Troubleshooting
Feeding a 240 V control transformer from a high-leg delta
Short answer
Yes. A control transformer primary responds only to the voltage across its two terminals, and on a high-leg delta every pair of lines delivers the full line-to-line voltage, so a 240 V primary on a 120 V leg plus the high leg is correctly fed. The 60 V per secondary lead to ground is a reference artifact, and the dropout is found by measuring across the contactor coil while it tries to hold.
On this page
- What the primary actually receives
- Why each secondary lead reads 60 V to ground
- Where the high leg belongs, in the Code and at the machine
- Moves that will not fix it
- The measurement order that settles it
- The coil check that finds the dropout
- Worked example: a 240/120 V transformer fed from a conventional leg and the high leg
- Questions asked
Yes: a 240/120 V control transformer fed from one conventional leg plus the high leg is wired correctly, and that connection is not why your contactor drops out. The primary responds only to the voltage between its two terminals, and on a high-leg delta every pair of lines delivers the same line-to-line voltage. What misleads is the meter reference: about 60 V from each secondary lead to ground is an artifact of an isolated secondary, not half voltage. The dropout is found with two measurements — across the primary, then directly across the contactor coil while it tries to hold.
What the primary actually receives #
A transformer primary responds to the voltage between its two terminals, as phasors — not to what each conductor sits at relative to ground. So your two primary conductors, one at about half the line-to-line voltage to ground and one at about 230 V, put neither their sum (about 350 V) nor their arithmetic difference (about 110 V) across the winding. The lines are 120 electrical degrees apart; their vector difference is the line-to-line voltage, and that is the only number the winding sees.
A high-leg delta — center-tap delta, red-leg delta — is a three-phase delta with the midpoint of one winding grounded, so the service can also feed lighting and receptacles from that centertap. All three line-to-line pairs stay nominally equal; only the voltages to the centertap differ:
| Supply | Conventional legs to the centertap | High leg to the centertap | Every line-to-line pair |
|---|---|---|---|
| 240 V high-leg delta | 120 V | ≈ 208 V | 240 V |
| 230 V high-leg delta | 115 V | ≈ 200 V | 230 V |
The high leg's voltage to the centertap follows V_high = (√3 / 2) × V_line-to-line — 0.866 times the line-to-line voltage.
The rule people half-remember is real but narrower than the way it gets repeated: never connect a line-to-neutral load to the high leg, because it would receive about 208 V where it expects the centertap's half. A control transformer primary rated for the line-to-line voltage is a line-to-line load, not a line-to-neutral one, and a conventional leg plus the high leg feeds it exactly as well as the two conventional legs would. The same geometry is what makes reverse feeding a step-down transformer on a high leg delta a separate decision on this supply.
What the high leg does change is the voltage to ground on the primary conductor tied to it — normal for this supply, and well inside the rating of ordinary 600 V machine-tool wire. That is a reason to meter lead-to-lead, not a reason to re-feed the transformer.
Why each secondary lead reads 60 V to ground #
Full voltage lead-to-lead with about half of it showing from each lead to ground is the signature of an isolated secondary: ground is a reference for the meter, not a conductor in the control circuit, and a high-impedance meter lets each lead settle near the winding's midpoint. The coil is paid in lead-to-lead volts, and yours read exactly the rated value, so the transformer is doing its job.
The reading itself is normal, as covered in why a control transformer secondary shows voltage to ground, and whether this machine's secondary is meant to be bonded or left floating is decided by its schematic. Do not add a bond just to quiet the meter.
Where the high leg belongs, in the Code and at the machine #
NFPA 70, the National Electrical Code, 2023 edition, covers panelboard and switchboard phase arrangement in 408.3, and that is the section that requires the high leg to be terminated on the B phase; the Code's other high-leg provisions cover its identification, which is why panels mark it orange. Confirm how your jurisdiction applies that with the authority having jurisdiction and the machine documentation.
Inside a machine tool the letters follow the builder's schematic, and after a plug change the lines may land on different letters than they did before. That costs the transformer nothing — every pair is line-to-line — but it reverses motor rotation, so check rotation before anything else after a plug change.
One rule never bends: the equipment ground is not a control return. It is a protective conductor, and the coil's return must be a conductor run from the transformer secondary.
Moves that will not fix it #
- Re-feeding the primary from the two conventional legs. The two feeds are electrically identical; the dropout stays. Restore that pair only if the machine schematic shows it, and expect no change in the symptom.
- Replacing the transformer because each secondary lead shows voltage to ground. That reading is normal for an isolated secondary, not a bad winding.
- Tying the control return to the equipment ground so the circuit works. It is not permitted, and it hides the open return you are hunting.
- Holding the contactor closed or bridging the seal-in contact. That bypasses the emergency-stop and overload chain the dropout may be reporting.
The measurement order that settles it #
- De-energize the machine, lock it out and test for absence of voltage at the incoming terminals before opening the cabinet. The energized measurements that follow are for qualified personnel working under the site's electrical safety procedure — the shock and arc-flash assessment NFPA 70E, 2024 edition, covers — with a true-RMS multimeter rated for the supply's measurement category and voltage.
- Read the transformer nameplate and terminal diagram, and confirm which primary terminals are in use, so the winding rated for the line-to-line voltage is the one actually connected.
- Measure L1–L2, L2–L3 and L3–L1 at the machine terminals. All three should match. One dead or low pair puts the fault upstream — replacement plug, cord, receptacle or supply protection — and nothing downstream matters until that is fixed.
- Measure directly across the two connected primary terminals. Expect the same value the line pairs showed; the high leg changes nothing.
- Measure across the secondary terminals before anything tries to pull in: the nameplate ratio times the primary voltage, half the primary on this unit.
- If you need to know which line is the high leg, meter each line to the bonded frame. The leg that reads distinctly higher than the other two is it. Ground readings identify supply legs; they never measure an isolated secondary.
The coil check that finds the dropout #
The coil responds to the voltage between its two terminals — the red wire and its return conductor, never the red wire to the cabinet, which only reproduces the reference artifact. A contactor that pulls in but will not stay is the signature of a holding path that opens at pull-in: the seal-in auxiliary contact in parallel with the start button, or something in series — the emergency-stop chain, an overload contact, an interlock.
Meter across the coil, press start and watch what happens the instant it pulls in:
| Reading across the coil at pull-in | What it means | Next check |
|---|---|---|
| Collapses toward 0 V | The control path opens on pickup | The seal-in auxiliary contact first, then the e-stop chain and the overload contacts |
| Holds at the secondary voltage and it still drops | The supply is exonerated | The coil's voltage tap, then the contactor itself |
| Dips and recovers | Supply impedance under the contactor's inrush | Secondary terminations, then whether the transformer is sized for that inrush |
A coil that holds its rated voltage across its terminals and still will not stay in points at the contactor — the case walked through in why a motor starter coil has voltage but won't pull in.
Worked example: a 240/120 V transformer fed from a conventional leg and the high leg #
The inputs are your own readings and nameplate: a supply described as a 230 V three-phase high-leg delta, its legs reading about 120 V, 120 V and about 230 V to ground; a transformer nameplated 240/120 V with its primary on one conventional leg and the high leg; a secondary reading its rated lead-to-lead value with about 60 V per lead to ground; and contactor coils rated 110 V. The high-leg relation comes from the supply geometry; the B-phase placement from NFPA 70.
The rules, in words: the high leg stands (√3 / 2) times the line-to-line voltage above the grounded centertap; any two lines deliver the line-to-line voltage to whatever is connected across them; and the secondary delivers its nameplate ratio times the primary.
The arithmetic:
- High leg to the centertap: 0.866 × 230 V = 199 V, about 200 V on the 230 V class; 0.866 × 240 V = 208 V on the 240 V class. Your high-leg reading to ground runs above the nominal value because the reference is the bonded machine frame, not the centertap itself — the leg that reads distinctly higher is the high leg either way.
- Primary voltage: the two primary conductors sit 120 electrical degrees apart, so their vector difference is the line-to-line value — the full line-to-line voltage lands across the winding, not the 350 V sum or the 110 V difference of the ground readings.
- Secondary, on the 240 V class your equal leg readings point to: the nameplate ratio halves the primary, 240 V × 0.5 = 120 V — exactly the lead-to-lead value measured.
Result: the high-leg pair delivers the full line-to-line voltage, the secondary holds its nameplate ratio, and the transformer is healthy. The 60 V to ground on each secondary lead is the isolated-secondary artifact, not a fault, and the primary connection is correct as wired, cross-checked against the nameplate and the machine schematic.
Decision: leave the primary on the leg pair it has; moving it buys nothing. Meter across the 110 V coil and press start — a reading that collapses toward 0 V the instant the contactor pulls in convicts the holding path: go to the seal-in auxiliary contact first, then the emergency-stop chain and the overload contacts. A reading that holds at the secondary voltage convicts the coil or its tap, not the supply.
Questions asked
Will swapping two lines at the new plug change the control voltage?
No. Every line pair on a high-leg delta delivers the same line-to-line voltage, so the transformer primary, the secondary and the coil supply are all unchanged whatever order the plug lands in. What a swap does change is phase sequence: motors run backwards and a phase-monitor relay may refuse to let the machine start. Check rotation before anything else after a plug change, and treat the old plug's L1, L2, L3 labels as history, not wiring information.
What should each line read to ground on this supply?
With the centertap grounded at the service and the machine frame bonded to it, the two conventional legs read about half the line-to-line voltage to ground and the high leg reads about 0.866 of it — roughly 208 V on a 240 V service. A high-leg reading well above that value means your reference is not sitting exactly at the centertap. Identify the high leg as the one that reads distinctly higher, then settle the actual line-to-line voltage with pair-to-pair measurements, which is the number the equipment nameplate is judged against.
The coil has full voltage across it and the contactor still drops — what now?
That reading exonerates the transformer, the supply and the control wiring. Check that the coil is on the tap that matches its supply, since many control contactors have selectable voltage taps, then look at the contactor itself: a cracked shading coil or a sticky armature will drop an alternating-current contactor that has every volt it asked for. Chatter points at the armature face; a clean drop with voltage present points at the tap.
Can other single-phase control loads sit on the high leg?
Yes, provided they are rated for the line-to-line voltage. Any load connected across two lines — control power transformers, solenoid coils, heaters — sees the line-to-line voltage no matter which pair it uses. What must not hang between the high leg and the centertap is a load rated for half the line-to-line voltage, such as a lighting or receptacle circuit, because it would receive the high-leg voltage instead. Check the nameplate rating, not which leg is high.