Primary current for a single-phase load on a three-phase transformer

Power distribution and transformers Published 8 min read

Short answer

A 30 kVA single-phase load at 230 V draws 130.4 A, computed as 30,000 VA divided by the load voltage. The primary line currents cannot come from a simple turns-ratio scaling of that value: they depend on which windings carry the load, which the connection diagram fixes. A purpose-built conversion connection carries the load with all three phases but needs roughly a 45 kVA bank under the common 2/3 sizing rule.

On this page
  1. The secondary current is one division
  2. What the 500/230 nameplate leaves out
  3. Why the turns ratio gives the wrong primary current
  4. Example: the full load across one winding of a 500 V delta-delta bank
  5. If the bank keeps its three-phase duty
  6. Sizing the supply for a 30 kVA single-phase duty
  7. Overcurrent protection that fits an unbalanced connection
  8. Before the load goes on
  9. Questions asked

A 30 kVA single-phase load at 230 V draws 130.4 A, and that part of the calculation closes with one division. The primary side of a 500/230 V three-phase transformer does not close so neatly: the line currents depend on which windings the load current actually flows through, and on a plain three-phase connection you get two hard-worked lines and one nearly idle one, not three equal currents you can read off the turns ratio. Below is the arithmetic, a worked delta-connected case that puts one winding at three times its rating, the sizing decision for a dedicated single-phase duty of this size, and the overcurrent protection that fits an unbalanced connection.

The secondary current is one division #

The load is quoted in kilovolt-amperes, so apparent power is already given and power factor never enters the current calculation:

I = S ÷ V = 30,000 VA ÷ 230 V = 130.4 A

That current flows in the phase conductor and, for a two-wire phase-and-neutral load, in the neutral as well. If the load runs three hours or more it counts as continuous, and NFPA 70, the National Electrical Code, 2023 edition, sizes the branch conductors and protective device at 125% of the continuous current: that is 163 A, met with the next standard device size of 175 A. Confirm the continuous-load treatment and the standard sizes against the edition your authority having jurisdiction enforces.

What the 500/230 nameplate leaves out #

The order shorthand, 500/230 3F, fixes three facts: the 500 V primary, the 230 V secondary, three-phase construction. It does not say whether the secondary figure is line-to-line or line-to-neutral, whether a neutral is brought out on a rated terminal, or how the windings connect. Those unknowns decide the whole job:

  • A wye secondary at the load voltage line-to-line gives 230 ÷ √3 = 132.8 V line-to-neutral, so there is no phase-to-neutral winding at that level for a phase-and-neutral load to connect to.
  • A delta secondary has no neutral at all unless the manufacturer brought one out. A neutral has to come from a rated winding arrangement, never from a field-made joint between winding ends.
  • The winding arrangement decides how the load current divides among the primary lines, which is the question you asked in the first place.

If the connection diagram shows no documented 230 V phase-and-neutral output, the unit cannot serve this load as ordered, whatever its kVA says. Moving links or opening the winding compartment is de-energized work: lock out and verify absence of voltage before touching anything. NFPA 70E, 2024 edition, governs the safe work practices; confirm the details with your authority having jurisdiction and the site procedures.

Why the turns ratio gives the wrong primary current #

The turns ratio is the primary voltage divided by the load voltage, 2.17 on this nameplate, and it is tempting to divide the secondary current by it and call the result the primary current. That result would be the current in one winding that carries the whole load, which is a winding current, not a line current. Line currents are phasor sums taken where windings meet at the delta or wye nodes, and when one winding carries everything, those sums come out unequal: two lines loaded, the third nearly idle.

Equal currents in all three lines take a connection built for the job. The reconnection schemes borrowed from three-phase generator practice, meaning double-delta, zigzag-derived arrangements, and the Scott or tee connection, share a single-phase load across all three phases, so the line current magnitudes come out close to equal. Equal magnitudes are not equal heating per phase: those currents are phase-displaced, so the kilowatts still split unevenly even when the amperes do not. Keep the names straight, too: the zigzag reconnection used to derive single phase is not the zigzag winding used to make an artificial neutral for grounding.

Example: the full load across one winding of a 500 V delta-delta bank #

Illustrative case with every input stated: load 30 kVA at 230 V, unity power factor, connected across one secondary winding; bank rated 30 kVA three-phase, delta-connected on both sides, 500 V line-to-line primary; magnetizing current neglected.

  1. Current in the loaded secondary winding: 130.4 A, the same division from the first section.
  2. Referred to the 500 V primary winding: 130.4 A × (230 ÷ 500) = 60.0 A. One primary winding now carries the whole load.
  3. Rated balanced primary line current of the bank: 30,000 VA ÷ (√3 × 500 V) = 34.6 A.
  4. Rated current of one delta winding: 34.6 A ÷ √3 = 20.0 A.
  5. The loaded winding runs at 60.0 A ÷ 20.0 A = 3.0 times its rating, continuously, from the moment the load is applied.
  6. The two primary lines feeding that winding each carry 60 A: 60.0 ÷ 34.6 = 1.73 times rated line current. The third line carries nearly nothing.

A wye-connected secondary loaded line-to-line gives the same line picture: two primary lines at about 1.73 times rating, one idle. Impedance and regulation move the figures by a few percent; they do not move the verdict. A standard three-phase bank of this rating cannot serve the full single-phase load, and no overcurrent setting fixes a winding asked to run at three times its continuous rating.

If the bank keeps its three-phase duty #

If this transformer also feeds three-phase loads and stays connected as built, keep the single-phase share at or below about a quarter of the three-phase rating: 25% of the rating is 7.5 kVA. Past that share, one phase carries a disproportionate slice of the apparent power, the phase voltages pull apart at the load terminals, and the loaded leg runs hottest. Treat 25% as a balance guideline from practice rather than a winding limit from a standard; the winding-current arithmetic for the actual connection is what sets a hard limit.

Sizing the supply for a 30 kVA single-phase duty #

Two decisions cover it.

For a dedicated single-phase load, specify a single-phase transformer rated at least 30 kVA, or a three-phase unit the manufacturer documents for single-phase output. The conversion connections that spread the load over three phases cannot deliver the full three-phase kVA as single-phase output; the working budget is two-thirds. To get the full rating out, that means a bank of 45 kVA three-phase at minimum, and the purchase still has to read 30 kVA or more in the manufacturer's stated single-phase rating for that specific connection, not just on the three-phase nameplate.

If the load has to live on a three-phase bus, hold it to the 7.5 kVA share from the section above and put anything larger on its own transformer.

The discipline is always the same: size by the load the transformer will actually carry, not by the nameplate it happens to have. That is the same problem, worked from the other end, in sizing a padmount transformer for a 120/240 V delta load.

Overcurrent protection that fits an unbalanced connection #

NFPA 70, the National Electrical Code, 2023 edition, covers transformer overcurrent protection in Article 450, which caps the protective devices as a percentage of the transformer's rated current. For a transformer under 1,000 V protected on the primary only, Article 450.3(B) allows a primary device at up to 125% of rated primary current and permits the next standard size when 125% does not match a standard device rating. On this bank's balanced rating that arithmetic reads 34.6 A × 1.25 = 43.3 A, satisfied by a 45 A device. With protection on both windings, the primary device may go to 250% and the secondary device to 125% of rated current.

Those percentages key off rated current, and rated current for a converted connection is not the balanced nameplate figure. On the delta case above, the two carrying lines run at 60 A while the third idles, so device ratings, conductor ampacities and trip settings come from the currents the manufacturer's connection data states for that connection. Every line still gets a protective device, including the one that idles at no load, because it still sees faults.

Energizing is its own event: inrush current runs far above rated for several cycles, and the primary device must ride through it. Estimating transformer inrush current for protection coordination walks through that margin. And when the converted output ends up single-phase but is still switched by a three-pole device, sizing a three-pole breaker for a single-phase transformer covers the pole-and-rating traps. Confirm the percentages and the edition that applies with the authority having jurisdiction and the transformer's documentation.

Before the load goes on #

Once the connection is settled, four checks close the job:

  • The connection in place matches the manufacturer's documented single-phase arrangement, and its stated single-phase kVA covers the load.
  • The voltage at the load terminals measures the voltage the load expects, phase to neutral, with the neutral on its rated terminal.
  • With the load applied, each primary line current reads close to the values stated for the connection, and no winding runs above its rating.
  • The primary and secondary protective devices match the ratings calculated from the connection data, and the conductors on every line carry the currents calculated above.

A reading outside those marks is a wiring or rating error, not a tuning problem: de-energize and go back to the diagram.

Questions asked

Are there transformers built to give single phase with a neutral from a three-phase supply?

Yes. A dedicated single-phase transformer is the straightforward answer for a pure single-phase duty. Some three-phase units are wound with a documented single-phase or centre-tapped secondary, and generator-style reconnections, including double-delta, zigzag-derived schemes, and Scott or tee connections, derive single-phase output from all three phases. Each carries a connection diagram and a derated kVA from its manufacturer. An improvised rewiring of a standard three-phase unit is outside its nameplate rating and is not a documented connection.

What does the idle third line do while the other two carry the load?

It carries only the transformer's magnetizing current, because none of the load current flows through the windings that feed it. The two working lines carry equal magnitudes displaced 180 degrees, so the supply sees what amounts to a two-wire circuit spread over three conductors. Any three-phase motor sharing the same secondary then sees a voltage unbalance that heats its rotor, so check that unbalance before accepting a large permanent single-phase load on a shared bus.

How does the load's power factor change these currents?

It does not change these numbers, because the load is stated in kilovolt-amperes, which already includes power factor. If a load were quoted in kilowatts, convert before calculating: 24 kW at a power factor of 0.8 is 24 ÷ 0.8 = 30 kVA. Lower power factor means more current for the same kilowatts in every winding and line, and transformer sizing follows apparent power, not kilowatts.

How much current does the neutral carry for this load?

For a two-wire phase-and-neutral load the neutral carries the same current as the phase conductor, so size the neutral and its terminations for full load current rather than for a three-phase unbalance remainder. On conversion connections that share the load across all three phases, the neutral current depends on the scheme, so read the rating of the neutral terminal in the manufacturer's connection diagram before sizing that conductor.

Keep reading

  • Selection guide

    Sizing a padmount transformer for a 120/240 V delta load

    Select the 300 kVA four-wire delta padmount and reject the 225 kVA unit: the center-tapped winding runs at 129% of its rating during the start on the smaller unit and 97% on the larger one. The choice holds only with a written tapped-section rating covering the start and continuous loading calculated here; otherwise use a single-phase bank or a 208Y/120 V wye secondary.

    Power distribution and transformers

  • Selection guide

    Sizing a three-pole breaker for a single-phase transformer

    Use the real primary current, 10 kVA x 1000 / 480 V = 20.83 A, not the 36.1 A a phantom balanced 30 kVA three-phase load gives. NFPA 70, 2023 edition, Table 450.3(B) permits 125% plus the next standard rating, so a 30 A two-pole breaker is the pick. A three-pole breaker of the same rating works only where its listing allows two-pole use, or with two poles in series on a differential-trip device.

    Protection: breakers, fuses and SCCR

  • How-to

    Powering a 600 V three-phase machine from 240 V single phase

    The nameplate works out to 20.8 kVA of apparent power. Fed from the single-phase shop service, that is about 87 A before converter and transformer losses, so the machine needs a rotary phase converter sized to its total demand plus a reverse-connected step-down transformer, unless tracing shows the internals run on 200 to 220 V. Verify loaded voltage balance before releasing the machine to production.