Troubleshooting
Why a VFD shows low output voltage and the motor has no torque
Short answer
The drive was following a V/f curve set far below the motor's rating: 38.6 V at 50 Hz instead of the 240 V a 220 V delta winding needs, about 16 percent of the required 4.8 V/Hz, which leaves roughly 3 percent of rated torque. Set base frequency and base voltage to the nameplate, then ring out and relink the six leads for low-voltage delta.

On this page
- Why is the VFD's output voltage so low?
- Why does low output voltage leave the motor with no torque?
- What should the V/f settings be for this motor?
- Why does a multimeter jump around on a VFD output?
- Does the DC bus reading prove the drive is healthy?
- How do you verify the six motor leads before relinking?
- What happens if the motor stays in star instead of delta?
- In what order should these checks run?
- Questions asked
An induction motor that spins freely but carries almost no torque usually has a voltage problem upstream of the windings, not a winding fault. In the case behind this article, a 1 hp, 220/415 V, six-lead motor ran to full speed with its belt disconnected and could be stopped with two fingers, while the drive's keypad showed 38.6 V at 50 Hz — about one-sixth of what the motor needed. The cause was the drive's V/f curve, set far below the nameplate. Correct the base voltage and base frequency settings first, then verify the six leads are linked for low-voltage delta; the loaded run at the end is what proves the repair.
Why is the VFD's output voltage so low? #
The drive is following the wrong point on its V/f curve: the output was 38.6 V at rated frequency, roughly 16 percent of the voltage the nameplate calls for, and that setting — not the motor — is what caps the torque.
In V/f control, the drive holds output voltage proportional to output frequency along a curve the settings define: as the speed command raises frequency toward base frequency, voltage climbs with it so the motor's flux stays constant, and at base frequency the curve must reach the motor's rated voltage. This drive's curve was scaled down — its rated-voltage point sat far below the nameplate — so every frequency arrived with a fraction of the voltage behind it. A drive sold as ready to run still ships a generic curve; nothing in it knows your motor.
The keypad told the story consistently: a healthy bus, the frequency command at rated frequency, and an output stage only following the curve it had been given. The V/f points live in the keypad's control-mode or V/f group, and manuals call the voltage point base voltage or intermediate voltage depending on the brand — match the setting by what it does, not by a number. Raising that point to the nameplate value restored full output at rated frequency in this installation, and the meter question below covers checking it independently.
Why does low output voltage leave the motor with no torque? #
Torque in an induction motor scales roughly with the square of the volts-per-hertz ratio, so running at 16 percent of the required ratio leaves about 3 percent of rated torque — a shaft you can stop with your fingers, which is exactly what this motor did.
Air-gap flux follows the voltage-to-frequency ratio. Feed rated frequency with a fraction of rated voltage and the field collapses; the rotor has almost no field to react against, so the shaft coasts unloaded and stalls on the smallest load. The keypad's 0.1 A of output current fits the same picture: a collapsed field draws very little magnetizing current.
Worked example, from the displayed values and the V/f relationship in the drive manual — an estimate of the size of the problem, not a measurement:
- Required ratio: 240 V ÷ 50 Hz = 4.8 V/Hz
- Delivered ratio: 38.6 V ÷ 50 Hz = 0.77 V/Hz
- Fraction of required: 0.77 ÷ 4.8 = 0.16, about 16 percent
- Torque estimate: 0.16 × 0.16 = 0.026, about 3 percent of rated torque
The square-law step assumes V/f mode and ignores stator resistance drop and saturation, so treat the 3 percent as order-of-magnitude and let the loaded run decide. Disconnecting the belt was still the right move: it proved the motor spins free and pointed the search at excitation. It proved nothing about the windings, because an under-fluxed motor spins free too.
What should the V/f settings be for this motor? #
Set the base frequency to the motor's rated frequency and the base voltage to the motor's rated voltage — for this motor, 50 Hz and 240 V, a ratio of 4.8 V/Hz — then use the keypad monitor to confirm output voltage tracks frequency up to those values.
Both values live in the drive's V/f or control-mode menu group; the voltage point appears in manuals as base voltage or intermediate voltage depending on the brand, so match settings by what they do, not by a parameter number. While the keypad is open, enter the rest of the nameplate — rated current, rated speed, rated frequency — because the drive's overload protection and torque estimate run on that data; article:spindle-vfd-hums-but-won-t-turn-fixing-wrong-motor-data shows what wrong motor data looks like from the shaft side. This installation, corrected, displayed full output at rated frequency with roughly 0.4 A of unloaded current — four times the earlier reading — before the loaded run, which remains the test that proves the fix. If the drive offers base frequencies above the motor's rating, leave them alone unless the application genuinely needs them: beyond base frequency the curve flattens and torque falls with speed.
Why does a multimeter jump around on a VFD output? #
The output is not sine-wave AC: the drive chops its DC bus into pulses several kilohertz wide, so an ordinary averaging meter reacts to every edge and swings across its ranges — that 20-to-1000 V flicker was the meter, not a changing voltage.
The output stage varies the pulse widths to shape the fundamental; an averaging display runs from tens of volts to the top of the range and back without meaning anything. Read the drive's own output-voltage and output-current monitors first: they are the drive's computed fundamentals and they answer the low-voltage question directly, as the sections above used them. For an independent figure, use a true-RMS instrument the drive manufacturer lists as suitable for PWM output measurements, connected and set up per its instructions — anything else on drive output reads noise. Probing live output terminals while the drive runs adds risk for little information; the keypad already shows what the output is doing.
Does the DC bus reading prove the drive is healthy? #
No: 323.3 V on the bus of a single-phase-input drive proves only that the rectifier is charging the bus; the inverter stage between that bus and the motor terminals sets the output voltage, and its V/f settings govern that stage.
An unloaded bus sits near the peak of the incoming AC, about 1.414 times the line RMS: 1.414 × 228 V = 322.4 V, so the reading on this keypad corresponds to an input of roughly 228 V RMS — present, a little low, and otherwise uninformative. It told you the supply and rectifier were alive and the input fuses were intact, nothing about what the motor received. Use the bus reading to confirm supply health, then judge the output from the output monitor.
How do you verify the six motor leads before relinking? #
With the equipment verified dead, isolate the six leads, ring out three resistance pairs with a meter, and rebuild the links from the motor's own diagram — the printed block a previous owner fitted proves nothing about which winding ends sit where.
Before the box opens: de-energize the feeder, lock out, and verify absence of voltage at the motor terminals as NFPA 70E, 2024 edition, requires for this kind of work; a drive's DC bus stays charged after shutdown, so wait the discharge time printed on the drive — IEC 61800-5-1, 2017 edition, requires that marking — and follow the manual's discharge steps. Editions and local amendments differ, so confirm the details with your authority having jurisdiction and the equipment documentation. Then:
- Disconnect the three output conductors at the motor and remove every bridge from the block.
- Measure resistance across all pairs of the six isolated leads. Exactly three pairs conduct — those are your windings. Label each pair.
- Compare the three resistances. Similar values support balance; an open pair or a wide gap stops the job for repair, not relinking.
- Fix each winding's start and finish from the cover diagram or the lead markings. Resistance cannot tell an end from a start, and a transposed end scrambles the winding relationship inside the motor in a way no conductor swap can cause or cure.
- Rebuild the low-voltage delta from the verified ends: U1 to W2, V1 to U2, W1 to V2, with one output conductor on each junction.
- Treat any recipe that ends W1 to U2 as a typo — it repeats U2 and strands V2. In a correct delta, each of the six ends appears exactly once.
- Never bridge U1 to U2, V1 to V2 and W1 to W2 and feed each pair: every winding then has both ends on the same conductor, sees zero volts, and no rotating field can form.
This motor arrived without its terminal block, so every marking on the new one needed proving against resistance readings and the cover diagram. Phrases like horizontal links or vertical links describe one specific block layout, not a rule — the junction identities are what count. article:wiring-nine-lead-dual-voltage-motor-leads-to-a-vfd works this same end-identification problem on a nine-lead dual-voltage machine.
What happens if the motor stays in star instead of delta? #
Star puts the line voltage divided by √3 on each winding — about 139 V where these windings are built for 220 V — so the motor is under-excited to 63 percent of design flux and torque drops to roughly 40 percent by the square law, even with the drive set correctly.
The division is the point of the two connections: delta puts the line voltage directly across each winding, star puts the line value divided by √3 across each. The line value here divided by √3 comes to 138.6 V, and 138.6 against the winding rating above gives 0.63 — 63 percent of design excitation, which the square law turns into roughly 40 percent of torque. That is the second way this symptom appears: the drive can be outputting exactly what its settings say and the connection still starves the windings. Low-voltage delta and high-voltage star exist precisely so the same windings suit two line voltages, which makes the nameplate voltage pair a verification target in its own right — read the actual plate and the manufacturer's diagram before trusting either link position. article:wye-or-delta-winding-for-a-200-hp-480-v-motor works the same connection choice from the voltage pair on a much larger machine.
In what order should these checks run? #
Fix the electrical basics de-energized first, then the drive settings, then the loaded run: verify dead, ring out the windings and rebuild the links, enter the nameplate data and the V/f points, run unloaded, and only then couple the belt.
- De-energize, lock out, verify absence of voltage at the motor terminals, and wait the drive's marked discharge time.
- Disconnect the output leads, ring out the six leads, and rebuild the low-voltage delta from verified winding ends.
- Enter the nameplate data and set the V/f base points on the keypad.
- Run unloaded and watch the keypad: output voltage should climb to the base voltage point at rated frequency, with unloaded current in a sane range for the motor — a fraction of nameplate, not a trickle.
- Couple the load and compare running current against the nameplate.
- If voltage, links and data all verify and torque is still missing, the fault sits in the driven machine or in nameplate data that never matched the motor — a binding load reads exactly like a weak motor.
Decision, case by case. Keypad showing a fraction of rated output at rated frequency: correct the V/f base points before touching the motor — that alone restored full output here. Output voltage correct but torque still weak: suspect the links, and ring out the leads to rebuild the low-voltage delta from verified ends, because star on a low-voltage winding set reads as a weak motor. Voltage, links and nameplate data all verified and torque still missing: the fault is mechanical or the nameplate is wrong, and the belt-off test with a resistance balance check separates the two. A replacement block's markings, a factory V/f curve and a bus reading can each mislead you, in that order — resistance readings, the actual plate and one loaded run are what settle it.
Questions asked
Does it matter which output conductor lands on U1, V1 or W1?
For torque, no: swapping any two of the three conductors only reverses rotation, and if the machine runs backwards you exchange two conductors with the equipment locked out. What matters is that each conductor lands on a junction built from one start and one finish of two different windings; conductor order cannot repair a transposed winding end.
Can a drive set for 240 V feed windings marked 220 V delta?
It is about 9 percent above the winding rating. Most motors are built to give rated performance across roughly a 10 percent voltage band at rated frequency, so continuous running is normally acceptable; confirm against the motor's own documentation and watch for extra heating or noise on the loaded run. If the plate offers no rating at that voltage, ask the manufacturer before relying on it.
What unloaded current should a healthy motor this size draw?
An induction motor on a correct V/f curve typically draws roughly one quarter to one half of nameplate current with no load attached. The reported 0.1 A sat far below that, which fits a collapsed field; after the setting fix the same drive showed about 0.4 A unloaded. Judge your reading against the nameplate amps rather than against another motor's.
Can I measure winding resistance with the drive still connected?
No. Lock out, verify absence of voltage, disconnect the three output conductors at the motor, and wait the discharge time marked on the drive before touching anything. A resistance reading taken through connected leads measures the drive's output circuits along with the windings and can damage the meter; ring the windings only with the leads isolated at the terminal box.
How can I check a dual-voltage rating pair against the winding connections?
Multiply the low-voltage rating by 1.73; the result should match the high-voltage rating within rounding, because star puts the line voltage divided by the square root of 3 on each winding while delta puts the line value directly across it. A reported pair that misses that ratio does not describe one set of windings in two connections, so read the motor's own plate and diagram before trusting either link position.
