Current IntelPower LibraryShop main store

Explainer

Motor starting voltage drop with utility short-circuit capacity

Power quality and harmonics Published 7 min read

Short answer

Dip% = 95 × starting MVA ÷ combined short-circuit MVA at the motor bus, where 1/S_total = 1/S_source + 1/S_transformer and starting MVA comes from locked-rotor amps, never full-load amps. For a 1000 HP motor at 4.16 kV with 25 kA available at 33 kV (about 1429 MVA), the utility term is small behind a small transformer but sets the ceiling behind a stiff one.

On this page
  1. The rule of thumb and its two errors
  2. Where the 95 percent factor comes from
  3. Adding the utility short-circuit capacity
  4. Worked example: 1000 HP motor on a 33/4.16 kV transformer
  5. What the result has to satisfy
  6. When the dip is deep, solve the quadratic
  7. Questions asked

The rule of thumb is defensible once you fix two things: build starting kVA from locked-rotor amps, not full-load amps, and divide by the short-circuit MVA of everything behind the motor, not the transformer alone. The corrected working formula is dip% = 95 × starting MVA ÷ combined short-circuit MVA, with 1/S_total = 1/S_source + 1/S_transformer. For the case in question, 25 kA at 33 kV works out to about 1429 MVA; behind an assumed 2500 kVA, 5.75% transformer, a 1000 HP motor starting at 6.5 MVA dips the 4.16 kV motor terminals about 14.6%, leaving 85.4% — above the usual 80% floor. The derivation, the arithmetic and the decision follow.

The rule of thumb and its two errors #

The posted version computes starting kVA as √3 × voltage × FLA and divides by the transformer short-circuit kVA. Both halves err in the same direction. Full-load amps is the running current; at standstill the motor draws locked-rotor current, commonly six to seven times FLA, so starting kVA built from FLA understates the load by that multiple. And the transformer short-circuit MVA presumes an infinite bus at the primary: a real source adds impedance in series, which lowers the number you divide by and raises the dip.

The same dip arithmetic on a stiff bus, where one impedance dominates, is worked through in motor starting voltage dip calculation on an 11 kV bus. The interest here is the opposite case, a transformer-limited secondary with a finite source, where both impedances count.

Where the 95 percent factor comes from #

Model the system as a source voltage Vs behind an impedance R + jX, delivering motor current I at power-factor angle φ into a terminal voltage VL. The phasor identity is:

Vs² = (VL·cos φ + R·I)² + (VL·sin φ + X·I)²

Expand it, drop the second-order terms in R·I and X·I, and the approximation is:

Vs − VL ≈ I·(R·cos φ + X·sin φ)

Locked-rotor power factor at standstill is low — near 0.3 for machines this size, with the exact value on the motor datasheet — so cos φ ≈ 0.3 and sin φ = √(1 − 0.3²) = 0.954. In a source-plus-transformer system R is small against X, so the drop is essentially 0.954·X·I per phase.

Convert to system quantities with S_sc = V_LL² ÷ X (the three-phase short-circuit MVA) and S_start = √3 × V_LL × I, and the per-unit drop collapses to sin φ × S_start ÷ S_sc:

dip% = 95 × S_start ÷ S_sc

The 95 is simply 100 × sin φ. A machine locked at 0.2 power factor pushes the factor toward 98; one at 0.35 pulls it toward 94. Dropping the factor and using the plain ratio S_start ÷ S_sc predicts a marginally deeper dip, which is the conservative side to be wrong on.

Adding the utility short-circuit capacity #

The source enters in four steps:

  • Convert the primary level to MVA: S_source = √3 × 33 kV × 25 kA = 1.732 × 33 × 25 = 1429 MVA. Ask the utility whether 25 kA is a maximum or a minimum figure; the dip is worst at the minimum, so request both.
  • Get the transformer term from the nameplate: S_trf = rated kVA ÷ (%Z ÷ 100), with %Z on the transformer's own kVA base.
  • Combine the two as series impedances. Series impedances add, so short-circuit MVA combines like parallel resistances: 1/S_total = 1/S_source + 1/S_trf, and S_total always lands below either term alone.
  • If the 4.16 kV cable run to the motor is more than a short length, fold it in: X_upstream = V_LL² ÷ S_total, add the cable X and R per phase in ohms, and take the MVA at the motor terminals as V_LL² ÷ X_total.

The cost of ignoring the source is measurable, not hypothetical: the infinite-bus dip is understated by roughly S_trf ÷ S_source of its own value. And S_total is the same quantity a fault study produces — the number behind a closed delta transformer fault current calculation — so an existing fault study at the bus hands you the source impedance term directly.

Worked example: 1000 HP motor on a 33/4.16 kV transformer #

Inputs, given versus assumed:

  • Given: a 1000 HP motor at 4.16 kV; a 33/4.16 kV transformer; 25 kA available at 33 kV; no other MV motors on the secondary bus.
  • Assumed for the arithmetic, to be replaced with nameplate values: a 2500 kVA transformer at 5.75% impedance, and a locked-rotor current of 900 A at 4.16 kV. The typical cross-check for a standard NEMA motor, 6.5 kVA per horsepower, gives 1000 × 6.5 = 6.5 MVA — in agreement with the 900 A figure below. For what RLA, FLA and LRA mean on a motor datasheet, see AC motor current ratings: RLA, FLA and LRA.

If confirming any of those numbers means opening a door on energized 33 kV or 4.16 kV gear, de-energize, lock out and test for absence of voltage first: NFPA 70E, 2024 edition sets the electrical safe work practices for that task, and your site program and the authority having jurisdiction govern the details.

Then:

  1. Source MVA: 1429 MVA, from the conversion above.
  2. Transformer MVA: 2.5 MVA ÷ 0.0575 = 43.5 MVA.
  3. Combined: 1 ÷ 1429 + 1 ÷ 43.5 = 0.00070 + 0.0230 = 0.0237, so S_total = 1 ÷ 0.0237 = 42.2 MVA. The sanity check holds: 42.2 is below 43.5.
  4. Starting MVA: √3 × 4.16 kV × 900 A = 6.49 MVA, carried as 6.5 MVA.
  5. Dip: 95 × 6.5 ÷ 42.2 = 617.5 ÷ 42.2 = 14.6%, leaving 100 − 14.6 = 85.4% of rated voltage at the motor terminals.
Case Short-circuit MVA at the bus Dip Terminal voltage
Transformer only, infinite bus 43.5 MVA 14.2% 85.8%
Utility 25 kA at 33 kV 42.2 MVA 14.6% 85.4%
Utility 12.5 kA, minimum case 41.0 MVA 15.1% 84.9%

The source term moves this answer by 0.4 points, matching the 43.5 ÷ 1429 ≈ 3% rule, because the transformer dominates. It would not take a much stiffer unit to change that: a 10 MVA, 5.75% transformer passes 174 MVA alone, and the same source pulls the bus down to 155 MVA — ignoring the utility would then understate the dip by about 12%.

What the result has to satisfy #

The floor. Typical practice holds at least 80% of rated voltage at the motor terminals through a start; take that as the design floor, and the motor manufacturer's minimum starting voltage and the starter's documented dropout voltage as the binding limits. The calculation is an estimate to check against that documentation and the governing code requirements, with the authority having jurisdiction ruling where they differ.

The torque check. Motor torque scales with the square of terminal voltage: 0.854² = 0.73, so this motor works from about 73% of its speed-torque curve during the start. Confirm that stays above the load curve over the whole speed range — the check that decides high-inertia loads such as fans, crushers and compressors.

The source level. If the utility minimum is half the quoted 25 kA, the last table row applies: 15.1% dip and 84.9% at the terminals. Still above the floor, but through a 15% limit if the project specification sets one, so get the minimum figure before the design is committed.

Decision. With the assumed 2500 kVA, 5.75% transformer and a 6.5 MVA start, this start passes at 85.4% with roughly five points of margin, and the utility term is a 0.4-point refinement rather than a verdict-changer. A smaller or higher-impedance nameplate transformer means rerunning step 3, since the dip scales linearly with starting MVA and with the combined impedance. If the number fails, cut the starting MVA before resizing the transformer: a reduced-voltage start, sized the way converting a 350 kVA soft start limit to starting current shows, lowers the dip in proportion. The result also leans on the given that this bus carries the one motor.

When the dip is deep, solve the quadratic #

The linear formula drops second-order terms, so it understates the dip, and the understatement widens as the dip grows. When the estimate approaches 20% of rated voltage, solve the phasor identity exactly instead. Expanded and collected in VL, it is a quadratic:

VL² + 2·b·VL + c = 0, with b = I·(R·cos φ + X·sin φ) and c = I²·(R² + X²) − Vs²

The positive root is VL = √(b² − c) − b. Work it per phase in volts or in per-unit on the motor base, then feed the exact VL into the torque check rather than a rounded percentage.

Questions asked

How do I turn a locked-rotor kVA code letter into starting MVA?

The code letter stamped beside the rated current on many motor nameplates gives a band of locked-rotor kVA per horsepower. Multiply the band by rated horsepower to bracket the starting kVA, and divide by the square root of three times the rated voltage if you need amps. A typical standard motor lands near 6.5 kVA per horsepower, which is the cross-check the worked example uses.

When can I leave the utility level out of the calculation?

When the transformer is weak against the source. The infinite-bus answer understates the dip by roughly the transformer-to-source short-circuit MVA ratio, so with 1429 MVA available at 33 kV any transformer passing below about 140 MVA keeps that error under 10 percent. Stiffer transformers, or weaker sources, need the combination step.

Does the 33 kV primary bus feel the start too?

Yes. The same starting current flows through the source impedance, and the primary-side dip is about 95 × 6.5 ÷ 1429, or 0.4 percent, for this start. That is small, which is why one medium-voltage motor rarely registers at the utility, but it is the mechanism that couples simultaneous starts on a single system.

What if another motor is running on the same 4.16 kV bus?

The dip lands on the whole bus, not just the motor being started. Any running motor's contactor coils and undervoltage protection must ride through it, and running torque falls with the square of the terminal voltage. The worked example holds only because that bus carries this one motor.

Keep reading

  • Selection guide

    Sizing a transformer for a 200 HP across-the-line motor start

    Select a 1000 kVA transformer with nameplate impedance of 6.5% or less. The 3 kVA-per-HP rule gives 600 kVA for the 200 HP pump alone; adding 390.9 kVA of always-on load gives 990.9 kVA, so that is the screening size. The dip screen confirms it: 8.8% sag at 5.75% impedance, inside the 10% target, while 750 kVA would need 4.9% impedance to pass.

    Power distribution and transformers

  • How-to

    Estimating transformer energization voltage sag from source impedance

    Screen the dip in pu with |ΔV|pu = k × St ÷ Ssc, using k = 10–12 times transformer full-load current at about 0.1 power factor. A 50 MVA transformer on a 500 MVA short-circuit source screens at 1.0–1.2 pu, which invalidates the fixed-current method and calls for a transient study; a 5 MVA unit on the same bus screens at 0.10–0.12 pu, a usable bound.

    Power quality and harmonics

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters