Explainer
Arc flash labels for a DC UPS battery bank
Short answer
Locking out the UPS charger does not remove the hazard: the series string is still a 120 V DC source. Assess the whole bank with a documented DC method from NFPA 70E Annex D, using the manufacturer's bolted-fault current, the real terminal gap and the task's working distance. At example inputs of 130 V, 20 kA, a 1/2 in gap and 18 in, published test data shows about 1.3 cal/cm², so label from the calculation instead of claiming a module-level exception.

On this page
- Does locking out the UPS charger remove the battery arc flash hazard?
- Should a bank of five 24 V batteries be assessed at 24 V or 120 V?
- Does an ungrounded bank or a small line-to-ground fault avoid needing a label?
- How do you calculate DC incident energy for a battery bank?
- Can the battery's ampere-hour rating give you the fault current?
- What does published DC test data say about a bank this size?
- When does a battery bank label have to be rechecked?
- Questions asked
A locked-out charger does not settle the label question on a substation UPS battery bank. With the charger circuit locked out, the five-module series string — nominally 120 V DC, about 140 Ah, commonly three parallel strings — is still the energized source at the main terminals, and the label comes from a documented DC arc flash calculation on that whole connected bank, not from the module rating, the ungrounded design or the lockout itself. NFPA 70E, 2024 edition, frames the work through the arc flash risk assessment and equipment labeling provisions of Article 130, with DC calculation methods documented in its informative Annex D. The sections below sort out which voltages govern, what the calculation needs, what the test data says, and where the genuine exceptions end.
Does locking out the UPS charger remove the battery arc flash hazard? #
No. Lockout removes only the charger's contribution, and the 120 V string across the terminals you are about to work stays fully energized; the battery, not the charger, is the source the label must describe.
Sequence the task accordingly: lock out the charger circuit, apply the lock, and verify with a meter that the charger side is dead before anything is opened — that de-energize-and-verify step covers the charger contribution and nothing else. The bank itself cannot be switched off for terminal testing or module replacement, so that work is planned as energized exposure under the site electrical safety program, with shock protection addressed alongside. The source the study must characterize is the bank at its main terminals: the string voltage across them and the bolted fault current they can deliver. That current comes from the battery manufacturer's data for the installed module, not from the charger breaker's rating, and the treatment of bolted fault current at DC battery bank terminals is covered step by step in Bolted fault current at DC battery bank terminals.
Should a bank of five 24 V batteries be assessed at 24 V or 120 V? #
Assess the exposure at 120 V DC: five 24 V modules in series put the full string voltage across the interconnects and main terminals, and replacing one module exposes conductors tied to the whole string; only work isolated to a single disconnected module is judged at the module's own rating.
The distinction matters because the tasks touch different parts of the same circuit. Replacing one 24 V module opens the string at that module, but the exposed interconnects still sit at string potential on their far ends, and a slipped tool across them sees the whole bank. The mapping from bank facts to assessment decisions is short:
| Bank fact | Assessment consequence |
|---|---|
| Five 24 V modules in series | Assess the exposed circuit at the full string voltage, 120 V DC; a module's own rating never describes the string exposure |
| About three parallel strings | Model the strings actually connected during the task; each one feeds a fault at the main terminals |
| 140 Ah nameplate | Storage capacity, not a fault-current input; the bolted number comes from manufacturer data |
| Ungrounded bank | Limits a first fault to ground; it does not touch terminal-to-terminal arc energy |
| Charger locked out | Removes the charger contribution only; the bank remains the source under assessment |
The one narrow case for the module rating is written into the study as a task-specific finding — module electrically out of the circuit, no exposed string conductor within reach — never applied bank-wide.
Does an ungrounded bank or a small line-to-ground fault avoid needing a label? #
No. A first fault to ground on an ungrounded bank drives limited current, but the terminal-to-terminal energy the label describes is unchanged, so an ungrounded design or a 12 V module rating is not a labeling exception.
What the ungrounded design does govern is the line-to-ground case: a first ground fault on an ungrounded DC bank drives limited current and often goes unnoticed, so the ground-fault number is small. That says nothing about a terminal-to-terminal arc, which is the event an incident energy analysis quantifies and the event a worker at the main terminals can actually initiate.
Wide terminal spacing works the same way — generous post spacing makes initiation less credible and can prevent sustainment — but that is a task-location finding the study records, not a bank-wide exemption, and closely spaced charger lugs or test-lead tips at the same bank justify their own number. Read the scope the same way NFPA 70E does: the assessment follows the task and the exposed conductors, so every argument about grounding or spacing lands in the study as an input, and none of them removes the label decision from the calculation.
How do you calculate DC incident energy for a battery bank? #
Use a documented DC method, not the AC tables: NFPA 70E's informative Annex D carries DC calculation methods — the Doan adaptation of the Lee method, refined by Ammerman's arc-voltage model — driven by four inputs: bank voltage, bolted fault current, gap and working distance, plus arc duration.
The lineage matters when you defend the number. Lee's open-air method was adapted to DC circuits and carried in Annex D of the 2012 edition; Ammerman and colleagues later rebuilt the arc voltage term from measured data reaching back to Ayrton a century ago, lowering predictions while staying close to the Doan value. The published arc-voltage compilations behind that work cover currents from a fraction of an ampere to 100 kA and gaps from 1 mm to 200 mm, so a 13 mm interconnect gap sits well inside the documented model range. When a DC calculation is required at all, and what the standard's main body asks for, is laid out in DC arc flash under NFPA 70E: when calculation is required.
Worked example, with clearly labeled example inputs so you can substitute your own: bank floating at 130 V DC under charge, manufacturer's bolted fault current 20 kA, gap 1/2 in (13 mm) at an intercell connector, working distance 18 in (455 mm), arc duration 0.8 s. For an idealized bound in the style the Annex D methods use, assume the arc absorbs half the string voltage at half the bolted current and radiates all of it over a sphere at the working distance:
- Arc power: 65 V × 10 kA = 650 kW
- Arc energy: 650,000 W × 0.8 s = 520,000 J
- Sphere area at 455 mm: 4π × (0.455 m)² = 2.60 m²
- Bound: 520,000 J ÷ 2.60 m² = 200,000 J/m², and 200,000 ÷ 41,840 J per cal/cm² = 4.8 cal/cm²
The published DC test interpretation at these same inputs measured 1.3 cal/cm², about a quarter of the bound — the repeated test finding that real arcs radiate far less than the idealization, with the arc's voltage demand rising steeply below a threshold voltage and sustainment getting hard at small banks' energy levels. The bound also shows what moves the answer: halve the duration to 0.4 s and it halves to 2.4 cal/cm²; step back to 24 in (610 mm) and it drops by (18/24)² ≈ 0.56, to about 2.7 cal/cm². Order the label from the documented method's output for your measured inputs — for this example set, 1.3 cal/cm² at that working distance. Every figure here is an estimate to confirm against the method's documented range, the edition your program adopts and the equipment documentation, and to confirm with your authority having jurisdiction where the requirement is in question.
Can the battery's ampere-hour rating give you the fault current? #
No — ampere-hours measure storage capacity, not prospective short-circuit current; a 140 Ah rating by itself fixes nothing about the bolted number the calculation needs. Get the module or string short-circuit current from the manufacturer's data, then add every parallel string that stays connected.
A VRLA module's prospective current follows from its internal resistance, state of charge and temperature, and manufacturers publish it per model, sometimes as an internal resistance you divide the open-circuit voltage by. Ampere-hours answer a runtime question — how long the bank feeds its load — and belong in the UPS sizing file, not the arc flash input list. Where strings run in parallel, each connected string delivers its contribution at the main terminals, so the study models the strings tied to the bus during the task, not the nameplate average; a module swap on one string, with the others still connected, still sees those strings through the interconnects. Write the per-string data, the connected count and the summation into the study record so the bolted number can be checked line by line.
What does published DC test data say about a bank this size? #
Published DC arc tests interpreted at 130 V, 20 kA, a 1/2 in gap and an 18 in working distance measured about 1.3 cal/cm² over a 0.8 s arc — low enough to plan around, but a per-bank calculation result, not a blanket exemption for every task and spacing.
That value comes from published DC arc testing in this voltage class, and two findings shape how you read your own result. First, radiated energy lands well below the idealized bound — the measurement above was roughly a quarter of it — so the Lee-style bound behaves as a ceiling, not a prediction. Second, arc voltage data going back a century shows threshold behavior: below a threshold voltage the arc's resistance climbs steeply and sustainment becomes difficult, which is why small ungrounded banks keep coming out with small numbers. Neither finding is an exception. Spacing follows the same logic: widely spaced battery posts make initiation less credible and that judgment is recorded per task location, while closely spaced charger lugs on the same bank get their own, likely higher, figure. One bank can correctly carry different label values at different locations.
When does a battery bank label have to be rechecked? #
Recalculate and relabel whenever the modeled bank stops matching the installed one: a changed module type, an added parallel string, new interconnect geometry, different protection or a different working method each moves the inputs enough to move the label.
Verification is field work before it is paperwork: confirm the installed series count per string, the parallel strings actually connected, the measured gaps at each task location, and the protective devices that will actually clear the fault. Charger lockout never gets credited as isolation of the batteries. NFPA 70E, 2024 edition, carries this entire exercise under the Article 130 arc flash risk assessment and equipment labeling provisions, with the DC methods in informative Annex D; where the program wants shock data on the same plate, NFPA 70E allows shock and arc flash data on one equipment label, and Shock and arc flash data on one equipment label: what NFPA 70E allows details what a combined label can hold.
The decision, stated plainly: a substation UPS battery bank is labeled from a documented DC calculation run on the full connected bank — every series module, every parallel string — per task location, with measured gaps, real working distances and manufacturer fault-current data. The module rating, the ungrounded topology and one small test number are inputs and context, not exceptions, and the only no-label outcome is the one the study itself documents as not credible at that location.
Questions asked
What PPE matches a battery bank arc flash label?
Select arc-rated PPE with a rating at least equal to the label's printed incident energy at its stated working distance. For a reading like this example's, standard arc-rated work clothing at or above the printed value covers the arc portion. Read the label rather than the module voltage: low DC energy numbers still leave the bank's shock hazard, which the label's shock section addresses on its own terms.
How far out is the arc flash boundary for a small DC bank?
NFPA 70E defines the arc flash boundary as the distance at which incident energy falls to 1.2 cal/cm². Scaling the example label value by the inverse square of distance: 18 in × sqrt(1.3/1.2) = about 19 in, roughly 0.48 m — barely past the working distance, which is typical for a bank of this size. Treat it as the method's estimate and print it from your own study.
Does IEEE 1584 give me a DC calculation?
No. IEEE 1584's incident energy model is built for three-phase 50/60 Hz AC systems and does not extend to DC. For battery banks, use a documented DC method such as the Annex D approach in NFPA 70E or the published DC arc model literature, and record which method, inputs and edition your study used.
Should each task on the bank get its own number?
Yes where the inputs differ. Main terminal work sees every parallel string and the closest conductor spacing; module replacement sees the string voltage with the module removed; charger lug work sees different gaps. The study can share one number where inputs genuinely match, but the task list, gaps and working distances belong in the record.