Troubleshooting
Why a soft starter trips after about 10 minutes of running
Short answer
Check the motor-current setting against the nameplate first: in the reported case a 251 A setting sat 32% above the motor's 190 A rating, so the overload model under-protected the motor. Then record the LED pattern before power-cycling, measure the running current per phase, compare cool and warm trip times, and keep the enclosure within the starter's documented temperature limit.

On this page
- Record the indication before the next power cycle
- Set the motor-current reference from the nameplate, not above it
- Measure the running current on all three phases
- Compare a cool start with a warm restart
- Check the air temperature against the starter's documented limits
- Read the starting settings as an across-the-line start
- Why the spare-starter swap proves less than it seems
- The decision path
- Questions asked
A soft starter that runs and then stops with its device and failure LEDs lit after about ten minutes is usually reporting heat, not a failed power section. Before swapping the unit again, put two numbers side by side: the running current against the motor's nameplate rated current, and the air temperature beside the starter against its documented limit. In the reported case the motor-current setting sat 32% above the motor's nameplate rating, which loosens the motor-overload model while leaving every hardware rating unchanged. The long-run shaft also works about 88% of each cycle in an uncooled panel; the shaft the spare starter passed on works about 9%. Both point one way: accumulated heat with under-set protection. De-energize, lock out and verify absence of voltage before any panel-side check; NFPA 70E, 2024 edition, covers the energized work none of these steps need — confirm the rules with your authority having jurisdiction and the equipment documentation.
Record the indication before the next power cycle #
The red device and failure LEDs say that the unit tripped; they do not say which protection operated. Photograph or write down every lit LED, its label and whether it is steady or flashing, and read the pattern against the operating instructions for the exact ordering number, the same first step as diagnosing a soft starter fault or alarm before resetting it. Main-power cycling wipes the displayed indication and lets the machine run again with the cause untouched, so each cycle spent re-arming the crusher is a lost data point.
Then note the time from start command to trip. About ten minutes of running, repeatable after every restart, is a signature worth keeping. The long forward segment on this shaft is 600 s, so a trip landing near the end of that segment — or right at the command into reverse — points at duty and transition timing rather than a random hardware fault. If the pattern identifies a protection function, follow that branch below; if it does not, keep the complete pattern for the manufacturer's support channel.
Set the motor-current reference from the nameplate, not above it #
The reported motor is 110 kW, 400 V, 60 Hz, with 190 A on the nameplate; the reported motor-current setting is 251 A. The margin between them is not a rounding artifact:
(251 − 190) / 190 × 100 = 32.1%
A soft starter's motor-overload model estimates winding heating from current and time relative to that reference. With the motor at rated load, the model's input is 190/251 = 0.76 of the reference, and because these models scale heating with current squared, they register (190/251)² ≈ 0.57 — about 57% of thermal capacity while the motor sits at 100% of its rating. The winding-protection trip that should come never does; what comes instead, ten minutes into the run, is the starter's own thermal state complaining about the same duty.
Sanity-check the nameplate before accepting it. Apparent input at rated conditions is √3 × 400 V × the rated current = 131.6 kVA, and 110 kW of shaft output against that implies a power-factor-times-efficiency product near 0.84 — a normal induction-motor figure, so the rated current stands. The connection matters too: rated current only holds for the connection the nameplate shows, and the page on what a star marking on a 380 V motor nameplate means shows how to read one before trusting any current figure.
Decision: set the motor current to the nameplate rated current, the same rule that puts a VFD's motor overload current setting at the nameplate FLA. The class reported as CLASS=10 only selects the overload curve; with the trip arriving mid-run rather than during acceleration, the curve is not the prime suspect — the inflated reference is. Trip class earns real attention on high-inertia starts, which a crusher drive can be, and setting overload relays for high-inertia motor starts covers that case.
Measure the running current on all three phases #
Put a recording true-RMS clamp on each phase and log through a complete long run; snapshots mislead on a crushing duty because the load swings with the material. Read the log against three branches:
- Running current above the nameplate value: the overload is real. An overfed crusher, worn bearings, a dragging seal or a low supply voltage all show up here, and the inflated reference was hiding them. Fix the loading and the mechanics — the protection was doing its job.
- Running current at the nameplate value with the trip still coming: the motor is not the overheated party, the starter's power section is. Move to the temperature checks below.
- A marked imbalance between phases: chase terminals, load-side connections and the supply before anything else, because imbalance heats the high phase even when the average looks acceptable.
Whichever branch the log shows, do not restore the old reference. Raising the setting does not increase what the power section can carry; it only moves the trip further from the truth.
Compare a cool start with a warm restart #
After a full cooldown, power up and record the time to trip; then restart immediately after the next trip and record again. Warm restarts tripping sooner than cool ones confirm thermal accumulation in the motor, the power section or the panel. This is documented soft-starter behavior: manufacturer documentation for solid-state soft starters describes the motor's thermal state being held in memory across a stop, with the motor-thermal protection holding the start off until that model cools — the same mechanism behind why a thermal overload trips again right after a reset. It explains the reported pattern exactly: the main switch resets the indication, but the motor, the power section and the panel are still hot, so the unit dies near the ten-minute mark again.
Check the air temperature against the starter's documented limits #
The manufacturer's manual for the SIRIUS 3RW30 and 3RW40 soft starters sets 60 °C as the maximum permissible ambient temperature for the unit, and it tabulates current ratings at specified ambient temperatures, with permitted current falling as ambient rises. Measure the air beside the starter through a full duty cycle and expect the peak at the end of the long forward run, not at start. There is no air conditioning in this panel, and a shaft that runs 88% of the time at crusher current is a heater: self-heating, closed doors and ambient heat stack quickly.
Keep the mounting clearances and ventilation the manual calls for, separate the starter from other heat sources, and if the logged air temperature approaches the values in the rating tables, use the manufacturer's documented decision path for an operating overload: check the set motor current, select a lower class, or recalculate the size allowance and fit a larger starter. Better cooling or a bigger unit is the fix; a higher setting never is.
Read the starting settings as an across-the-line start #
The reported settings — starting voltage 100%, ramp time 0 s, ramp-down 0 s — are not a soft start. Full line voltage reaches the motor from the first instant, the current-limiting function has nothing to do, and the reported starting current of 1277 A, about 6.7 times the rated current, is a plain across-the-line magnitude delivered through the power section. The configuration is legitimate if the load tolerates line starting, but call it what it is: every start is a full-voltage start, repeated all shift on crusher duty.
If gentle acceleration is actually the point, set a real initial voltage and ramp and verify the start with the recording clamp; setting a soft starter current limit without overheating the motor covers the balance between limit, ramp and motor heating. The value shown as xle=4 stays out of every calculation until the operating instructions for the exact ordering number define it — a setting label guessed from its shape is how panels get mistuned.
Why the spare-starter swap proves less than it seems #
The tripped unit ran fine on a 160 kW test panel in a cooler room — on the other shaft. That shaft runs 4 s forward and stops for 40 s, about a 9% duty; the problem shaft runs 605 s of every 685 s cycle, about 88%. A soft starter's suitability depends on running current, start duration and the cooling interval between starts, and the swap changed all three at once: different motor, different duty, different enclosure temperature.
So the swap is a useful comparison and a useless component test. It does say something precise: the unit survives light duty and a cool room, which steers suspicion away from a latent hardware fault and toward the duty and heat on the long-run shaft.
The decision path #
- Record every lit LED and the start-to-trip time, and read the pattern in the operating instructions for the exact ordering number before cycling main power.
- Set the motor current to the nameplate rated current — the reported case runs it 32% high.
- Log per-phase current through a full long run: above the nameplate value, fix the load; balanced at the nameplate value with trips persisting, treat it as starter and panel heat; unbalanced, chase connections and supply first.
- Log the air temperature beside the starter through a full cycle and keep it inside the manual's ambient tables — 60 °C is the documented ceiling for this series. Cool the panel or recalculate the size allowance and fit the larger size; never raise the settings to buy time.
- Compare cool and warm trip times; warm-restart trips coming sooner confirm thermal accumulation rather than a random fault.
- Read 100% voltage with a 0 s ramp as an across-the-line start, and set a real ramp if soft starting is the goal.
- Treat the cooler-panel pass as evidence about duty cycle, not about the starter.
Questions asked
Does setting the motor current above the nameplate give the starter more headroom?
No. The value only moves the reference of the motor-overload model; the power section's current capacity is fixed by the hardware. With the reported 251 A reference on a 190 A motor, the model reads about 57% thermal load at full-load running, so it under-protects the motor and says nothing about the starter's own temperature. Set the reference to the nameplate rated current.
Why did the swapped starter run fine on the other machine?
The other machine runs the light shaft: 4 s forward and 40 s stopped, about 9% duty, in a cooler room. The problem shaft runs 605 s of every 685 s cycle, about 88% duty, in an uncooled panel. Duty, running current and enclosure temperature all changed with the swap, so the test never reproduced the conditions that trip the original application.
How hot can the panel around a soft starter get?
For the SIRIUS 3RW30 and 3RW40 series, the manual sets 60 °C as the maximum permissible ambient temperature, and the current ratings are tabulated at specified ambient temperatures, falling as ambient rises. Measure the air beside the unit through a full duty cycle, keep it within the table for the exact ordering number, and treat readings creeping toward the limit as a cooling problem to fix, not a setting to raise.
Is 100% starting voltage with a 0 s ramp a valid soft-start setting?
It is a permitted configuration but not a soft start: full line voltage reaches the motor from the first instant, so the reported 1277 A, about 6.7 times the rated current, is an across-the-line start with none of the current limiting a soft starter exists to provide. If the load needs gentle acceleration, set a real initial voltage and ramp; if it does not, the starter is effectively a line contactor with extra electronics in the path.
Should the trip class be raised to buy more running time?
No. Raising the class or the current reference only delays or suppresses the trip while the heat stays in the motor and the power section. The manufacturer's support documentation for this series offers three legitimate responses when the overload operates: check the set motor current, select a lower class, or recalculate the size allowance and fit a larger starter. Measured current and panel temperature decide which one applies.