Explainer
5% voltage drop on single-phase fittings on a three-phase supply
Short answer
Take the 5% on the phase-to-neutral voltage at the fitting's terminals: a floor of 218.5 V at the last fitting. The line-to-line figure is the same 5% expressed between phases, not extra margin to spend on a single-phase fitting.
On this page
- Is the 5% voltage drop taken line-to-neutral or line-to-line?
- Why are the two figures the same 5%?
- Where does the √3 in the voltage-drop formulas come from?
- What happens if you spend the line-to-line figure on a single-phase fitting?
- Doesn't alternating phases cancel the neutral drop?
- What does the section-by-section calculation give on a real run?
- Which standard sets the limit?
- How do I confirm the calculated drop with measurements?
- Questions asked
Take the 5% on the phase-to-neutral voltage the fitting actually receives: 0.05 × 230 V = 11.5 V, which puts the floor at 218.5 V at the last fitting's terminals. The familiar 20-volt figure is real but line-to-line — it is 5% of the 400 V between phases. Divided by 1.732 it becomes 11.55 V line-to-neutral, the same 5% again, because that line-to-line voltage corresponds to 230.9 V phase-to-neutral on a balanced system. Subtract the line-to-line figure straight from the fitting's phase voltage and you have allowed an 8.7% drop without noticing. The feeder is three-phase; every load on it is single-phase, and the voltage that decides compliance is the one across each fitting's phase and neutral terminals.
Is the 5% voltage drop taken line-to-neutral or line-to-line? #
On the line-to-neutral voltage, as above: the last fitting must see at least 218.5 V between its own phase and neutral terminals under the assessed load.
A voltage-drop limit protects the load, so its percentage belongs to the voltage the load is connected across. Your fittings are line-to-neutral devices; the line-to-line voltage never appears across their terminals. A line-to-line basis belongs to equipment connected across two phases — a three-phase motor, or a heating element spanning two phases. Sharing a three-phase feeder changes how the drops of many fittings share the cable; it does not change which voltage the percentage is taken on.
Why are the two figures the same 5%? #
Because the line-to-line limit is the same percentage in disguise: divided by 1.732 it becomes 11.55 V line-to-neutral, 5% of the 230.9 V phase voltage that the nominal line-to-line figure delivers on a balanced system.
On a balanced system, line-to-line voltage is √3 times line-to-neutral voltage — a vector difference between phases 120° apart, not two phase voltages added. Check it: the nominal line-to-line voltage ÷ 1.732 = 230.9 V. The same factor converts a balanced set of drops, so a line-to-line drop of the tabulated size with equal per-phase drops appears at each single-phase load as 11.55 V. If you want the full derivation of how a line-to-line voltage is derived from line-to-neutral values, it is this same vector arithmetic at work.
| Reference | Arithmetic | 5% limit |
|---|---|---|
| Line-to-neutral at the fitting | 5% of the phase voltage | 11.5 V |
| Line-to-line, a balanced three-phase load | 5% of the line-to-line voltage | 20 V |
| That line-to-line figure expressed per fitting | ÷ 1.732 | 11.55 V |
| That line-to-line figure applied straight to the fitting | as a percentage | 8.7% — the error |
The 0.05 V between the two per-fitting figures is the rounding built into the 230/400 nominal pair, not extra allowance, and 380 V is simply what the bus reads after a line-to-line drop of that size; it is not the voltage at any phase-to-neutral fitting.
Where does the √3 in the voltage-drop formulas come from? #
It converts between the two references: the balanced three-phase formula √3 × I × L × R produces a line-to-line figure, so divide that result by 1.73 — or work each fitting as a single-phase loop — when the load is line-to-neutral.
- Single-phase, two wires: VD = 2 × I × L × R. The 2 counts the phase conductor and the neutral conductor, in series.
- Balanced three-phase load: VD = √3 × I × L × R. No neutral current flows, and the √3 is the same vector factor applied to the drop.
- Your circuit, single-phase loads on a shared three-phase feeder: each fitting is single-phase arithmetic — its own phase conductor out, neutral back — and each neutral segment carries the vector sum of every fitting downstream on all three phases.
Where reactance matters (large conductors, widely spaced runs, poor load power factor), replace R per metre with R × cos φ + X × sin φ, the basis of the mV/A/m cable tables used with the IEC 60364-5-52 Annex G calculation method.
What happens if you spend the line-to-line figure on a single-phase fitting? #
You allow an 8.7% drop: the fitting then sits at 210 V, which is 8.5 V below the floor and 1.7 times the permitted drop.
The line-to-line number is the correct magnitude for a line-to-line measurement on this supply, which is why it sounds plausible; it simply cannot be compared against a phase-voltage limit without dividing by 1.732 first. Keep two constraints separate while you decide: the installation rule sets the drop permitted from the origin of the circuit to the equipment, and the fitting's own input-voltage range comes from its manufacturer documentation — a nominal nameplate by itself declares no tolerance. Fittings that still light up satisfy neither number.
Doesn't alternating phases cancel the neutral drop? #
Only where the downstream fitting counts are equal: rotation balances the origin exactly, but the tail sections of the run are unbalanced, and their residual neutral current adds real volts at the farthest fittings.
Each cable section carries only the fittings downstream of it, per phase. A circuit that starts L1, L2, L3 and repeats is perfectly balanced at the origin, yet every section between one phase's fitting and the next carries counts that differ by one fitting. Equal sinusoidal currents cancel in the neutral; unequal ones leave a residual, and nonlinear LED drivers add triplen harmonics that add in the neutral instead of cancelling. The neutral's volts displace the fitting's neutral terminal, so a phase-only or line-to-line-only check misses part of the delivered voltage. That is why the calculation runs phase and neutral together, section by section.
What does the section-by-section calculation give on a real run? #
18.8 V, or 8.2% of the phase voltage, at the last L3 fitting — a circuit that fails the permitted limit outright and would still be waved through on a line-to-line allowance, which is exactly the error in question.
Illustrative example inputs (not a code result — every value stated): three-phase four-wire feeder at the nominal system voltage, 50 Hz; 12 LED fittings each drawing 3.0 A at the phase voltage (the driver's rated input current, not watts divided by that voltage); rotation L1, L2, L3 repeating from fitting 1; first fitting 200 m from the origin, 30 m spacing, so fitting 12 sits 530 m out; 6 mm² copper phase and neutral. Copper at 0.0172 Ω·mm²/m at 20 °C gives 2.87 mΩ/m per conductor, × 1.2 for a 70 °C conductor gives 3.44 mΩ/m — the same basis as the mV/A/m cable tables. Reactance is ignored; at these sizes it is a small fraction of resistance.
The worst fitting is the last one on the longest phase run. Phase-conductor drop is Σ(I × L) × R:
| Route section | Length | L3 fittings downstream | L3 current |
|---|---|---|---|
| Origin → fitting 3 | 260 m | 3, 6, 9, 12 | 12.0 A |
| Fitting 3 → 6 | 90 m | 6, 9, 12 | 9.0 A |
| Fitting 6 → 9 | 90 m | 9, 12 | 6.0 A |
| Fitting 9 → 12 | 90 m | 12 | 3.0 A |
Σ(I × L) = 12.0 × 260 + 9.0 × 90 + 6.0 × 90 + 3.0 × 90 = 4740 A·m, so the L3 conductor drops 4740 × 3.44 mΩ/m = 16.3 V.
The neutral carries the vector sum per section. Fully balanced stretches — 12/12/12 A, 9/9/9 A, 6/6/6 A, 3/3/3 A — leave nothing. Wherever the counts differ by one fitting the residual is exactly one fitting's current: 3 A on one phase against 6 A on each of the other two leaves 3 A, because the two 6 A contributions sum to 6 A opposite the single phase and 6 − 3 = 3 A. Those sections total 240 m, so the neutral adds 3.0 A × 240 m × 3.44 mΩ/m = 2.5 V.
| Last fitting on each phase | Phase drop | Neutral drop | Total | Share of phase voltage |
|---|---|---|---|---|
| L1 — fitting 10, 470 m | 13.8 V | 1.9 V | 15.7 V | 6.8% |
| L2 — fitting 11, 500 m | 15.1 V | 1.9 V | 16.9 V | 7.4% |
| L3 — fitting 12, 530 m | 16.3 V | 2.5 V | 18.8 V | 8.2% |
Fitting 12 sits at 211.2 V. Against the permitted drop this fails; against a line-to-line allowance it would be signed off, and that is the size of the mistake. The fix is conductor size, route length or split feeders — the toolkit walked through for fixing voltage drop on a long 277 V lighting feeder. Here, 10 mm² scales the drop to 11.3 V (4.9%, 218.7 V at the fitting), passing with 0.2 V of margin, which is not margin worth designing on. Decision on these inputs: 16 mm² copper, which gives 7.0 V (3.1%, 223.0 V) under a 5% rule. If the adopted rule applies a 3% lighting figure, 16 mm² misses 6.9 V by 0.1 V — take 25 mm² (4.5 V, 2.0%) or split the run into two feeders. Re-check current-carrying capacity and protection coordination for the larger conductor, and treat the result as an estimate to verify against the governing code and the fitting documentation.
Which standard sets the limit? #
IEC 60364-5-52 does: clause 525 governs the voltage drop permitted between the origin of the consumer's installation and the equipment, and Annex G suggests 5% for general use but 3% for lighting.
The Annex G figures are recommendations — national wiring rules and their national annexes fix the enforceable numbers, the reference voltage and the reference points, so confirm the edition and amendments with your local authority having jurisdiction. Street lighting is lighting: if the adopted rule keeps Annex G's split, the budget is 6.9 V, tighter than the 5% premise calculated above. The reference points decide what goes in the budget: clause 525 measures from the origin of the installation, and where that origin sits upstream at a private substation, calculating voltage drop through step-up and step-down transformers belongs in the same budget.
How do I confirm the calculated drop with measurements? #
Two coordinated phase-to-neutral readings, one at the origin and one at the limiting fitting under the same load: their difference is the circuit's drop, while a simultaneous movement at both points is supply variation.
Use a true-RMS meter rated for the measurement category of the boards involved, and take the readings with all fittings energized — wait out or temporarily defeat the photocell so the assessed load is actually connected. Read what the numbers tell you: a difference that tracks load is conductor and joint impedance; one section or fitting far out of line is a joint resistance to repair, not an allowance to enlarge; phase-to-neutral voltages that diverge as load rises point at a neutral connection to check. Both readings are live work at fittings and boards, so they belong to qualified personnel following the site electrical safety procedure — NFPA 70E, 2024 edition, where it applies — with instruments and protective equipment that procedure requires.
Questions asked
Why do the two figures differ by 0.05 V?
The tabulated limit is 5% of the rounded nominal phase voltage. The 11.55 V arrives when you divide the nominal line-to-line voltage by 1.732, which lands on the 230.9 V phase voltage that the rounded 230/400 nominal pair hides. Both are 5% of their own reference, so the choice is only about consistency: use the reference your adopted rule names, and keep every drop in the calculation on that same basis.
Do LED driver harmonics change the neutral current?
They can. The vector-sum cancellation assumes sinusoidal currents. Drivers with significant triplen harmonic content, which the driver data sheet shows as input THD, put harmonic currents in the neutral that add arithmetically even when the fundamentals cancel perfectly, so the measured neutral drop can exceed the sinusoidal calculation. Drivers with low THD keep the difference small; measure the neutral current if the data sheet is silent.
Does the utility transformer drop count toward the 5%?
Not from where clause 525 of IEC 60364-5-52 measures: the span runs from the origin of the consumer's installation to the equipment, so the utility's transformer sits outside it. Anything you own inside that span, including a private substation transformer and every metre of cable after the origin, is inside the budget. Confirm where your local rule places the origin before allocating volts.
What if my local rule sets 3% for lighting?
Then the budget is 3% of the phase voltage, which is 6.9 V, and the floor is 223.1 V at the fitting. Annex G of IEC 60364-5-52 suggests exactly that split, 3% for lighting and 5% for other uses, and street lighting is lighting. In the worked example, 16 mm² lands at 7.0 V and misses by 0.1 V, so the committed choice there is 25 mm² or a split feeder.
Can I take one reading at the last fitting and compare it to 218.5 V?
Only with the origin voltage logged at the same moment. A lone 218 V reading means 11 V of circuit drop if the origin sits at 229 V, and none at all if the origin itself has sagged to 219 V. Two coordinated phase-to-neutral readings, origin and fitting, under the same load, are what separate supply variation from cable drop.