Current IntelPower LibraryShop main store

How-to

3RW55 soft starter control wiring and overload setup

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

Assign each control input and output function in the 3RW55 local menu, enter the motor nameplate full-load current so the electronic overload trips at 150% of it on its thermal characteristic, and connect the motor's PTC leads to the thermistor input, not as a dry contact. A 40 A motor trips at 60 A.

On this page
  1. Which control inputs do you assign, and to what function?
  2. How do you set the outputs for run, fault and full voltage?
  3. How does the 150% overload trip actually get set?
  4. How much trip time does 150% current actually give?
  5. How do you wire the motor PTC thermistor?
  6. What sequence do you follow to configure and save everything?
  7. What do you check when an input acts but the motor doesn't start?
  8. Questions asked

On a SIRIUS 3RW55 soft starter you set every control-terminal function in the local menu against the terminal diagram in the equipment manual, enter the motor nameplate current for overload protection, and wire the motor's PTC leads to the documented thermistor input. Nothing here needs external relays. This article covers the full input and output assignment plus the overload and thermistor configuration from the keypad; for the rotary FLC and trip-class dials, see the dedicated article on soft starter rotary switch settings for FLC and trip class.

Which control inputs do you assign, and to what function? #

Assign each digital input its function in the parameter menu, not by terminal position alone: a stop input that closes to command stop, two start inputs that both command the same direction, and a fault-reset input. The starter evaluates each input against the function you assign it, so the physical terminal and the function are two separate decisions.

Map the four inputs like this:

  • IN1: contact closure commands stop. Check the documented command polarity; with a closed-contact stop, an open wire looks like no stop request, so verify the behavior with the control circuit energized and the power section isolated.
  • IN2: commands a start in the installed direction.
  • IN3: the same start function as IN2. Two inputs commanding the same direction do not make a reversing starter; direction comes from the power-circuit phase arrangement. If the menu does not accept the same function on two inputs, combine the two requests through external control logic while keeping stop priority over both.
  • IN4: fault reset. Confirm in the manual how reset behaves when a start command is still present, so the machine does not restart on reset.

Give the stop request priority over any start request and define what happens if IN2 and IN3 ever close together, even though you intend them never to. Keep any safety-related stopping function on its own hardwired path, outside these programmable assignments.

How do you set the outputs for run, fault and full voltage? #

Assign the relay outputs by function in the menu: running status, group fault, and ramp-complete or full-voltage indication, leaving the fourth output unassigned with its wiring isolated and documented. The equipment manual notes the group error output on terminals 95 and 96 as the usual way to link a fault indication into the control circuit; confirm the contact type and its electrical limits in the terminal diagram before loading it.

A status output reports an internal starter condition. The full-voltage output closes after the acceleration ramp completes and the unit is at full voltage or in bypass, which is not the same event as the run indication, so pick the function whose meaning matches what your PLC or pilot lamp needs. If you log or display starter status at the machine, an industrial panel PC at the starter line-up is one way to bring those signals to an operator station.

How does the 150% overload trip actually get set? #

Enter the motor's rated operational current from the nameplate and let the electronic motor overload trip on its own characteristic; the trip demand of 50% above rated current is satisfied by the thermal model, not by any current-threshold setting. The manual documents the motor parameters the starter uses, including the rated operational current Ie and the service factor, and states that the electronic motor overload calculates the approximate motor temperature from the measured motor currents and that motor data.

So do not raise a setting dial to 150% and call it done: that changes the reference the thermal model uses, not the trip point. Setting overload from nameplate full-load current works the same here as on a thermal overload relay, which the article on setting overload relays from motor nameplate full-load current walks through.

How much trip time does 150% current actually give? #

There is no single time: the thermal model trips when its calculated temperature reaches the limit, so the time at 150% depends on the trip class and the thermal state the motor already carries. Worked example, clearly illustrative: a motor with a nameplate rated operational current of 40 A at its installed voltage and connection gives 1.50 × 40 A = 60 A as the trip demand current. With the overload set to Class 10, the class definition means the model must trip within 10 s from a cold, balanced three-phase condition at 7.2 times the setting current, so at 60 A, only 1.5 times the 40 A setting, the trip takes far longer than 10 s and depends on the preceding load. Read the trip class and its curve the way the article on reading overload relay trip classes and curves describes, and verify the actual time against the starter documentation for your model and firmware. If a process truly needs an instantaneous trip at a fixed current, that is a separate current-monitoring function, not this overload.

How do you wire the motor PTC thermistor? #

Connect the motor's raw PTC sensor leads directly to the starter's documented thermistor motor protection input and select the thermistor evaluation function; do not treat the sensor as a dry contact. A PTC is a temperature-sensitive resistance, so it needs the starter's evaluation circuit, not a digital-input contact scan.

Only if an external thermistor evaluation relay already converts the sensor to a contact do you wire that contact to a digital input instead. The manual also notes conditions for using the 3RW55 with thermistor motor protection in Class I and Class II hazardous locations; if the motor is in a classified area, follow that section exactly. After wiring, prove the sensing loop: open the PTC circuit at the starter terminals and confirm the starter reports the sensor fault, then restore it.

What sequence do you follow to configure and save everything? #

De-energize and verify absence of voltage at the power and control terminals before opening the starter, then configure and wire in this order:

  1. Record the starter order number and installed options, and pull the matching terminal diagram and parameter descriptions from the equipment manual.
  2. Record the motor nameplate: rated voltage, rated operational current, connection, service factor, and the temperature-sensor type.
  3. Enter the motor parameters, including the rated operational current Ie, in the menu.
  4. Assign the input functions: stop, the two start inputs, and fault reset, with the command mode each one needs (a maintained command stays asserted; a momentary command needs run hold-in in external logic).
  5. Assign the output functions: running, group fault, and ramp-complete or full voltage; leave the unused output isolated.
  6. Select the trip class and thermal overload settings for the motor and its duty.
  7. Select the thermistor motor protection function for the connected PTC.
  8. Set the starting mode and, if you need more than one load profile, use the starter's three parameter sets; note that automatic parameterization always sets the starting mode to soft starting with voltage ramp and current limiting, so set the mode explicitly where it matters. The menu path for the ramp runs as Parameters, then Soft Starter, then the parameter set, then Start settings, then Starting mode.
  9. Wire to the documented common and supply arrangement, save the configuration with the documented keypad procedure, and record the final assignments.

What do you check when an input acts but the motor doesn't start? #

Watch input state, command state and output state separately on the display: an input that changes on screen but produces no motor response is a command-authority or function-assignment problem, while a motor that runs without its output closing is a wrong output function. If a fault indication appears, read the displayed fault and the manual's fault table before changing any setting, and reset only after the cause is known. For the case where the motor then runs above nameplate current after bypass, the separate article on a motor running over nameplate amps after soft starter bypass covers that fault path.

Questions asked

Does setting the overload to 150% make the starter trip instantly at that current?

No. The electronic motor overload works like a thermal replica: it estimates winding temperature from measured current and elapsed time against the motor data you entered. At 150% of the rated operational current it trips after a heating time taken from the selected trip class and the motor's existing thermal state, never instantly.

Can I use two separate inputs for the same start command on a 3RW55?

Check the input function list in the equipment manual for your firmware before assigning the same start function to two digital inputs. If the menu does not accept a duplicate, combine the two requests with external control relay logic, keep the stop command priority over both, and prevent backfeeding between the two signal sources.

What happens if the PTC circuit breaks or shorts?

The thermistor evaluation in the starter reports sensor faults separately from an overtemperature trip. After wiring, operate each condition deliberately: open the sensor loop and then short it at the starter terminals with power to the control circuit only, and confirm the starter displays the matching sensor-fault indication each time before releasing the machine.

Keep reading

  • Troubleshooting

    Diagnosing a soft starter fault or alarm before resetting it

    Record the exact fault or alarm text, the values shown with it, and whether it appeared during start, run, or stop, before you reset, because a reset clears the diagnostic context. Then check the supply, the starter's documented ratings, the configured motor data, and the load: most trips trace to one of those four, not to a failed starter.

    Motors and motor starters

  • Explainer

    Why a single-phase soft starter can't fix a heavy fan start

    No setting rescues this start: the single-phase ATS01-type soft starter ramps voltage over a documented 1 to 5 seconds, and at fixed frequency 60% voltage leaves only 36% torque, so a heavy fan sits near stall at near-locked-rotor current until the overload or the supply fuse operates. The fix is a three-phase motor on a VFD sized for the single-phase supply, with acceleration set to 20 to 30 seconds.

    Motors and motor starters

  • Troubleshooting

    Why a soft starter trips after about 10 minutes of running

    Check the motor-current setting against the nameplate first: in the reported case a 251 A setting sat 32% above the motor's 190 A rating, so the overload model under-protected the motor. Then record the LED pattern before power-cycling, measure the running current per phase, compare cool and warm trip times, and keep the enclosure within the starter's documented temperature limit.

    Motors and motor starters