Short answer

Yes. With one input phase open, the surviving two lines act as a single-phase bridge: at equal output power each carries √3 ≈ 173% of normal line current while the DC bus falls from 1.35×V_LL to about 0.9×V_LL with two-pulse instead of six-pulse ripple. Whether the diodes actually overstress depends on the load type, so a phase-failure relay tripping the supply breaker is the protection an overcurrent device alone cannot give.

On this page
  1. Will a three-phase rectifier overload after losing one phase?
  2. How much does the line current rise when one phase opens?
  3. What happens to the DC bus voltage and ripple?
  4. Does the current rise actually overheat the diodes?
  5. What protection catches a rectifier phase loss?
  6. How do you check the bridge after a phase burn-off?
  7. The decision
  8. Questions asked

Yes, a three-phase bridge rectifier keeps running after one incoming phase burns off, and at equal output power the two surviving lines each carry √3 ≈ 173% of their normal line current. The DC bus falls from 1.35×V_LL to about 0.9×V_LL, and the ripple changes from six pulses to two pulses per supply cycle. Whether the diodes actually fail from that depends on the load type, and the protection that catches the condition reliably is a phase-failure relay on the input, not an overcurrent trip.

Will a three-phase rectifier overload after losing one phase? #

It keeps operating, because diodes need no rotating field to keep conducting, but the overload question depends on what the DC load does. The two intact legs become a single-phase bridge through their four diodes, the two diodes of the open leg carry nothing, and the surviving diodes conduct half of each supply cycle instead of one third.

The induction motor comparison from the question only half carries over. A single-phased three-phase motor fails on restart because it develops no starting torque; a rectifier simply rectifies whatever voltage the two live lines present, with lower output and heavier ripple. The rectifier shows no dramatic stall, which is exactly why the damage can go unnoticed until the diodes run hot and fail short.

How much does the line current rise when one phase opens? #

The rise is √3 = 1.732, so each surviving line carries about 173% of its normal current, assuming the DC side keeps drawing the same power. The arithmetic comes from comparing equal input power delivered by three lines against two: three-phase line current is P/(√3 × V_LL), single-phase current over one line pair is P/V_LL, and the ratio of the two is √3.

Worked example, illustrative inputs stated in full: a 500 kW DC load on a 3.3 kV line-to-line, three-phase supply, ideal diodes, smooth DC current, no source impedance.

  • Healthy: I = 500 000 W / (√3 × 3300 V) = 500 000 / 5716 = 87.5 A per line.
  • One phase open, same input power: I = 500 000 W / 3300 V = 151.5 A, carried by the two intact lines and returning through each other.
  • Ratio: 151.5 A / 87.5 A = 1.73.

That is an upper bound. The DC bus voltage sags to roughly two-thirds of normal, and if the load does not hold its power, the input power falls with it and the real current ratio drops below 1.73. Establish which way your load moves before deciding the diodes are overstressed.

What happens to the DC bus voltage and ripple? #

The no-load DC output falls from 1.35 × V_LL to about 0.9 × V_LL, which is 0.667 of the healthy value, and the ripple changes from six pulses per supply cycle to two. On the 3.3 kV supply from the example, a healthy no-load bus sits near 4.455 kV; on two lines it sits near 2.97 kV. Those are ideal-bridge numbers (ideal diodes, no source impedance), so read the actual bus with a true DC meter and an oscilloscope and expect the loaded values to sit lower.

The ripple signature is the fastest diagnostic you have. Six humps per 50 Hz or 60 Hz cycle means all three legs conduct; two humps means one phase is gone. No meter or relay on the AC side needs to be interpreted for that check.

Does the current rise actually overheat the diodes? #

It depends on the load type, and that is the one quantity to establish first. Diode conduction loss scales with average forward current, and the conduction pattern changes at the same time as the current:

Load behaviour What the DC side does Effect on the surviving diodes
Constant current (regulated) Current holds, voltage falls Each diode conducts half the cycle instead of one third, average current 1.5× normal — worst case for the stack
Constant power Current rises as voltage falls Line current at or above the 173% figure
Resistive Voltage and current both fall Line current may never exceed rated; an overcurrent device stays silent

With a constant-current load, each of the four conducting diodes runs at roughly 1.5 times its normal dissipation, and junction temperature moves on a time constant of seconds to minutes. That is a genuine thermal overload, and an unprotected bridge can fail minutes after the phase is lost — the failure you describe, where the diodes popped after a phase burned off. A diode that fails shorted then adds a fault path across the supply, so the event escalates from an overload into a short circuit.

Note one thing about the nameplate pair in the original report: 3.3 kV AC input to 3 kV DC output does not match a direct bridge, which would give about 1.35 × 3.3 kV at no load. Either a transformer sits ahead of the bridge or the nameplate values are not simple bridge terminals. Where a transformer is present, its winding connection decides what the secondary shows with a primary phase open, so measure the secondary line voltages rather than calculating them.

What protection catches a rectifier phase loss? #

A phase-failure or unbalance relay on the input, tripping the supply breaker, is the protection that works for every load type, because it acts on the cause rather than on a load-dependent symptom. The alternatives each miss a case:

Approach Detects What it misses
Phase-failure / unbalance relay on the input Loss of a phase regardless of load Nothing, if sensing and trip path are wired correctly
Per-leg fuses with blown-fuse indication Fault current inside a leg A supply-side open phase, which draws no fault current
DC undervoltage or ripple monitor Bus near 0.667 of normal, two-pulse ripple A lightly loaded bridge that deviates too little to trip
Overcurrent or thermal trip only High current or temperature The resistive-load case, where current never exceeds rated; a thermal trip also lags the diode junction

The recommended setup is the input phase-failure relay with DC undervoltage monitoring as a second, independent check. This is the same principle that governs single-phasing protection on other three-phase equipment: current-only devices miss the low-current cases, which is why phase loss detection belongs on the voltage side. The coverage decision for a motor driven through a phase-loss monitor is discussed in why phase loss monitors miss single-phasing on an open delta, and the general point that ACB single-phasing protection needs phase-loss detection rather than overcurrent sensing alone is made in the knowledge-base article on single-phasing protection and phase-loss detection.

How do you check the bridge after a phase burn-off? #

De-energize, lock out, test for absence of voltage, and discharge the DC bus capacitors per your site procedure before opening anything; a bridge DC bus holds lethal charge long after the supply is off. Then work the event in this order:

  1. Find and repair the cause: input fuses, isolator contacts, cable and termination at the burn point. Repair before re-energizing.
  2. Test every diode in the bridge, forward drop and reverse leakage against the datasheet limits, not only the visibly failed ones. The interruption transient at the moment the phase opened can overstress any device, and a series string can share reverse voltage unevenly afterward.
  3. Check the voltage-sharing resistors, equalizing capacitors and snubbers for open or drifted values.
  4. If a transformer feeds the bridge, check it with insulation resistance and winding resistance per phase for signs of the single-phase excursion.
  5. Fit or verify the phase-failure relay and its trip path to the breaker before restoring load.

To confirm balanced three-phase operation afterward: read the three line voltages and currents and confirm all three are present and approximately equal — a zero on one phase or a 1.73× reading on two means you are still on two lines. Scope the DC bus for six pulses per cycle, compare the bus voltage to nameplate, and simulate loss of one phase at the relay's test terminals to prove the breaker trips.

The decision #

If your DC load is constant-current or constant-power, a lost phase is a thermal overload and the bridge fails on a timescale of minutes, which matches the diode failure you saw; protect it with an input phase-failure relay tripping the breaker, plus DC undervoltage as a backstop. If the load is resistive, the diodes may survive indefinitely but the process sees a sagging, badly rippling DC supply, so the same relay is still the right protection. Either way, an overcurrent device alone is not phase-loss protection: test and replace the whole bridge after the event, and verify the relay's trip before re-energizing.

Questions asked

How do I calculate the current rise when one phase of a rectifier is lost?

Use the ratio of single-phase to three-phase input current at the same power: I1φ/I3φ = (P/V_LL)/(P/(√3 × V_LL)) = √3 = 1.732. That result is an upper bound, because the DC bus voltage sags when the phase is lost and a falling output voltage reduces the input power, which pulls the real ratio below 1.732.

How can I tell whether a rectifier is running on only two lines?

Read all three line currents with a clamp: one phase reads zero and the other two read equal and elevated. On an oscilloscope the DC bus shows two ripple humps per supply cycle instead of six, and the DC voltage sits near two-thirds of its normal value. On a 3.3 kV supply that means a reading near 2.2 kV where about 3 kV DC belongs.

Do I need to replace the whole bridge after a phase burns off, or only the failed diodes?

Test every diode, not only the visibly failed ones, because the interruption transient at the moment the phase opened can overstress devices anywhere in the bridge, and a series string can end up sharing reverse voltage unevenly. Check the voltage-sharing resistors, equalizing capacitors and snubbers too, then follow the manufacturer's matching guidance if the stack is a matched series string.

Keep reading

  • Comparison

    True power factor of a single-phase input VFD and how to raise it

    A 240 V single-phase drive with a diode bridge and capacitor front end reads near 0.95 displacement power factor but only about 0.7 true power factor, because its line current comes in narrow peaks. A series reactor in the AC line or DC link is the accepted fix, quoted at 0.9 to 0.95; shunt capacitors are never used. Active PFC or an active front end pays only where a written requirement demands more.

    Power quality and harmonics

  • How-to

    Assessing VFD harmonics when one small drive runs a plant

    No filter is justified on ratings alone: 6 hp × 0.746 kW/hp = 4.48 kW is 6.6% of 68 kW connected capacity. Measure voltage THD at the shared bus with the drive off and then running, and read the drive's input current. If the bus stays under IEEE 519's 5% THD limit with no single harmonic above 3%, leave it alone; if it climbs over, an input reactor on the drive is the fix.

    Power quality and harmonics

  • Explainer

    Zero sequence circuit of a single-phase transformer on a wye system

    A single-phase transformer connected phase A to neutral on a grounded wye system has no zero-sequence network of its own. Its current set gives equal sequence components, each one third of the tap current, which is the signature of a single-line-to-ground connection. Model the tap with the transformer leakage impedance plus the secondary load referred by the turns-ratio squared as Zf, entering the sequence loop as three times Zf.

    Protection: breakers, fuses and SCCR