Zero sequence circuit of a single-phase transformer on a wye system
Short answer
A single-phase transformer connected phase A to neutral on a grounded wye system has no zero-sequence network of its own. Its current set gives equal sequence components, each one third of the tap current, which is the signature of a single-line-to-ground connection. Model the tap with the transformer leakage impedance plus the secondary load referred by the turns-ratio squared as Zf, entering the sequence loop as three times Zf.
On this page
- Equal sequence currents give the connection away
- The impedance that goes in the loop
- A 25 kVA tap on a 12.47 kV grounded wye feeder
- Where the zero-sequence current returns
- Putting the tap into a three-phase study
- Why the three-phase zero-sequence diagram is the wrong tool
- Checks before the model drives a setting
- Questions asked
A single-phase distribution transformer with its primary between phase A and neutral of a grounded wye system has no zero-sequence circuit of its own, and it needs none. Seen from the source it is a connection from one phase to ground, which is the single-line-to-ground connection: the three sequence components of its current come out equal, each one third of the tap current. The impedance that enters the sequence loop is the transformer leakage impedance plus the secondary load referred through the turns ratio squared, and it goes into the loop as three times that value. Build it that way and every check below falls out of the arithmetic; build it as a delta-wye zero-sequence network and the return path is wrong before you solve anything.
Equal sequence currents give the connection away #
The tap draws current only in phase A; phases B and C carry nothing from this load. Run the symmetrical-component transform on that current set and the three components come out identical: I0 = (Ia + Ib + Ic)/3 = Ia/3, with I1 = Ia/3 and I2 = Ia/3.
Equal sequence components are the defining signature of a single-line-to-ground connection — the same relation an A-to-ground fault produces — so the tap couples all three sequence networks and cannot sit in a zero-sequence diagram alone. It is the same bookkeeping as the primary current for a single-phase load on a three-phase transformer, and it carries the same check: with only the tap unbalanced on the feeder, the neutral conductor returns the full tap current to the source, three times I0.
The secondary winding is galvanically isolated from the primary, so no sequence current crosses the transformer as such. The secondary circuit reaches the primary-side model only as the referred impedance of the next section.
The impedance that goes in the loop #
The standard symmetrical-components treatment places a fault impedance from each phase to a common point and a ground impedance from that point to earth, and connects the three sequence networks in series through them for a single-line-to-ground fault. For the tap, the phase-to-common-point impedance is the whole story:
Zf = Zt + Zload × (V1/V2)²
Zt is the leakage impedance, read from the nameplate percent value with its own kVA and voltage rating, and V1/V2 is the turns ratio. The magnetizing branch stays out of a loaded study, because a working tap draws exciting current that is small against its load current, and it matters only when the secondary is open or nearly open. The referral arithmetic, including the traps in turning a nameplate percent impedance into a referred ohmic value, is worked through in the page on nameplate percent impedance versus referred impedance calculations.
A 25 kVA tap on a 12.47 kV grounded wye feeder #
Example inputs. Feeder: 12.47 kV grounded wye, 60 Hz (example study values). Transformer: 25 kVA single-phase, 7200 V primary on phase A and neutral, 240 V secondary, nameplate impedance 2.5 percent (example nameplate). Secondary load: 16 kW resistive at 240 V (example metered load). Source: sequence impedances under 1 percent of Zf at the tap bus (example utility data — a stiff bus).
The rule. A loaded phase-to-neutral tap is a single-line-to-ground connection. Every sequence network carries one third of the tap current, and the loop impedance is Zf, appearing three times.
The arithmetic.
- Base impedance on the primary: 7200² / 25,000 = 2073.6 ohms; the leakage impedance is 0.025 × 2073.6 = 51.8 ohms.
- Load resistance: 240² / 16,000 = 3.6 ohms; the 30:1 turns ratio squared is 900, so the referred load is 3.6 × 900 = 3240 ohms.
- Loop impedance: Zf = 51.8 + 3240 = 3292 ohms, or 3.29 kilohms; the loop value is 3 × 3292 = 9876 ohms.
- Sequence currents: I0 = 7200 / 9876 = 0.73 A.
- Phase A: Ia = 3 × 0.73 = 2.19 A. Direct check: 7200 / 3292 = 2.19 A — the factor of three cancels, as it must.
- Neutral return: 2.19 A back to the source grounding point.
- Secondary side: 30 × Ia = 65.6 A through the load, which sees 65.6 × 3.6 = 236 V. The 4 V shortfall is the leakage drop, Ia × Zt = 113 V on the primary side and 113 / 30 = 3.8 V referred.
Result. 0.73 A in each sequence network, 2.19 A in phase A, and 2.19 A in the neutral return, good to the accuracy of the assumed impedances; confirm the leakage value against the transformer test report and the source values against the utility data before the numbers drive a setting.
Decision. Enter the tap in the study as a phase-A-to-ground impedance of 3.29 kilohms — loop value 9876 ohms — with 0.73 A as the current in each network. Then set Zf to zero: the same loop must return the bolted single-line-to-ground current at the tap bus. If it does not, the interconnection is drawn wrong before the transformer data matters.
Where the zero-sequence current returns #
The loop closes only if the primary neutral has a conductive path back to the source grounding point; a grounded-wye source supplies ground fault current where a delta source does not, as laid out in why a grounded wye sources ground fault current and a delta does not. Trace that path and count each segment: on a multigrounded feeder the return divides between the neutral conductor and earth, and the study's zero-sequence source value already carries the return impedance. If the neutral is grounded through an impedance instead, add three times its ohmic value to the zero-sequence loop, because three times the loop current flows through it. On an ungrounded system there is no phase-to-neutral connection to model at all — no zero-sequence current, no tap; single-phase loads go phase-to-phase and the ground path stays out of the model. The tap itself has no delta winding, so nothing circulates inside it: every ampere of unbalance leaves through the neutral.
Putting the tap into a three-phase study #
The single-phase kVA rating is not a three-phase rating, and entering it as one puts the impedance on the wrong base. Convert the nameplate percent impedance from its own kVA and voltage rating to the study's MVA and voltage base, convert the referred load the same way, and add the two for the loop impedance on a common base. If the software accepts only three-phase transformer models, enter the tap as a phase-A-to-ground shunt impedance of the computed value instead of as a bank.
Two checks close the study out. With the load shorted, the model must return the bolted single-line-to-ground current at the tap bus — the same impedance-referral arithmetic as calculating transformer interrupting current from impedance. With the load set to its rated value, the computed primary current must land on the nameplate full-load figure. Agreement within the accuracy of the impedance data confirms the model end to end.
Why the three-phase zero-sequence diagram is the wrong tool #
Textbook zero-sequence diagrams — grounded wye-wye banks, wye-delta banks with a delta tertiary — describe three-phase equipment: three identical windings, one per phase, their zero-sequence behavior set by winding connections and core construction. The tap has one primary winding. Drawing it into a three-phase zero-sequence network invents windings on phases B and C that do not exist, and it misplaces the return path the neutral actually carries.
Where the three-phase diagrams do apply, construction decides the values: a grounded-wye winding's zero-sequence impedance sits near 0.85 times its positive-sequence value as the usual study estimate, while a three-legged core forces zero-sequence flux into the tank wall and moves the measured figure. On a delta-wye bank, a ground fault on the grounded-wye side drives zero-sequence current that circulates inside the delta and heats the tank, a failure mode covered in grounded phase fault tank heating in a delta-wye transformer. None of that machinery belongs to the single-phase tap: one winding, one phase, one neutral return — the single-line-to-ground connection.
Checks before the model drives a setting #
- Neutral return: with only the tap unbalanced on the feeder, the neutral current equals the phase A current, three times I0.
- Phases B and C: zero in the solved quantities; anything else means the interconnection is drawn wrong.
- Bolted check: with the loop impedance set to zero, the model must reproduce the single-line-to-ground fault value at the tap bus.
- Records first: compare against the transformer test report and the feeder meter records before anyone opens a termination. When a new measurement is unavoidable, de-energize, lock out and verify absence of voltage before touching a conductor; NFPA 70E, the 2024 edition, covers the shock and arc-flash boundaries for the work that remains energized, and your authority having jurisdiction and the equipment documentation settle the local requirements.
- Ground relay sensing: the tap's load current returns through the neutral, so a residual-connected or three-CT ground scheme that does not enclose the neutral reads that load as ground current, and on a multigrounded feeder part of the return can bypass the neutral through earth. That is the sensing behavior behind what a zero sequence CT does in ground fault protection; set the relay above the tap load or enclose the neutral, per the relay documentation.
Questions asked
Why does the loop carry three times Zf instead of Zf once?
In a single-line-to-ground interconnection the three sequence networks are connected in series, and one loop current runs through every element. The fault impedance appears once in each sequence network, so the loop sees three drops of I0 times Zf. The phase current is three times the loop current, which cancels the factor: dividing the phase voltage by three times Zf and multiplying by three gives the same current as dividing the phase voltage by Zf directly.
What changes if the tap connects phase to phase instead of phase to neutral?
Without the neutral connection there is no zero-sequence path, so I0 is zero and the ground loop drops out of the model entirely. The load becomes a phase-to-phase connection: the line-to-line voltage drives the loop, the positive and negative sequence networks carry equal and opposite currents, and the neutral carries no return current from the tap. Referring the load impedance through the turns ratio works exactly as before.
When does the magnetizing branch of the model matter?
Only when the secondary is open or lightly loaded. The exciting current of a working distribution transformer is a few percent of rated current at most, so loaded studies leave the magnetizing branch out and keep the leakage impedance plus the referred load. An open-secondary tap draws nothing but exciting current, so the single-line-to-ground model with a load impedance no longer describes it; read the exciting current from the factory test report instead.
What current does a bolted fault on the tap secondary put on the primary?
Short the referred load to zero and the loop carries only the leakage impedance, 51.8 ohms in the example, giving about 139 A in phase A with the same current returning through the neutral. The system reads it as a single-line-to-ground fault on phase A. Set the tap loop impedance to zero against the bus data and the result must match the bolted single-line-to-ground value there; a mismatch means the interconnection, not the transformer data, is wrong.