A 500 V 50 Hz motor on 400 V or 480 V supply
Short answer
Neither supply is a nameplate supply for this dual-rated motor: 400 V 50 Hz runs it at 80% of rated volts-per-hertz with about 64% of rated torque, and 480 V 60 Hz at 83.5% with about 70%. If the choice is forced, take 480 V and set the overload from measured current. The clean fix is a motor wound for the mains or a drive holding the rated 10 volts per hertz at 80% speed.

On this page
- Will a 500 V 50 Hz motor run on a 400 V supply?
- What does the volts-per-hertz ratio say about each supply?
- How much torque is left on each supply?
- What happens to the speed on each supply?
- Which supply draws more current?
- Can a VFD make this motor fit the mains?
- Which supply should I pick, and how do I set the overload?
- Questions asked
Neither proposal is a nameplate supply for this motor, and the choice between them is decided by volts per hertz. On 400 V 50 Hz the winding runs at 80% of its rated flux ratio and holds about 64% of rated torque; on 480 V 60 Hz it runs at 83.5% of rated flux with about 70%. If the installation must accept one of the two, take the 480 V connection and expect a hotter, torque-starved machine on anything near full load. Speed follows the supply frequency, current follows the coupled load, and the durable fix is a motor wound for the mains — or a drive that holds the rated ratio at reduced speed.
Will a 500 V 50 Hz motor run on a 400 V supply? #
It will spin and carry a reduced load, but it is 20% short of rated flux and delivers only about 64% of its rated torque, so a load near the 0.75 kW rating pulls the slip up until the overload trips or the motor stalls.
This example plate reads 500 V, 0.75 kW, 1.92 A, 2855 rpm at 50 Hz and 575 V, 0.86 kW, 1.96 A, 3455 rpm at 60 Hz — one winding specified for both supply systems, which is why the two lines share one flux ratio. Both proposals are three-phase line-to-line voltages, so every ratio below compares line-to-line against line-to-line. What the plate does not offer is a third voltage: a terminal-board reconnection exists only if the connection diagram shows one, and nothing on a dual-rating plate of this kind implies it.
What does the volts-per-hertz ratio say about each supply? #
The plate's flux ratio is 10 V/Hz at both of its ratings, and each proposal feeds 8 V/Hz: the reduced-voltage supply runs at 80% of rated flux, the higher-voltage supply at 83.5%.
Worked ratios for this nameplate:
- 50 Hz rating: 500 V ÷ 50 Hz = 10 V/Hz. The 400 V proposal gives 400 V ÷ 50 Hz = 8 V/Hz, which is 80% of rated flux.
- 60 Hz rating: 575 V ÷ 60 Hz = 9.58 V/Hz. The 480 V proposal gives 480 V ÷ 60 Hz = 8 V/Hz, which is 8 ÷ 9.58 = 0.835, so 83.5% of rated flux.
Read that as one defect in both cases: the frequency matches the winding, the voltage does not, so the iron runs at reduced flux and the torque-speed curve shrinks. For calibration, NEMA MG-1 expects a standard motor to deliver rated performance with supply voltage within 10% of nameplate at rated frequency; a fifth to a sixth below nameplate sits outside that band, so the manufacturer's data for this frame — not a general tolerance — is what clears the installation. That ratio is the entire reading of a dual-rating plate: the volts-per-hertz ratio and nameplate power of a dual-rated motor works through the same comparison.
How much torque is left on each supply? #
Electromagnetic torque at a given slip scales with the square of the voltage ratio, so the reduced-voltage supply leaves about 64% of rated torque — (400 ÷ 500)² = 0.64 — and the higher-voltage supply about 70%, from (480 ÷ 575)² = 0.697.
The square applies at every point on the torque-speed curve, so locked-rotor, pull-up and breakdown torque all drop by the same factor: a machine that broke away comfortably at rated voltage runs on roughly two-thirds of its margin on the reduced-voltage connection. These are torque ratios, not derated power ratings — the shaft power actually available depends on where the load lets speed settle, which the next section works through. The same physics at a narrower gap governs running a 460 V motor on a 400 V supply; only the size of the ratio changes.
What happens to the speed on each supply? #
Frequency sets synchronous speed, and both nameplate speeds imply a two-pole winding: the shaft settles near 2855 rpm on either lower-frequency connection and near 3455 rpm on the higher-frequency connection, a touch slower on the low-voltage lines because the deeper slip needed to rebuild torque costs speed.
Worked speeds for this plate:
- Synchronous speed = 120 × frequency ÷ poles. At 50 Hz: 120 × 50 ÷ 2 = 3000 rpm, and the rated 2855 rpm is (3000 − 2855) ÷ 3000 = 4.83% slip.
- At 60 Hz: 120 × 60 ÷ 2 = 3600 rpm, and the rated 3455 rpm is (3600 − 3455) ÷ 3600 = 4.03% slip.
- At rated load torque on the reduced-voltage supply, slip deepens by roughly the inverse of the torque factor: 4.83% ÷ 0.64 ≈ 7.5%, so speed sits near 3000 × (1 − 0.075) ≈ 2775 rpm. On the higher-voltage supply: 4.03% ÷ 0.697 ≈ 5.8%, so speed sits near 3600 × (1 − 0.058) ≈ 3390 rpm.
Those last two figures are linear-slip estimates, valid only on the straight part of the curve below breakdown — check them against the manufacturer's curve data before promising a speed to the machine builder. Moving from the nameplate frequency to the higher one lifts every speed in proportion to frequency, the same jump covered when a 415 V motor runs 20% faster on the next supply up, and a fan or pump asks for torque roughly with the square of that speed increase.
Which supply draws more current? #
There is no single winner: on a light load the under-fluxed motor draws less current because magnetizing demand falls, while at or near rated load both supplies push current above the nameplate figures, with the reduced-voltage supply the hotter because its torque ceiling is the lower.
The 1.92 A and 1.96 A on the plate describe the rated points: full flux, rated slip. Cut the flux and slip must deepen to rebuild torque, and stator and rotor copper losses deepen with it — which is why a lightly loaded machine often runs cooler on reduced voltage and a working one runs hotter. Judge by measurement, not inference: with the real load coupled, log all three line currents through acceleration and steady running and compare the phases against each other, because unequal phases point to a connection or winding fault, not to the voltage choice. Verify absence of voltage with the board locked off before any terminal work, and leave live checks to qualified people under the plant's electrical-safety procedure.
Can a VFD make this motor fit the mains? #
Yes — a drive holding the rated 10 V/Hz turns either mains into a valid supply: the reduced-voltage mains at 40 Hz, the higher-voltage mains at 48 Hz, both at 80% of rated speed with full rated torque available.
Three checks keep that honest. First, an ordinary voltage-source drive cannot synthesize more fundamental output voltage than its DC bus carries, so the drive's voltage class must match the winding — the shortfall behind a VFD that shows low output voltage while the motor has no torque, which is the same starvation quantified above. Second, at 40 Hz a fan or pump needs roughly (0.8)³ ≈ 51% of its nameplate-frequency shaft power, so speed-dependent loads fit with room to spare, while a constant-torque load keeps asking for full torque and gets it. Third, the shaft-mounted cooling fan slows in the same proportion, so confirm the frame's continuous low-speed cooling capability in the manufacturer's data before promising full torque indefinitely. Size the drive's current rating for the motor's rated amperes and the acceleration duty, not for the running load alone.
Which supply should I pick, and how do I set the overload? #
Take the higher-voltage supply if you must choose — it sits closer to both nameplate ratings, with 70% of rated torque available where the other line offers 64% — and treat either connection as a reduced-capability installation: set the overload from measured running current, not from the plate.
Case by case: a load with real torque margin — a fan, a centrifugal pump below its curve, a conveyor run light — runs acceptably on the higher-voltage connection and probably on the reduced-voltage one, with shaft-power expectations cut to match the torque figures. A constant-torque duty — a compressor, a positive-displacement pump, a crusher — has no honest margin on either connection: fit a motor wound for the mains, or fit a drive and run the winding at its rated flux ratio as in the section above. Never buy back a tripping start by raising the overload: the relay guards the winding, and the winding is what is overheating. Set it from the measured running current of the chosen connection, the way setting overload relays from motor nameplate full-load current works at rated supply — except the number entered here is measured, because the plate's amperes describe a supply this installation does not have.
Questions asked
Does a dual 500 V and 575 V rating mean the winding has two separate voltage taps?
No. Those two plate lines describe one winding specified for both the lower and the higher supply frequency, and the same terminal connection normally serves both. A star or delta reconnection exists only if the connection diagram on the plate or in the terminal box shows one for a voltage you can actually supply, so check the diagram before moving any links.
Is the service factor still usable on a supply this far below nameplate?
No. The service factor on the plate applies at rated voltage and frequency, because the manufacturer defines that thermal reserve at the nameplate condition. On either proposed supply, rated load already means deeper slip and higher losses than the plate's thermal design assumed, so the reserve is spent before the overload reaches its setting. Size the driven load to the torque the supply can actually deliver, not to the service factor.
Will it still break away a stiff load on the reduced-voltage supply?
Only if the load needs clearly less than the torque left on that supply. Locked-rotor and pull-up torque fall by the same voltage-squared factor as running torque, so a compressor loaded against pressure or a conveyor started under product can lose its entire margin. If the machine needs close to rated torque to turn, use a drive running reduced frequency at the rated flux ratio, or fit a motor wound for the supply.
Does running on the higher-frequency supply overstress the motor or the driven machine?
Yes, check the mechanics. The shaft turns about a fifth faster on the higher-frequency connection, and the plate lists no separate maximum speed for the rotor, its bearings or the fan. The driven machine speeds up by the same proportion, so its own rated speed, couplings and seals must accept it, and fan and pump demands rise steeply with speed. Verify both machines against the higher speed before committing to that line.