Troubleshooting
Why a motor starter coil has voltage but won't pull in
Short answer
Voltage across A1 and A2 with no current flowing proves only that the wiring is intact, not that the coil can pick up. Log the coil voltage during the failed closing attempt: most of these faults are a supply or wiring sag below the coil's pickup window, or a latched overload state that the reset button does not clear. Replace the starter only when the voltage stays inside its window and the unit still refuses to close.
On this page
Your meter shows full voltage from A1 to A2, the contactor sits there, and the reset button changes nothing, so the starter must be bad. Usually it is not. With no current flowing there is no voltage drop, so a static reading proves only that copper reaches the terminals, never that the coil can draw making current. When a starter will not close on command, work in this order: log the voltage across A1 and A2 during the failed attempt, prove the reset chain and permissives, and condemn the unit only when both are clean. In the field these faults land, in that same order of likelihood, on a supply or wiring sag under load, a latched protective state, and, a distant last, a failed starter. Here is how to tell them apart in one visit.
What a good reading at A1 and A2 actually proves #
With the coil idle, no current flows through the control wiring, so nothing drops voltage and the meter returns the supply value. That is the whole content of the reading. Four traps make it worse:
- No load, no drop. A resistance that steals 5 V at 1 A steals nothing at 0 A. The reading only means something while the coil is drawing making current.
- Ghost voltage. A typical digital multimeter's 10 MΩ input, reading through the off-state leakage of a PLC's electronic output, displays volts the circuit cannot deliver. Confirm with a test lamp or a low-impedance tester: leakage lights nothing, a real supply does.
- The wrong two points. Probing A1 to ground with the A2 return open still shows a live conductor. Measure across A1 and A2, coil connected.
- Too slow. A supply that folds back for a fraction of a second during the close looks perfect on a meter updating a few times a second. Use min/max capture at minimum, and a logging meter when the fault is intermittent.
The decision: every voltage claim in this diagnosis comes from across A1 and A2, with current flowing.
The voltage window a coil needs to close #
IEC 60947-4-1 (2018 edition) covers low-voltage contactors and motor starters and requires the electromagnet to close reliably within a control-voltage band the manufacturer declares; the generic operating limits behind it sit in IEC 60947-1 (2020 edition). On industrial contactor data sheets that band runs from 85 to 110 percent of the rated coil voltage Us. A 120 V AC coil must therefore close anywhere between 102 V and 132 V; a 24 V coil between 20.4 V and 26.4 V. The band printed on your installed coil's data sheet is the number that governs.
Closing is the hardest work the coil does: it must build enough force, across a full air gap and against the return spring, to move the armature. Making current therefore runs well above sealed current, several times higher on AC designs, because the coil's impedance only rises once the armature seats. Holding takes a fraction of that effort; a typical contactor drops out only somewhere below 75 percent of Us. That asymmetry is the trap: a supply or wiring path too weak to pick the contactor up from open can hold it closed indefinitely once something else closes it. And never leave a humming, unseated AC coil energized while you think: it keeps drawing making current and overheats. Remove the command.
Log the voltage during the failed attempt #
One safety note, used once. Reaching A1 and A2 means opening an energized enclosure, so de-energize, lock out and test for absence of voltage before you open it. The logging itself is a live measurement: run it under your site's electrical safety program and PPE rules, confirmed with your safety office and the equipment documentation, because NFPA 70E (2024 edition), which covers electrical safety in the workplace, governs how that work is done on your site. Use an instrument rated for the measurement category of the point.
- Record before you reset. Photograph the unit's indications and note the machine state at the failure. Resetting first erases the evidence, the same discipline as diagnosing a soft starter fault or alarm before resetting it. Take the complete order number off the label (units like 3RA6120-1BP32 and 3RA6120-1CP32) so you work from the right documentation.
- Sketch the series chain that feeds A1: the protective NC contact (95/96), the E-stop and guard chain, the PLC output or interposing relay, terminal blocks, the supply.
- Capture three events on the same channel across A1 and A2: at rest, a failed closing command, and a successful command on an identical healthy starter under comparable machine conditions. Log the supply output on a second channel at the same time.
- Read the minimum voltage at A1 to A2 during the failed attempt and compare it with the pickup minimum declared on the coil's data sheet.
Three traces, three decisions #
| What the log shows during the failed command | Where the fault is | The decision |
|---|---|---|
| Supply output and A1 to A2 fall together below the coil's window | The source: capacity, or simultaneous pull-in loads on a current-limited supply | Repair or upsize the supply, or sequence the close commands; the starter is fine |
| Supply output holds while A1 to A2 collapses | Resistance between supply and coil: undersized run, oxidized terminal, loose termination | Measure the drop across each segment under load; reterminate or upsize; the starter is fine |
| A1 to A2 stays inside the window for the whole command | The unit or its logic: latched state, missing permissive, or internal failure | Follow the reset path below; replace only when the indications show ready and it still will not close |
When several starters can close together, making currents add: size the control supply for the sum of the simultaneous making currents plus the sealed load, not for the sealed load alone.
Worked example: 24 V at rest, 19 V at the coil #
Hypothetical inputs, typical of a real panel; take yours from the coil's data sheet and a resistance measurement. A 24 V DC control supply. A coil with a declared 0.85 to 1.1 times Us window, so a pickup minimum of 0.85 x 24 = 20.4 V. Making current 0.9 A, sealed current 0.2 A. A control run of 50 m each way in 0.75 mm² copper. One oxidized terminal pair measuring 3.0 ohm.
Loop resistance of the run, with copper at about 0.018 ohm·mm²/m: R = 0.018 x (2 x 50) / 0.75 = 2.4 ohm. Add the bad joint: 2.4 + 3.0 = 5.4 ohm.
- At rest, 0 A x 5.4 ohm = 0 V dropped, and the meter reads 24.0 V at A1 to A2. Voltage is good.
- At the closing command the coil draws 0.9 A and the path drops 0.9 x 5.4 = 4.9 V. The coil sees 24.0 - 4.9 = 19.1 V, under the 20.4 V minimum. The contactor does not close, and that is correct behavior for a healthy coil.
- Once closed it would draw 0.2 A, drop 1.1 V and hold at 22.9 V, which is why the starter beside it, on a shorter run, starts every time.
- After reterminating the joint: 0.9 x 2.4 = 2.2 V dropped, and the coil sees 21.8 V, inside the window. It closes.
Decision: the starter was never faulty. Three ohms of oxide was.
Latched states and the reset chain #
The Siemens SIRIUS 3RA6 packs a circuit breaker, a contactor and a solid-state overload relay in one unit. After a trip, closing is blocked until the documented reset happens, and the 3RA6 manual documents that reset as disconnecting the control supply from A1/A2, done in the standard wiring by the NC overload signaling contact 95/96 in the coil circuit. Read that carefully: a reset attempt that never actually removes power from A1 and A2 does not meet the documented condition. Log A1 to A2 through the reset; if the voltage never falls to zero, the unit was never reset, only poked. How that NC contact belongs in the coil circuit is covered in wiring overload relay contacts to the coil and the PLC.
The same logic applies to every series permissive, any condition that must be true before the command counts: the E-stop chain, guard interlocks, a safety relay's outputs, a PLC handshake. One open element and the coil circuit is dead no matter what the pushbutton does, and an electronic output's leakage can still paint a ghost voltage on a high-impedance meter, so confirm with the test lamp.
This explains the field pattern you may be living in. Swapping the unit removes control power from A1 and A2 and reseats every terminal. On a starter whose documented reset is removing the A1/A2 supply, the replacement may work because the swap cleared the latch or disturbed the bad joint, not because the old unit failed. That is why the log comes first.
The decision for each case #
- A1 to A2 falls below the coil's declared pickup minimum during the command: supply or wiring fault, and the starter is almost certainly good. Fix the path, then re-log to prove it.
- The indications show a trip, or A1 to A2 never reaches 0 V during the reset attempt: satisfy the documented reset, which on the 3RA6 means removing and restoring the control supply at A1/A2, then correct whatever caused the trip.
- A1 to A2 holds inside the window for the full command, the indications show ready, the permissives are proven, and it still will not close: internal failure. Replace the unit, and keep the failed one with your log for the supplier.
- The coil hums unseated: remove the command before anything else, because an AC coil held that way destroys itself.
And if your starter closes fine but drops out mid-run, you are on the other fault: random dropouts on electronic coil motor starters.
Questions asked
The same starter closes cold but not after the panel has run for hours. Why?
Copper's resistance climbs about 0.39 percent per degree C. A coil at 100 °C has roughly 31 percent more resistance than at 20 °C, so at the same terminal voltage a DC coil carries about 24 percent less current. A voltage that cleared the pickup minimum on a cold morning misses it hot. Note the panel temperature beside each log entry; the fix is still margin in the control path, not a new starter.
A new starter fixed it. Was the old one actually faulty?
Not proven. The swap removes and restores control power at A1 and A2, which on the SIRIUS 3RA6 is itself a documented reset, and reseating the terminals can clear a high-resistance joint. Bench-test the removed unit with a known-good supply at its rated coil voltage and follow the documented reset sequence before you scrap it, and keep the event log with it either way.
How do I size a control supply when several contactors close at once?
Making currents add. Four coils like the 0.9 A example draw 3.6 A for the closing instant, far above their 0.8 A combined sealed draw. Add every other running load, then choose a supply rated above that total, or sequence the commands so the makes never overlap. A supply that hits current limit during a simultaneous close drags every coil on the bus below its pickup minimum at once.
The coil hums loudly but never closes. Is that the same fault?
Often yes. The hum means current is flowing, so first check whether the voltage from A1 to A2 collapses under that load, the sag fault from the worked example. If the voltage holds inside the declared window while it hums, the armature is mechanically stuck or dirty and the unit comes out. Either way, remove the command first: an AC coil held unseated draws making current continuously and burns out.