Current IntelPower LibraryShop main store

How-to

Wiring overload relay contacts to the coil and the PLC

Motors and motor starters Published 6 min read

Short answer

The overload relay's NC trip contact (95-96) belongs in series with the contactor coil so a trip drops the motor out even while the PLC still commands run; the NO auxiliary (97-98) is a separate status input to the PLC. A PLC input is not overload protection, because no general-purpose controller input is a listed motor overload device, so a panel wired the other way needs rewiring.

On this page
  1. Why the trip contact belongs in the coil circuit
  2. Identify the contacts before you touch anything
  3. Rewire the trip path
  4. Tracing the trip path on a 480 V three-phase starter with a 24 V coil
  5. What each signal tells the PLC
  6. After the trip, reset on purpose
  7. Questions asked

No. Feeding the coil straight from the 24 V supply and using the overload relay only to flag a PLC input is not an acceptable overload path. Put the normally closed trip contact — 95 and 96 on IEC-style relays — in series with the contactor coil, so a trip removes coil current even while the PLC keeps commanding run. Land the normally open auxiliary, 97 and 98, on a PLC input for status. The relay protects; the PLC watches. No general-purpose PLC input, rung or output card is a listed motor overload device, which is the whole reason the hardwired contact goes back in.

Why the trip contact belongs in the coil circuit #

Protection, not preference. NFPA 70, the National Electrical Code (2023 edition), requires running-overload protection for motors in Article 430, Part III, and covers the devices that provide it: an overload relay responding to motor current and opening the circuit it protects. UL 508A, the standard covering industrial control panels, follows the same line — the motor overload function is performed inside the panel by equipment suitable for that function. IEC 60204-1:2016, covering the electrical equipment of machines, treats overload protection the same way: the machine's own switching performs it, and programmable logic does not stand in for it. Confirm the applied requirement with your authority having jurisdiction and the starter and relay documentation.

In the panel you found, a trip does this: the relay operates, a PLC input changes state, and the motor runs until the program acts, the output drops and whatever sits between the output and the coil opens. Every step of that chain is logic and hardware carrying no motor-overload rating, and every step can be edited, forced or fail. The outcome is the pattern in why motors burn up with no overload trips on 480 V: current keeps flowing, the relay sits there tripped, and the winding cooks. Decision: rewire it. This is a missing protection path, not a wiring style.

Identify the contacts before you touch anything #

On IEC-style overload relays, 95-96 marks the normally closed trip contact and 97-98 the normally open auxiliary. Verify both against the diagram on the installed relay, because the marking gives you the function, not the condition. With the relay reset, 95-96 reads closed and 97-98 reads open; a trip swaps them. Read the coil marking too: it alone does not settle AC or DC. Duty matters here — the coil is an inductive load and a PLC input is a small DC load, so each contact's rated switching voltage and current come from the relay's data, not from habit. If the starter's markings are worn or absent, work through it the way you would when identifying unknown terminals on a NEMA size 1 motor starter before moving any wire.

Rewire the trip path #

This work opens a starter panel that normally holds 480 V and control power. Lock out, then test for absence of voltage on the power side and on the 24 V control supply, and account for separately supplied PLC I/O — NFPA 70E (2024 edition) covers the safe-work procedure that applies.

  1. Photograph and mark the existing connections, and plan to update the drawing when you are done.
  2. Break the coil circuit and insert 95-96 in series with the coil — supply side or return side, either one interrupts; keep the existing stop devices and permissives ahead of it so nothing is bypassed.
  3. Land 97-98 on the PLC input, with the input common and polarity matching the input type.
  4. Set the relay's trip-current dial to the motor's nameplate full-load current, and keep all three phases through the relay: these relays sense phase loss, so a bypassed pole blinds them.
  5. With everything still isolated, check continuity through the coil path with the relay reset, then operate the relay's documented trip button and confirm the path opens while 97-98 closes.
  6. Restore power, run the functional test below, and confirm the relay's reset mode is manual, not automatic.

The chain you are building — pilot and protective contacts in series ahead of the coil — is the same logic as wiring a three-phase coolant pump starter from a 120 V signal, with the overload as one more series element.

Tracing the trip path on a 480 V three-phase starter with a 24 V coil #

Inputs, from the panel as built: a 480 V three-phase line; an across-the-line contactor with a 24 V coil, AC or DC per its marking; an overload relay with the 95-96 normally closed trip contact and the 97-98 normally open auxiliary; a control supply at that same voltage; a PLC input fed from the relay contact. Rule in words: the coil sees the control supply minus the drops across whatever is in series with it, a closed contact drops essentially nothing, and an open contact breaks the path.

As built, coil fed straight from the supply:

  • Before a trip: the coil sits at full control voltage.
  • After a trip: nothing in the coil circuit changed, so the coil still sits at full control voltage and the motor keeps running.

Rewired with 95-96 in series:

  • Relay reset, run commanded: the closed 95-96 drops essentially nothing, so the coil holds at full control voltage and the contactor stays in.
  • Relay tripped: 95-96 opens, coil current = 0 A, and the contactor opens the 480 V power circuit. The 97-98 input then sits at control voltage when tripped and at 0 V when reset.

Decision and threshold: with power restored for the functional test under your site's energized-work rules, meter across the coil and operate the relay's trip button. A reading that falls from 24 V to 0 V means the interruption path exists. A coil that still reads 24 V with the relay tripped means it does not — rewire. The 97-98 input should move the opposite way, from 0 V to full control voltage.

What each signal tells the PLC #

Signal What it proves What it does not prove
Overload NO auxiliary (97-98) The relay is tripped Why it tripped, or that 95-96 is in the coil circuit
Contactor auxiliary contact The contactor changed mechanical state The cause of a dropout, or the overload state
PLC run output The program is requesting run Coil voltage, contactor closure, motor current
Tap on the coil side of 95-96 The coil is energized Whether a change is a trip, a stop, an open permissive or a lost supply

Run feedback from a contactor auxiliary is good practice for catching a command with no closure. Trip status comes from 97-98. Neither replaces the trip contact in the coil circuit.

After the trip, reset on purpose #

A tripped overload always has a cause: jammed load, single phasing, worn bearing, a motor too small for the load. Manual reset puts a person at the starter after the trip instead of letting a start command relaunch into the same overload, so if the relay has a reset-mode selector, leave it manual. Latching the 97-98 input so an operator acknowledges the trip adds the same discipline on the screen — status, not protection.

Questions asked

Can the overload contact break either side of the coil circuit?

Yes. Series is what matters, not which conductor. Putting 95-96 in the coil's supply conductor or in its return both interrupt coil current on a trip. Pick the side your drawing and terminal layout make clean, keep the stop devices and permissives in the same chain, and update the drawing so the next person traces it correctly.

Is tapping the coil side of the trip contact instead of using 97-98 acceptable?

It is not a protection problem, but it is poor diagnostics. That tap sits at control voltage whenever the coil is energized, so a trip, a stop command, an open permissive and a dead supply all read the same to the PLC. The 97-98 auxiliary closes only when the relay is actually tripped, which is the information an operator needs.

Would adding PLC logic to drop the run output on a trip fix the panel?

No. The motor's overload protection would then depend on the scan time, the program, the input card, the output and any interposing relay, none of which is rated as motor overload protection, and all of which can be edited, forced or fail. Keep the hardwired 95-96 path as the interruption and treat the input as status only.

Should the overload relay be set to auto reset?

No. Manual reset puts a person at the starter after a trip, and a trip always has a cause to find: a jammed load, single phasing, a worn bearing, an undersized motor. Auto reset can relaunch into the same overload repeatedly and cook the winding between the times anyone looks at the panel.

Does a contactor auxiliary contact on the PLC prove the motor is protected?

No. It proves the contactor mechanism changed state, which is useful for spotting a run command with no closure, but it says nothing about why the starter dropped out or whether the overload is in the coil circuit. Trip status comes from the overload's own auxiliary contact; protection comes from the trip contact in the coil circuit.

Keep reading

  • How-to

    Wiring a three-pole contactor for a single-phase motor

    Run the single-phase current through two poles in series per the overload maker's diagram — supply to terminals 1 and 5, a link between 3 and 6, motor leads at 2 and 4 — and never parallel all three poles. Set the overload at 125% of the 6 A nameplate full-load current (7.5 A) when the service factor is 1.15 or higher or the temperature rise is 40 °C or less, otherwise 115% (6.9 A), per NFPA 70 (NEC) 430.32.

    Motors and motor starters

  • Selection guide

    Selecting overload and jam protection for a reversible motor

    Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.

    Motors and motor starters

  • Troubleshooting

    Why motors burn up with no overload trips on 480 V

    Crystallized insulation several feet back from motor terminals is the signature of high-resistance terminations cooking the leads from I²R heat, while unbalanced voltage adds negative-sequence heating that current-magnitude overload heaters never see. Record all three line-to-line voltages and all three phase currents under load, verify the transformer grounding, and measure insulation resistance on every failed branch before any restart. Welded contacts and ruptured starters are consequences of closing onto failed motors, not a separate mystery.

    Motors and motor starters