Current IntelPower LibraryShop main store

Selection guide

Measuring three-phase motor current for a PLC alarm input

Motors and motor starters Published 7 min read

Short answer

Use a self-powered current-loop transducer with a span at least equal to the motor's maximum current — 100 A here — clamped around one insulated phase conductor and wired to a PLC analog input configured for current. Never land a bare CT secondary on an analog input, never clamp around all three conductors, and treat the alarm as monitoring: the overload relay still does the protecting.

On this page
  1. Choose the signal source before the sensor
  2. Monitoring is not overload protection
  3. One phase or all three, and where the aperture goes
  4. Size the span over the motor's maximum
  5. Wire the loop with the circuit de-energized
  6. Worked example: scaling the transducer on this motor
  7. Set the threshold and the timer
  8. Selection checklist
  9. Questions asked

For a three-phase motor whose largest draw is about 100 A, the instrument for this job is a current transducer: a current-transformer core with a built-in signal conditioner that puts out a loop current proportional to the current in one conductor. Pick a span at least equal to the motor's maximum current, pass one insulated phase conductor through the aperture — never the whole cable, where the three phase fields cancel — and land the loop on a PLC analog input configured for current. A bare current transformer will not do either part: its AC secondary is not a signal a current or voltage input can read, and a secondary left open under load develops hazardous voltage. If a drive already runs this motor, check what it can report before buying hardware.

Choose the signal source before the sensor #

If the motor runs on a variable frequency drive or a soft starter, read that device's documentation first: most can output motor current as an analog signal or over a network, and the value offered, its scaling and its update behavior belong to that specific drive and its parameter set. Treat the drive-reported figure as the monitoring signal only after confirming it meets the alarm requirement.

For a motor started across the line, the choice comes down to three instruments. A current switch is discrete: it closes a contact or solid-state output at one setpoint, which suits proof-of-run and simple overcurrent alerts but gives the program no number to trend or re-threshold. A raw measuring current transformer with its common 5 A AC secondary needs a separate signal conditioner between it and the analog input. The self-powered current-loop transducer combines the core and the conditioner in one body and wires straight into a current-type analog input.

Signal source Output Connects to Best for Watch out
Self-powered current-loop transducer A standard current loop proportional to the current in one conductor PLC analog input set for current Continuous tracking with an adjustable threshold — this application Span must cover the motor's maximum; one conductor only through the aperture
Current transformer plus separate conditioner 5 A AC secondary, conditioned to the loop Conditioner output to the analog input Plants that already standardize on 5 A secondaries Secondary must never be open under load; extra parts and wiring
Current switch Contact or solid-state closure at one setpoint PLC digital input Proof-of-run, one fixed overcurrent alert No measured value, no adjustable threshold
Drive-reported current Analog output or network register Analog input or the drive's network Motors already on a drive Value, scaling and update rate come from the drive's documentation

For continuous monitoring with an operator alarm on this motor, select the self-powered current-loop transducer. Selectable-range versions let you tighten the span once the running current is known, provided the span still covers the maximum draw.

Monitoring is not overload protection #

NFPA 70, the National Electrical Code, 2023 edition, covers motor branch circuits in Article 430, including the requirement for motor overload protection; a transducer feeding a PLC alarm is monitoring and does not satisfy it. Confirm the installation's requirements with the authority having jurisdiction and the motor and starter documentation. Keep the overload relay as the protective device — its auxiliary contact is the direct way to tell the PLC a trip occurred, covered in wiring overload relay contacts to the coil and the PLC. The transducer earns its place by reporting the trend that leads up to a trip, hours before the trip happens.

One phase or all three, and where the aperture goes #

A three-phase motor carries a current in each phase conductor, and the three do not add: what the motor draws is per-phase amperes. For an alarm of the form over x amps for y seconds on an otherwise healthy supply, one phase is the correct and economical measurement — the phases track each other closely, and the overload relay already guards each one.

Measure all three phases only when the alarm must act on imbalance between them, which takes three transducers and comparison logic — the measurement described in diagnosing current imbalance across every motor on a service.

Placement is where this job goes wrong most often. The aperture goes around one insulated phase conductor. Around the full three-conductor cable the magnetic fields of the balanced phases cancel, and the transducer sits at its live zero while the motor runs at full load. Around two conductors the same partial cancellation corrupts the reading. Split the phases at a point where they separate — a starter output terminal or the motor terminal box — and put the sensor on one.

Size the span over the motor's maximum #

The span must reach at least the largest current the motor draws, which is the stated maximum of this motor; anything smaller pins the loop at full scale before the maximum and the reading stops meaning anything. Among the spans that cover the maximum, the smallest one gives the finest resolution around the alarm point.

Starting current runs several times running current for the seconds the motor takes to accelerate, so expect the loop to sit at full scale on every across-the-line start. That is normal for a monitoring channel, and the persistence timer in the logic screens it out. Before committing, check the transducer's short-time overload rating in its datasheet against the duty of repeated starts.

Wire the loop with the circuit de-energized #

Open the starter enclosure or the terminal box and fit the sensor only after the circuit is de-energized, locked out and tested for absence of voltage at the point of work — NFPA 70E, 2024 edition, covers the electrical safe work practices this follows.

With the panel dead, wire the two transducer terminals in series with the loop: the input's current terminal, the transducer, and the loop supply, which many analog modules provide internally and others take from an external 24 V DC supply — the module manual settles it. Configure the channel for current, not voltage, and check polarity against both the module and the transducer diagrams. If a raw current transformer is used instead, its secondary must never sit open while primary current flows: standard practice is to short or load the secondary first, because the open secondary develops hazardous voltage.

Worked example: scaling the transducer on this motor #

Inputs:

  • Motor maximum current: 100 A — the stated largest draw of this motor.
  • Transducer span: a 0-100 A span mapped onto the current loop — the configured example span.
  • Loop current: 12.0 mA — an illustrative reading taken in series at the input terminals with a digital multimeter.

Rule in words: the loop current maps linearly between 4 mA at zero amps and 20 mA at the top of the span.

Arithmetic:

  • Loop span: 20 mA − 4 mA = 16 mA.
  • Scale factor: span ÷ 16 mA = 6.25 A per mA.
  • Reading above the live zero: 12.0 mA − 4 mA = 8.0 mA.
  • Motor current: 8.0 mA × 6.25 A per mA = 50 A.

The motor is drawing 50 A. The decision: 50 A is half of this motor's expected maximum, so the reading is plausible, the loop is healthy and the aperture is on a single conductor — commission the channel. Program the two degenerate readings as faults rather than as zero amps: a dead loop reads no current at all, and a live-zero reading on a loaded motor means the core is seeing no net field, which points at the whole cable through the aperture or a dead channel. If the program works in raw counts, map the module's documented counts at the live zero and at full scale onto zero and the span top, taking the endpoints from the installed module's manual rather than from any other module's.

Set the threshold and the timer #

Set the alarm threshold in amps, above the motor's nameplate full-load current with room for the current rise a supply running above or below nameplate voltage causes; the full-load amps come off the motor nameplate. Set the persistence timer longer than the motor's longest acceleration from a cold start, so the start transient never reaches the alarm — the same long acceleration that drives setting overload relays for high-inertia motor starts sets this timer too. Measure the acceleration once with the transducer commissioned, then set the timer beyond it.

Selection checklist #

  • Span at or above the motor's maximum current, chosen as the smallest covering span.
  • Current-loop output into an analog input channel configured for current, with loop power arranged per the module manual.
  • Aperture fitted on one insulated phase conductor where the phases separate.
  • Datasheet short-time overload rating checked against the starting duty.
  • Threshold above nameplate full-load current; timer beyond the measured acceleration time.
  • Overload protection untouched: the alarm monitors, the overload relay protects.

Questions asked

Does the supply voltage of the motor matter to the transducer?

No. The transducer senses the magnetic field of one conductor, so it does not measure voltage and behaves the same on a 240 V or a 480 V motor. What voltage does affect is insulation: check the sensor's rated voltage in its datasheet and mount it only on insulated conductors, never on bare bus.

Where does the loop get its power?

A two-wire transducer is loop-powered: the same pair carries the supply current and the signal, wired in series with the loop supply and the input's current terminal. Check the analog module manual for a built-in transmitter supply; where there is none, add a 24 V DC supply in series per the wiring diagrams.

What does the loop reading do during a full-voltage start?

Starting current runs several times running current, so the loop sits at full scale for the whole acceleration and the trend shows a flat-topped pulse whose width equals the start time. Read that width once and set the persistence timer beyond it. Repeated starts are also the duty the transducer's short-time overload rating must cover.

How can I verify the loop and the scaling without the PLC program?

Put a digital multimeter in current mode in series with the loop and read milliamps at the input terminals. On the span chosen here, a 12 mA reading is half the motor's maximum: eight milliamps above the 4 mA live zero at 6.25 A per mA. Cross-check against a clamp-on ammeter on the phase conductor to prove the scaling end to end.

Do I need a transducer on every phase?

For a load-level alarm, no: one phase tracks the others on a healthy supply, and the loss of a phase is the overload relay's job, not the monitor's. A one-phase sensor does go blind to trouble on the unmeasured phases, so measure all three only when the alarm must act on imbalance between phases.

Keep reading

  • Troubleshooting

    Motor running over nameplate amps after soft starter bypass

    The motor averages 192.7 A against 164.0 A FLA with only about 0.90% voltage-magnitude unbalance, so the supply is not the proven cause. Treat excess shaft load or excess motor loss first, and confirm negative-sequence voltage with a three-phase power-quality analyzer reading V2/V1, total kW and speed before replacing the starter or the motor.

    Motors and motor starters

  • Troubleshooting

    Diagnosing current imbalance across every motor on a service

    Compute unbalance per NEMA MG-1 as maximum deviation from the three-phase average, not the min-to-max spread: a 13% spread is 6.5% unbalance. Identical A-mid, B-low, C-high readings on ten different motors mean the asymmetry is upstream of the machines, so measure voltage unbalance and negative sequence at the motor terminals and current sharing in the parallel feeder sets, not ten motor circuits.

    Power quality and harmonics

  • Explainer

    Running a three-phase motor on single-phase 208 V

    Yes — a spinning three-phase motor fed across two terminals regenerates the third leg, but winding heating caps it near 30-40% of rated horsepower, so it is a bench trick, not a supply. For real loads, use a rotary phase converter with an idler at least the next size above the largest motor, or a single-phase-input VFD for motors only — never a drive for amplifiers or power supplies.

    Motors and motor starters