Explainer
Checking a 2500 A incomer against a 1600 kVA transformer
Short answer
The corrected running load is 2196 A at 415 V, so the 2500 A incomer holds it with 304 A of margin, but the 1600 kVA transformer's rated secondary current is about 2226 A — 98.7 percent loaded. Accept both only after the long-time pickup is set at or below the transformer rating, every permitted start fits the trip curve, and the fault study clears the 100 kA withstand.
On this page
- Is the 2500 A incomer adequate for this panel?
- What current must the incomer carry with everything running?
- What does the code require for a main feeding several motor loads?
- Example: what secondary current does a 1600 kVA transformer deliver at 415 V?
- Does the incomer protect the transformer from overload?
- Will starting the pumps and chillers trip the incomer?
- Is the busbar's 100 kA withstand enough for the fault duty?
- How do you verify the settings before the panel is trusted?
- Questions asked
A 2500 A incomer is the right frame for this panel only after three checks: the corrected running load totals 2196 A at 415 V and leaves 304 A of margin to the frame, the trip settings must sit below the 1600 kVA transformer's rated secondary current of about 2226 A, and the fault duty must stay inside the switchboard's withstand rating. The load list circulating with this panel dropped one pump; the corrected sum and the checks below decide whether the consultant's transformer and the existing breaker both stand.
Is the 2500 A incomer adequate for this panel? #
Adequate on running load and close on starts, but the frame size decides nothing by itself: you need 304 A of running margin confirmed against real demand, start events that fit the trip curve, and a fault duty below what the breaker and the switchboard can withstand.
Three decisions hide behind "is it adequate": carrying the running load, supplying each start without an unwanted trip or an unacceptable dip, and clearing a bolted fault within ratings. The frame answers none of them. Treat full simultaneity as the design check and credit the HVAC staging as diversity only where the chiller controls demonstrably keep all compressors from loading at once — with 30 A of transformer headroom, undocumented diversity is not a substitute for a load schedule.
| Decision | Data you need | What it settles |
|---|---|---|
| Running load | Rated currents, transformer rating, busbar rating, long-time pickup | Whether the whole path carries the simultaneous load |
| Starting | Start currents and durations, staging sequence, trip curve | Nuisance-trip risk and voltage dip |
| Fault duty | Transformer impedance, utility data, breaker interrupting rating, assembly withstand | Whether a bolted fault clears within ratings |
What current must the incomer carry with everything running? #
Plan for full simultaneity: two chillers at 1003 A, two pumps at 81 A, one air-handling unit at 12 A and one lighting board at 16 A sum to 2196 A, which is 304 A under the frame.
| Load | Quantity | Rated current each | Subtotal |
|---|---|---|---|
| Chiller | 2 | 1003 A | 2006 A |
| Pump | 2 | 81 A | 162 A |
| Air-handling unit | 1 | 12 A | 12 A |
| Lighting distribution board | 1 | 16 A | 16 A |
| Total | 2196 A |
A circulating calculation that totals 2115 A has dropped one pump's 81 A — the table restores it. The chillers stage their compressors to HVAC demand, so measured demand may sit below this sum, but credit that only with the controls' permitted stage combinations in hand. The same summing exercise on a smaller board is worked through in sizing the feeder breaker for three motors on one 208 V feeder.
What does the code require for a main feeding several motor loads? #
NFPA 70, the National Electrical Code, 2023 edition, Article 430 sizes a multi-motor feeder conductor at the sum of the full-load currents plus 25 percent of the largest motor, and caps the feeder overcurrent device at the largest branch short-circuit device plus the other motors' full-load currents.
Those rules assume separate motors. A chiller is one listed packaged assembly: its rated load current already accounts for the staged compressors inside it, so it enters the sum once at its nameplate value — you cannot add 25 percent of the chiller's 1003 A rating as though the package were a single motor. The 2366 A figure built that way both overstates the adder and rests on the pump-omitting 2115 A base, so it settles nothing. Requirements differ by country, edition and local amendment: confirm the applicable rules with the authority having jurisdiction and the equipment documentation. In IEC jurisdictions, IEC 61439 addresses the same reality through the assembly's rated diversity factor.
Example: what secondary current does a 1600 kVA transformer deliver at 415 V? #
The rated secondary line current of a three-phase transformer is S × 1000 ÷ (√3 × V_LL), and the arithmetic below puts this unit at about 2226 A — the corrected running load sits at 98.7 percent of it, with roughly 30 A or 21 kVA of headroom.
- Rated current: I = 1600 kVA × 1000 ÷ (1.732 × 415 V) = 1,600,000 VA ÷ 718.8 V = 2225.9 A
- Connected load: 1.732 × 415 V × 2196 A = 1,578,485 VA ≈ 1578.5 kVA, and 1578.5 ÷ 1600 = 98.7 percent of rating
- Headroom: 1600 − 1578.5 = 21.5 kVA, about 30 A at this voltage
State the assumptions: three-phase load, nameplate kVA, secondary terminal voltage held at rated. This is a rating estimate to be checked against the nameplate, not a measured demand. On these inputs the transformer is a close full-load match to the connected load, not a generous supply — it stands only if the loads genuinely run together and the protection holds it at or below rating.
Does the incomer protect the transformer from overload? #
Not by frame size alone: with the long-time pickup left at the full frame, the transformer could be held about 12 percent above its rated secondary current indefinitely, so set the pickup at or below the transformer's rated current with a delay that coordinates downstream.
A frame rating is a thermal and interrupting envelope; the adjustable long-time pickup is the actual operating threshold. The ratio 2500 A ÷ 2226 A is 1.12, so a frame-level pickup tolerates 112 percent of the transformer's rating indefinitely. Set the long-time pickup at or just below the transformer's rated secondary current, take the delay from the transformer's overload guidance, and coordinate so downstream devices clear first. Confirm the primary-side device covers internal faults — the secondary breaker cannot see them. And check the restart plan: after a supply interruption, an unstaged restart of every compressor together is a bigger starting event than any single start below.
Will starting the pumps and chillers trip the incomer? #
The pump restart governs: with one pump offline and everything else running, 2115 A of running load plus its 555 A start is a 2670 A transient, about 107 percent of the frame — this rides on the short-time and instantaneous settings, not the frame.
The one-minute pump-before-chiller delay removes one overlap, not all of them: a pump can restart while both chillers run, and each compressor stage starts against whatever is already online. The worst chiller case is one chiller running at its 1003 A rating while the second starts at its 969 A maximum with everything else online: 1003 + 969 + 162 + 12 + 16 = 2162 A, below the frame. Two inputs are missing from the equipment data you have: the pump's accelerating time, and the source impedance that sets how deep the bus dips during each event. Starting peaks are an instantaneous-setting question, not a frame question — why motor start peaks don't compare to instantaneous breaker settings gives that distinction. The dip itself comes from the source impedance behind the transformer; motor starting voltage drop with utility short-circuit capacity works that calculation.
Is the busbar's 100 kA withstand enough for the fault duty? #
Unknown until the impedance data is in: 100 kA for 1 s is the busbar's short-time withstand, not the breaker's interrupting rating, and the prospective fault current follows from the transformer nameplate impedance plus the utility contribution — at an assumed 6 percent impedance the secondary would deliver about 37 kA.
Withstand and interrupting are different numbers. The 1 s figure says how much current the bars, supports and bracing carry while a device clears; the air circuit breaker's rated breaking capacity says what the device itself can interrupt at the service voltage. The prospective current is the transformer's rated secondary current divided by its per-unit impedance, plus the utility contribution and motor feedback. Illustration only: at an assumed 6 percent impedance, 2226 A ÷ 0.06 = 37.1 kA from the transformer alone. If the study total exceeds the withstand or the breaking capacity, the board fails the fault check no matter how much load margin it has — pull the nameplate impedance and the utility's available fault data and run the numbers; calculating a transformer's interrupting current from its impedance lays out the method.
How do you verify the settings before the panel is trusted? #
Read the trip unit and then watch a full-load run: record the long-time pickup and delay, short-time pickup and delay, instantaneous and earth-fault settings from the ACB's trip-unit display, then trend per-phase current and voltage through each permitted start and at maximum demand.
- De-energize, lock out and verify absence of voltage before opening any cubicle; on many motorized ACBs the trip-unit display shows settings with the door closed.
- Compare the long-time pickup with the transformer's rated secondary current; plot each start event on the time-current curve for the installed trip unit, including the 2670 A pump restart.
- Trend per-phase current and voltage at maximum demand and through each start. If the board has no historian, meter data collection belongs on a fanless mini PC beside the switchboard.
- Confirm the chiller controls stage their restart after a supply interruption instead of starting every compressor together.
- File the transformer kVA and impedance, the trip settings and the equipment rated currents, so the next change is checked against numbers rather than memory.
Questions asked
Why can't the 25 percent largest-motor rule be applied to the chiller's rating?
NFPA 70 Article 430 applies the 25 percent adder to individual motor full-load currents when a feeder serves separate motors. A chiller is one listed packaged assembly whose rated load current already covers its staged compressors and controls, so it enters the load sum once at its nameplate value. A 2366 A result built by adding 25 percent of the chiller rating is unsound; confirm the governing method with the authority having jurisdiction.
How much apparent power can the incomer actually pass at 415 V?
At 415 V three-phase, 2500 A corresponds to 1.732 × 415 V × 2500 A, which is about 1797 kVA — roughly 12 percent above the transformer's 1600 kVA rating. That gap is the argument for setting the long-time pickup below the frame: the switching device can command more apparent power than the transformer should deliver continuously.
Does starting the pump first make the starting current irrelevant?
No. The delay removes the pump-and-chiller overlap, but a pump can restart while both chillers are at full load, putting about 2670 A through the breaker for the pump's accelerating time. Check every combination the controls permit against the trip curve, and get the start duration from the pump manufacturer's data before calling the sequence safe.
What is the difference between the 100 kA withstand and the breaker's interrupting rating?
The 100 kA for 1 s figure is the switchboard's short-time withstand current: how much fault current the busbars and supports carry for one second while a device clears. The air circuit breaker's interrupting rating is its tested breaking capacity at the service voltage. Both must exceed the calculated prospective fault current, including the utility contribution and motor feedback.