Explainer
CPU inrush current and circuit breaker selection explained
Short answer
Inrush current is the millisecond charging pulse at power-up, not a continuous load. A controller drawing 0.7 A with a 1.9 A pulse sits far below a C-characteristic breaker's 5-to-10-times magnetic trip band, so a 1 A DC-rated C-curve breaker is the right pick provided the whole branch load stays within its continuous capacity.

On this page
Inrush current is the short charging pulse a device draws in the first milliseconds after power is applied — it is not the current the device carries while running. When a compact controller's datasheet lists an input current of 0.7 A and an inrush current beside it, the inrush figure describes a pulse measured in milliseconds, and a C-characteristic breaker sized to the continuous load sees the pulse as under twice its rating, far below the 5-to-10-times band where that curve is even permitted to trip magnetically. The right selection basis is the breaker's published time-current curve, its DC rating at the branch voltage, and the summed load on the branch — not a rule of thumb like a C curve trips at three to five times its rating, which is not what the standard says.
What the two datasheet numbers mean #
Input current is the current the controller draws through its power terminals under the operating conditions the datasheet states. Read the fine print: the 0.7 A figure may be typical, maximum, or tied to a particular configuration and supply voltage. Only a maximum, or a typical figure with margin, is safe to use as your design load.
Inrush current is the transient demand at energization. Electronic equipment has input capacitance; charging it pulls a brief pulse well above the operating current, then the current falls back within milliseconds. The pulse duration and measurement definition are set by the equipment manufacturer, so treat the inrush figure as the peak of a startup event, not as a load the breaker must carry continuously. A similar distinction applies on the AC side of control gear: the transformer and motor inrush trips covered in why a motor circuit breaker trips on transformer inrush at first start have the same shape — a short pulse a properly chosen protective device must ride through.
How a C-characteristic breaker actually responds #
Miniature breaker trip characteristics are defined in IEC 60898-1. The letter marks a magnetic (instantaneous) trip band:
- B: trips magnetically at 3 to 5 times rated current.
- C: trips magnetically at 5 to 10 times rated current.
- D: trips magnetically at 10 to 20 times rated current.
A pulse at 1.9 times rated current — where the example's inrush figure lands on the proposed breaker — is inside the band where the standard requires the breaker not to trip instantaneously (the cold-state hold threshold is 1.13 times rated current for at least an hour, and conventional tripping begins at 1.45 times). Whether a pulse at 1.45 to 5 times rated current trips depends on its duration and the manufacturer's curve, which is why the datasheet curve, not the letter alone, is the selection document. If a startup pulse is long or repeated, the D characteristic gives more margin, which is the subject of why a D-curve breaker trips on equipment start inrush.
The thermal element still governs your continuous load: at 1.13 times rated current the breaker must hold indefinitely from cold, and at 1.45 times it must trip within an hour. Size the rating so the summed continuous branch load sits comfortably below those thresholds.
Worked example: a DC control branch feeding one controller #
Inputs:
- Branch voltage: 24 V DC, from the control-power supply feeding the controller power terminals.
- Controller input current: 0.7 A, the datasheet operating figure.
- Controller inrush current: 1.9 A, the datasheet energization pulse, duration stated only as milliseconds.
- Proposed breaker: 1 A frame, C characteristic, miniature breaker.
Rule: compare each current against the breaker's rated current and against the IEC 60898-1 C-characteristic bands.
Arithmetic:
- Inrush ratio: 1.9 A ÷ 1 A = 1.9 times rated current.
- C-curve magnetic band: 5 to 10 times the breaker rating, so 5 A to 10 A on this frame. The pulse is below 5 A, so no instantaneous trip is permitted.
- Continuous load ratio: 0.7 ÷ the breaker rating = 0.7, or 70% of the rating — below the 80% continuous-loading practice of NFPA 70, the National Electrical Code (2023 edition), so the thermal element holds indefinitely at 1.13 times the rating, or 1.13 A, and above.
- Thermal trip check: 1.45 times the rating = 1.45 A. The inrush pulse exceeds this for milliseconds only; the one-hour thermal response does not register such a pulse, as the manufacturer's curve confirms.
Result: the proposed breaker rides through the pulse and carries the load.
Decision: use the proposed C-curve breaker, provided it is rated for DC service at the branch voltage in the pole arrangement its manufacturer specifies, and provided nothing else shares the branch. If a second device adds, say, another 0.4 A continuous and its own pulse, the summed continuous demand reaches 1.1 A — above the rating — and the branch moves to a 2 A C-curve breaker with conductors protected accordingly. The breaker also needs an interrupting rating that matches the available fault current at the panel; the panel-level implications are covered in what sets a control panel's short-circuit current rating.
Check the DC rating before trusting the curve #
IEC 60898-1 and the characteristic letters are written around AC service. A breaker applied on a 24 V DC control branch must carry an explicit DC voltage rating, and the manufacturer states which poles must be series-connected to reach it, because a DC arc does not pass through a current zero the way an AC arc does. The characteristic letter does not establish DC suitability — only the breaker's own datasheet does. Also confirm the breaking capacity against the prospective fault current: industrial miniature breakers are commonly offered in ranges around 6 kA and 10 kA, and the 10 kA frame is the usual choice on industrial control panels.
Check the branch, not just the controller #
The breaker responds to everything on the branch. If the controller shares a feed with an HMI, an I/O block or a lighting circuit, sum every continuous load and account for coincident energization pulses before selecting the rating. Measure with a current probe and a scope or power-quality recorder — a handheld meter cannot resolve a millisecond pulse — and confirm the supply's output stays within the controller's permitted input-voltage range during startup. If a trip follows sustained running rather than power-up, the cause is continuous overload or a derating issue, not inrush, and increasing the breaker rating to silence it is acceptable only if the conductors remain protected.
The decision, restated #
For a controller listing 0.7 A input and a millisecond inrush pulse on a 24 V DC branch: the pulse is 1.9 times the breaker's rating, below the 5-times floor of the C-characteristic magnetic band and momentary against the thermal response, so the proposed DC-rated C-curve breaker with the manufacturer's pole arrangement is correct when it is the only load. Move to the next rating up only when summed continuous branch load, additional energization pulses, or the conductor protection check forces it — and then verify the conductors are protected at the new rating.
Questions asked
Is inrush current drawn only at power-up?
Yes. It is the transient pulse that charges the input capacitance when voltage is first applied, lasting milliseconds, after which the device settles to its normal input current. The datasheet lists it separately from the input current precisely because it exists only during energization. It says nothing about the load the breaker carries in continuous operation.
Why not just use a 2 A breaker to be safe?
Oversizing weakens conductor protection: a 2 A breaker carries twice the current before its thermal element responds, so the wire it protects must also be rated for that. On the case here, 1.9 A is only 1.9 times a 1 A rating, well inside the hold-in region of a C curve, so the larger rating buys nothing. Step up only when the summed branch load or the curve check demands it.
Does the C-characteristic mean the same thing on DC?
The current multiples come from IEC 60898-1, which is written for AC mains miniature breakers. On a 24 V DC control branch, the curve multiples still describe the trip band, but the breaker must be individually rated for DC at that voltage with the pole arrangement the manufacturer specifies, because extinguishing a DC arc is harder than an AC one. Read the DC rating on the breaker's own datasheet, not from the characteristic letter.
How do I measure the actual inrush pulse?
Use a current probe with an oscilloscope or a power-quality recorder, because a handheld meter's display update is too slow to catch a pulse lasting milliseconds. Capture current at the moment the branch is energized, then compare the peak and duration with the datasheet definition and the breaker's time-current curve. De-energize, lock out and verify absence of voltage before opening any terminal compartment.