impedance as a decimal — the lowest nameplate value if the units differ — for the transformer-limited three-phase ceiling.
  7. Write the result down with its basis: symmetrical, three-phase, at the terminals, transformer-limited.
  8. Refine it with source and conductor impedance for equipment duty and protection settings, and reconcile it with the current short-circuit study, so that every figure on the drawing matches a fault type, a voltage and a measurement point before it is compared with anything.

Questions asked

The three nameplate impedances differ. Which one belongs in the bank calculation?

The bank kVA and the line-to-line voltage stay the same as for identical units. If the spread between nameplates is wide, have the bank modelled from the actual winding data instead of forcing one number to cover it.

Does the single-phase fault current on the drawing change once the units are wired as a bank?

No. A single-phase fault keeps the faulted winding's own voltage, kVA base and impedance, plus whatever return path the connection and grounding provide, which is why the drawing's 5 kA figure never combines with anything: it was never a share of a three-phase fault. Phase-to-phase and three-phase faults are separate quantities that come out of the sequence networks built from the winding connections.

The data sheet gives impedance in ohms instead of percent. How do I convert?

Multiply the winding kVA by 1000 and divide the winding voltage squared by the result; that number is the winding's base impedance in ohms. The ohmic value divided by that base, multiplied by 100, is the percent figure, and it then behaves like a nameplate value. Keep the conversion on the winding's own voltage and kVA: moving one unit's ohms onto the bank's three-phase base without rebuilding the base is the mistake that inflated the original result.

Is the ground-fault current the same as the three-phase figure?

No. The three-phase value runs on the positive-sequence network alone. Size any ground-fault protection from that loop, not from the three-phase duty.

Do motors on the secondary add to the transformer's fault contribution?

Yes. Running motors feed the fault through their own impedance, so the current at a secondary switchboard is the transformer's share plus the spinning machinery's share for the first few cycles. The transformer-limited figure is only one component, which is one more reason the bank rating and its percent impedance alone do not finish the duty check: the load side has to be counted too.

Keep reading

  • How-to

    Closed delta transformer fault current calculation

    Compute each delta branch from its own kVA and impedance, then take phasor differences at the line terminals: for a 150 kVA leg with two 100 kVA legs at 240 V and 3.3% Z each, the bolted three-phase terminal fault is highest at each end of the 150 kVA winding and lower at the junction of the two 100 kVA windings. Size secondary equipment on the higher terminal value.

    Protection: breakers, fuses and SCCR

  • Explainer

    Available fault current vs secondary short-circuit current

    Available fault current and secondary short-circuit current name the same prospective current only when both refer to the same point, fault type and current basis. A supplied value equal to the transformer's full-load current divided by its percent impedance assumes an infinite source: for a 300 kVA, 480 V, 2.0% Z unit that is 361 A / 0.02 = 18,050 A. That number is conservative for equipment duty but not automatically the worst case for arc flash.

    Protection: breakers, fuses and SCCR

  • How-to

    Calculating Transformer Interrupting Current From Impedance

    Use the impedance's own base: 10.2% is stated on the 8,333 kVA self-cooled (OA) rating, so rated current at 5.04 kV is 1,653 A and the transformer-limited secondary fault current is 1,653 ÷ 0.102 ≈ 16.2 kA. That figure sizes a breaker on the secondary bus; a primary breaker's interrupting rating is set by the upstream available fault current, not by the transformer.

    Protection: breakers, fuses and SCCR