Explainer
Why three CT readings don't give three-phase kWh
Short answer
No — three CT readings total a current in amps, and current carries no voltage or phase-angle information, so no arithmetic turns it into kilowatt-hours. Commit to a three-phase power meter that measures the three currents and the voltages: the PLC totalizes its kW with Energy_kWh = Power_kW × Interval_hours, or reads its kWh register, then multiplies by an adjustable rate for cost.

On this page
- Do you add the three CT readings to get total three-phase consumption?
- Why can't amps be converted into kWh?
- What does a three-phase power meter need besides the CTs?
- How does the PLC turn the meter's kW into kWh and cost?
- How far off is a CT-only estimate with an assumed power factor?
- How do you verify the PLC's kWh against the meter?
- Which path do you commit to for each goal?
- Questions asked
You cannot. Three CT readings add up to a current — amps — and amps carry no voltage and no phase-angle information, so no arithmetic, averaging or rate multiplication turns them into kilowatt-hours. The committed answer: keep the CTs for loading diagnostics, add a three-phase power meter that measures the three currents and the voltages, and let the PLC totalize the meter's kW or read its kWh register before applying an adjustable rate. Below: why amps fail, what the meter must be wired to, the accumulation math with a worked 480 V example, how far an assumed power factor misses, and how to verify the total.
Do you add the three CT readings to get total three-phase consumption? #
No. Adding them gives a current total — 300 A in the worked example below — and that number answers only a loading question: how hard the feeder works, phase against phase, with no route to energy or cost.
Keep those three analog inputs and scale them to engineering units: they show imbalance, they trend loading between areas, and they drive overload alarms. CTs alone are the right tool when current itself is the goal, as with measuring three-phase motor current for a PLC alarm input. But an amp total times a rate in currency per kilowatt-hour is dimensionally meaningless — amperes times that rate is not a unit of anything. One related trap is treating the busiest phase as the whole feeder's draw: see whether the highest leg is the total amp draw on a three-phase panel.
Why can't amps be converted into kWh? #
Because active power is volts times amps times the cosine of the angle between them, and a CT reports only the middle term: the same current at power factor 0.85 and at 0.60 is two different powers, two different shift totals, two different bills.
For a balanced sinusoidal three-phase load, P = √3 × V_LL × I_line × PF, with volts times amps giving watts, divided by 1,000 for kilowatts. Energy is power held over time, and one kilowatt-hour is 3.6 megajoules: 1,000 W for 3,600 s. The CT knows nothing of V_LL and nothing of the angle, which the load itself sets — a lightly loaded motor and a heater can draw similar amps while consuming very different active energy, because reactive current flows without doing billable work. That is why an energy meter samples voltage and current together and multiplies them thousands of times per second.
What does a three-phase power meter need besides the CTs? #
Voltage, matched to how the service is wired: a three-wire meter takes the three CT secondaries plus line-to-line voltage connections A-B, B-C and C-A, while a four-wire wye service needs three line-to-neutral voltage leads, so confirm the switchgear configuration first.
Inside, a multichannel analog-to-digital converter samples every voltage and current channel; semiconductor reference designs hold class 0.1 three-phase metering on that architecture, and commercial instruments at class 0.5, 1 or 2 work the same way. The meter then hands the PLC something it can use: live kW over a communications link, an accumulated kWh register, or a pulse output where each pulse means a documented quantity of energy.
One safety note, at the point of wiring: the voltage leads and CT circuits go in with the gear de-energized, locked out and verified absent of voltage — NFPA 70E, 2024 edition, covers that procedure and the protective equipment for it — and the CT secondaries land on shorting-type terminal blocks so no secondary is ever open while primary current flows; confirm the panel-specific requirements with the authority having jurisdiction and the meter's installation manual.
How does the PLC turn the meter's kW into kWh and cost? #
By totalizing: every interval the PLC computes Energy_kWh = Power_kW × Interval_hours, adds it to a running total, then multiplies that total by an adjustable rate — and a meter that sends kWh directly, or pulses, shortens the chain further.
The tag names here are illustrative, not any vendor's: Power_kW is a REAL written from the meter, Interval_hours is a REAL holding the task period in hours, Energy_kWh is a retentive REAL initialized to 0, and Rate_per_kWh is an operator-adjustable REAL. A one-minute periodic task gives Interval_hours = 60 ÷ 3,600 = 0.0167 h.
Worked example, hypothetical inputs: a 480 V, 60 Hz three-phase feeder with a balanced sinusoidal load, CT readings of 100 A, 98 A and 102 A (sum 300 A, average 100 A), meter power factor 0.85. Apparent power: 1.732 × 480 V × 100 A ÷ 1,000 = 83.1 kVA. Active power: 83.1 kVA × 0.85 = 70.7 kW. Energy over an 8 h shift at that loading: 70.7 kW × 8 h = 565 kWh. Energy charge: 565 kWh × Rate_per_kWh. The meter reaches its register without assuming balance or power factor — it multiplies the sampled volts and amps — so the arithmetic above is the paper estimate and the meter's number is the one the PLC totals. A single rate captures only the energy charge; demand charges and power-factor penalties are separate tariff components, so decide up front whether the figure is a consumption number or a bill forecast.
How far off is a CT-only estimate with an assumed power factor? #
By the ratio between assumed and true power factor: hold the amps and voltage fixed and the same feeder delivers 565 kWh over the shift at 0.85 but 399 kWh at 0.60 — a 42 percent miss, which is why nobody commits a budget to assumed power factor.
Run the arithmetic: apparent power is unchanged, so 83.1 kVA × 0.60 = 49.9 kW, and 49.9 kW × 8 h = 399 kWh. The amps never moved, yet the energy moved by 166 kWh. Harmonic distortion widens the drift further, because reactive and distortion current both flow unpriced through an amp reading while a true-power meter accounts for the real power they carry. The committed line: an assumed-power-factor amp total is legitimate as a relative loading index or a demand alarm, and illegitimate as kilowatt-hours, a cost forecast, or anything with a rate attached.
How do you verify the PLC's kWh against the meter? #
Read both totals over the same timed window: the PLC figure should sit within rounding of the meter's kWh register, and each phase's kW should read positive and near its neighbors — four checks catch almost every wiring and scaling mistake.
- Phase association: a swapped CT-to-voltage pairing shows as one phase low or negative; a phase stuck near zero traces to the secondary circuit — see when a CT reads correct volts and the meter reads zero amps.
- Pulse scaling: the PLC count times the documented energy per pulse must equal the register's increment over the same window.
- Integration timebase: hold the load steady for one hour and the total should climb by exactly
Power_kW— the test that proves the totalizer. - Meter class: where the number touches money, use a meter built to IEC 62053-21, 2020 edition, which defines accuracy classes 1 and 2 for active-energy meters — the class number is the permitted error in percent at reference conditions — and treat the utility's meter as the register of record.
Which path do you commit to for each goal? #
Four paths, chosen by what the number is for: CTs alone for loading and alarms, a power meter for live kW, meter-fed totalization for kilowatt-hours and cost, and a class 1 meter wherever the figure carries money.
| Goal | Path you commit to | Why |
|---|---|---|
| Phase loading, imbalance, motor overload alarm | The three CTs into analog inputs | Current answers a loading question directly |
| Live kW on an operator display | Power meter with voltage and current inputs | Only the meter multiplies volts by amps |
| kWh and energy cost | Meter's kWh register, or PLC totalizing meter kW, times Rate_per_kWh |
Amps have no route to energy |
| Anything that carries money | Meter per IEC 62053-21 class 1 or better | The class number is the percent error limit; the utility meter stays the bill |
That is the whole decision: current for loading, metered power for energy, metered energy times a rate for cost.
Questions asked
What does the accuracy class on an energy meter mean?
The class number is the permitted error in percent of the reading at the standard's reference conditions. IEC 62053-21, 2020 edition, defines classes 1 and 2 for active-energy meters, so a class 1 meter may sit 1 percent off at unity power factor and rated current, with the allowed error widening at light load. North American revenue meters follow ANSI C12.20, whose 0.2 and 0.5 classes are tighter.
Can the meter report power factor instead of me assuming it?
Yes. Any meter that computes true power also computes apparent power, and power factor is kW divided by kVA: 70.7 kW on 83.1 kVA is 0.85 in the worked example. Log it over a full shift before reusing a value offline, because induction motors drop well below nameplate power factor when lightly loaded, and mixed process loads drift through the day.
How much energy does one meter pulse represent?
Whatever the meter's documentation states as its pulse constant; it differs by model and programmed rate, so never infer it. Example: a meter documented at 10 watt-hours per pulse delivers 360 kWh over 36,000 pulses, because 36,000 pulses times 10 Wh is 360,000 Wh. Count on a high-speed counter input and compare the running total with the register to prove the scaling.
What does a reversed CT do to the total?
Its phase power arrives with the sign flipped, so the totalizer subtracts it: on a balanced three-phase load the reading falls to one third of the true value. A swapped voltage-current pairing gives a different wrong answer, usually one phase low or negative. Either fault shows up on a phase-by-phase kW display within a minute; correct the polarity at the shorting terminal block, not in software.