Sizing the feeder breaker for three motors on one 208 V feeder

Protection: breakers, fuses and SCCR Published 6 min read

Short answer

NFPA 70, National Electrical Code, 2023 edition, Article 430.62 sizes a multiple-motor feeder breaker as the largest motor branch short-circuit device rating plus the table full-load currents of the remaining motors. For three 5 hp, 208 V three-phase motors on 45 A branch breakers that is 45 A + 33.4 A = 78.4 A, so the feeder takes an 80 A inverse-time breaker. The 2.5 × total running-current shortcut gives 101.5 A and over-sizes the feeder.

On this page
  1. What NFPA 70 430.62 requires
  2. Table current, not the 40.6 A estimate
  3. Step-by-step: sizing the feeder breaker
  4. Starting duty: will the breaker hold
  5. What moves the answer
  6. The decision
  7. Questions asked

Size the feeder at an 80 A, three-pole inverse-time (thermal-magnetic) circuit breaker, fed through #6 AWG copper conductors. That is the answer NFPA 70, the National Electrical Code, 2023 edition, gives for three 5 hp, 208 V three-phase motors on one feeder. Section 430.62 caps the feeder's short-circuit and ground-fault device at the largest branch protective device rating for any motor on the feeder plus the table full-load currents of the other motors: 45 A + 16.7 A + 16.7 A = 78.4 A, and the next standard rating is that value. The common shortcut, 2.5 times total running current (2.5 × 40.6 A = 101.5 A), points at a 100 A breaker the section does not permit. The method, the checks and what moves the number follow.

What NFPA 70 430.62 requires #

Article 430 of NFPA 70, the National Electrical Code, 2023 edition, governs motors, motor circuits and controllers. Section 430.62 sets the ceiling for the short-circuit and ground-fault device on a feeder supplying several motors: its rating or setting may be no greater than the largest rating or setting among the motors' branch-circuit short-circuit and ground-fault devices, plus the sum of the table full-load currents of the other motors supplied. It is a maximum, so a smaller device always complies if it carries the load. And it is built from the branch device rating rather than a multiplier on total current, on the logic that one motor can be accelerating while the others run at full load, and that motor's branch device already covers its inrush. Editions and local amendments differ, so confirm the requirement with the authority having jurisdiction and the equipment documentation.

Table current, not the 40.6 A estimate #

The 40.6 A behind the shortcut is a running-current estimate, not a sizing input. With its assumptions stated (0.85 power factor, 0.90 efficiency), it comes from 3 × 5 hp × 746 W/hp ÷ (√3 × 208 V × 0.85 × 0.90) = 11,190 W ÷ 275.6 = 40.6 A. Fine for a load study; not what the code counts. NEC 430.6 requires conductor and protective-device calculations to use the tables, and Table 430.250 lists 16.7 A full-load current for a 5 hp, three-phase, 208 V squirrel-cage motor, so the group's table total is 50.1 A, already above the estimate. The overload relays themselves are a separate decision, set from motor nameplate full-load current rather than the table, as covered in setting overload relays from motor nameplate full-load current.

Step-by-step: sizing the feeder breaker #

  1. Confirm the motors from their nameplates: 5 hp, three-phase, 208 V, squirrel-cage, direct-on-line starts, with the vendor supplying each branch protective device and overload. Before opening any existing enclosure to read them, de-energize, lock out and test for absence of voltage. If any motor turns out to be single-phase, everything below changes.
  2. Take the table full-load current per motor from Table 430.250, the value quoted above.
  3. Establish the largest branch device. With nothing installed yet, the code basis is Table 430.52, which allows an inverse-time circuit breaker at 250% of table FLC: 2.5 × that value = 41.75 A. That is not a standard rating, so 430.52(C)(1) Exception 1 permits the next one up, 45 A. If the vendor's devices are already in, read the actual installed rating and use that number instead.
  4. Add the other motors: 45 A + 33.4 A = 78.4 A. That is the maximum feeder device rating.
  5. Choose the device. The standard ratings around the maximum are 70 A and 80 A, and the latter is the one to set. Its interrupting rating must be at least the available fault current at the line terminals (NEC 110.9); that number does not come out of this calculation, so take it from the utility's fault data or a system study.
  6. Size the conductors under 430.24, which requires 125% of the largest motor's table FLC plus the rest: 1.25 × 16.7 A + 33.4 A = 54.3 A minimum ampacity. #6 AWG copper at 75°C, rated 65 A, meets it. A feeder device rated above a 65 A conductor is how Article 430 works: the feeder device clears faults and overload protection lives at the motors. The single-motor version of this arithmetic is covered in motor branch circuit sizing under the NEC.
  7. Check starting duty, then order: 3-pole, inverse-time, on #6 AWG copper.

Starting duty: will the breaker hold #

Staggered starts are the design case. One motor at locked rotor draws roughly six times its table FLC, about 100 A, and the two running motors add 33.4 A, so the feeder carries about 133 A, under 1.7 times the rating, for the few seconds of acceleration. A thermal-magnetic breaker's thermal element rides that out.

All three starting together draw on the order of 300 A, about 3.8 times rating, which sits below the magnetic pickup of typical 80 A frames (instantaneous trip usually lands five to ten times rating), so even a simultaneous start normally holds. Pickup bands vary by series, so overlay the actual starting envelope on the manufacturer's time-current curve; a protective device coordination study tutorial walks through that method. If your curve shows a conflict, stagger the starts or put a soft starter on one motor. Do not raise the breaker: 78.4 A is a ceiling.

What moves the answer #

Every amp of branch-device rating moves the feeder ceiling one-for-one, which is why the vendor's protection schedule matters more than any rule of thumb:

Largest branch device 430.62 calculation Feeder device to set
40 A breaker 40 A + 33.4 A = 73.4 A 80 A breaker
45 A breaker 45 A + 33.4 A = 78.4 A 80 A breaker
50 A breaker 50 A + 33.4 A = 83.4 A 90 A breaker
60 A breaker 60 A + 33.4 A = 93.4 A 100 A breaker

The 2.5 × total-current shortcut lands on 100 A, a number that matches only the last row and overshoots the other three. Two more levers exist: the motor mix itself, since a larger or smaller largest motor changes both terms, and where the feeder lands. If it terminates on a listed motor control center rather than a plain enclosure, the device rating must also stay at or below the rating of the MCC's common power bus.

The decision #

Three 5 hp, 208 V three-phase motors with vendor-provided 45 A inverse-time branch breakers: install the 80 A, three-pole inverse-time breaker at the feeder source on #6 AWG copper conductors, with an interrupting rating at least equal to the available fault current there. If the vendor's devices differ, re-run the addition with the table above. If all three must start together, verify the one curve you are buying against the combined inrush, and stagger the starts or soft-start one motor if it fails.

Questions asked

Do I need a feeder breaker at all if the vendor protects each motor?

Yes. The vendor's branch devices sit at the motor end and see nothing wrong with a fault on the feeder conductors between your source panel and their panel. Those conductors need short-circuit and ground-fault protection at their source, and 430.62 exists to size it. Leaving the feeder unprotected because each motor has a starter is the one mistake this rule prevents.

Do I use the nameplate amps or Table 430.250 amps?

Table 430.250 for this calculation. NEC 430.6 requires the table values for conductor, branch-device and feeder-device sizing because they cover the highest-current motor in a horsepower class. Nameplate full-load current is what the vendor's overload relays are set from. A 5 hp, 208 V three-phase motor can nameplate below the table value and the table value still governs here.

Why can the feeder breaker feed conductors rated 65 A?

Article 430 splits the duties. The feeder device clears short circuits and ground faults only; overload protection for the motors lives in the branch overloads, so the usual match between device rating and conductor ampacity does not apply. The ceiling comes from 430.62 and the conductor minimum from 430.24. The scheme depends on those branch overloads being installed and set, because without them the feeder conductors have no overload protection at all.

If I use an adjustable-trip breaker, what do I set?

Set the long-time pickup so the result stays at or below the 430.62 ceiling, 80 A here, because the section limits the setting, not just the frame. Keep the instantaneous pickup above the worst starting current: all three motors at locked rotor is on the order of 300 A, so a 400 A pickup, five times that rating, clears it with margin. Record the settings with the one-line.

Does the same method size feeder fuses?

Yes, the method is identical; only the branch percentage changes. Table 430.52 allows a dual-element time-delay fuse at 175% of table FLC: 1.75 × 16.7 A = 29.2 A, which goes to the next standard fuse, 30 A. The feeder fuse maximum is then 30 A + 33.4 A = 63.4 A, so a 70 A dual-element fuse. Redo the branch step with the fuse column before you buy.

Keep reading

  • Selection guide

    Sizing a three-pole breaker for a single-phase transformer

    Use the real primary current, 10 kVA x 1000 / 480 V = 20.83 A, not the 36.1 A a phantom balanced 30 kVA three-phase load gives. NFPA 70, 2023 edition, Table 450.3(B) permits 125% plus the next standard rating, so a 30 A two-pole breaker is the pick. A three-pole breaker of the same rating works only where its listing allows two-pole use, or with two poles in series on a differential-trip device.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Using a motor circuit breaker on a servo infeed

    Yes — a GV2ME-class manual motor controller is acceptable on a servo drive infeed when the drive manual lists that device class for short-circuit protection, its short-circuit rating at the panel voltage exceeds the available fault current, and its thermal dial is set to the drive's rated input current. A UL 1077 supplementary protector alone is never the branch-circuit protective device under NFPA 79 or the NEC; replace each one with a UL 489 breaker, a listed fuse, or an approved motor circuit breaker.

    Electrical safety and codes

  • How-to

    Wiring a three-pole contactor for a single-phase motor

    Run the single-phase current through two poles in series per the overload maker's diagram — supply to terminals 1 and 5, a link between 3 and 6, motor leads at 2 and 4 — and never parallel all three poles. Set the overload at 125% of the 6 A nameplate full-load current (7.5 A) when the service factor is 1.15 or higher or the temperature rise is 40 °C or less, otherwise 115% (6.9 A), per NFPA 70 (NEC) 430.32.

    Motors and motor starters