Troubleshooting
Fixing a soft starter phase loss fault after a voltage change
Short answer
Set the soft starter's mains voltage parameter to 400 V and its motor rated current to the pump's 400 V nameplate value. The phase-loss monitor compares each phase with the programmed reference; at 400 V on a 690 V setting every phase reads about 42% low, past the documented 15% drop threshold, so the starter trips loss of phase even with all phases present.
On this page
- Why does loss of phase L1 trip when all three phases are present?
- Where do you change the mains voltage setting?
- Why does a bigger motor run longer before the trip?
- Why didn't disabling the protections stop it?
- Can a 690 V starter run a 400 V pump at all?
- What if the fault stays after the settings are corrected?
- How do you confirm the fix before the pump goes in?
- Questions asked
Set the starter's mains voltage parameter to the new supply voltage and its motor rated current to the pump's nameplate full-load current at that voltage — that is the whole fix. The phase-loss monitor on this series compares each phase with the voltage it has been programmed to expect, and the documented trip point is a drop of more than 15% from the permissible rated operational voltage. With the old fan-installation reference still programmed, every phase on the new supply reads 42% below it, so the starter reports loss of phase L1 with all three phases healthy. The values here are for the Siemens SIRIUS 3RW44 series; read them against the operating instructions for your unit before changing anything.
Why does loss of phase L1 trip when all three phases are present? #
Because the phase-loss monitor does not test the supply in absolute terms: it tests each phase against the programmed mains voltage, and the new supply on the old reference is a 42% shortfall — nearly three times the documented 15% drop that triggers the trip.
The 3RW44 operating instructions describe this fault as phase L1 missing, dropping out or failing while the motor is running, and the remedy they give is to restore the phase or the voltage dip. The detection behind that wording is a voltage drop greater than 15% in the permissible rated operational voltage, and the reference for that percentage is the mains voltage the device has been told to expect. Run the arithmetic on the redeployment:
- 690 V − 400 V = 290 V
- 290 V ÷ 690 V = 0.42, so every phase sits 42% below reference, all the time
A genuinely lost phase is one phase low. This condition is three phases low by the same amount, and the monitor cannot tell the difference because all it sees is the percentage. Which phase is named first depends on evaluation order and on small imbalances between phases; the reference error itself is common to all three. Read the stored fault record before acting on the displayed text — diagnosing a soft starter fault or alarm before resetting it keeps the sequence that shows which event came first.
Where do you change the mains voltage setting? #
In the device data group on the starter's built-in operator panel: the line voltage entry goes from the old fan-installation value to the new supply value, and the motor rated current entry in the same group goes to the full-load current of the motor actually connected.
With no start command active, enter the parameter menu from the panel and page to the device and motor data; both settings live in that group and are stored by the routine the operating instructions describe. The same data is reachable through the manufacturer's commissioning software when you configure away from the door. Do not carry parameter numbers over from another series or firmware revision — work from the parameter list for your unit.
| Setting | Left over from the fan | Correct for the pump |
|---|---|---|
| Mains (line) voltage | Fan installation value | New supply value |
| Motor rated current | Fan motor's full-load current at the old voltage | Nameplate full-load current of the connected motor |
| Current limit and ramp | Tuned for the fan | Re-set for the pump before it runs |
During the test ladder, enter the nameplate current of whichever motor is on the output at the time, then put in the pump's value before the pump is connected, so the electronic overload always matches the machine that is actually turning.
Why does a bigger motor run longer before the trip? #
Because the monitor weighs phase current alongside voltage, and a larger motor keeps real current in all three lines deeper into the ramp, which holds off the confirmation that a phase is missing — an actually open phase would trip small and large motors identically.
That symptom ladder — same fault, later trip, bigger motor — is the clue that separates a monitoring-reference problem from a power-circuit problem. Estimate the currents the starter saw at the new voltage with I = P ÷ (√3 × U × PF × η), assuming power factor 0.85 and efficiency 0.90:
- 5.5 kW: 5,500 W ÷ (1.732 × 400 V × 0.85 × 0.90) = 5,500 ÷ 530 ≈ 10 A
- 15 kW: 15,000 W ÷ 530 ≈ 28 A
- 30 kW: 30,000 W ÷ 530 ≈ 57 A
About a fivefold current increase from the smallest to the largest test motor, with the trip retreating further into the ramp at each step. A monitor that confirms a live phase by current argues longer against a wrong voltage reference when the current is real. A blown fuse or an open pole gives the same early trip at any motor size. These currents are estimates; the nameplate values govern.
Why didn't disabling the protections stop it? #
Because the functions you switched off are the configurable ones — overload, thermistor, underload — while phase-loss detection on this series is fixed device monitoring with no parameter that turns it off, which is why every disable left the trip exactly where it was.
That is by design, not a fault. The correct move is to correct the reference the monitor compares against, not to fight the monitor. Leave the phase-loss function alone even where a series offers adjustment: a submersible pump that single-phases while running destroys its winding long before anyone notices, and the function you cannot disable is the one covering that failure mode.
Can a 690 V starter run a 400 V pump at all? #
Yes — the main circuit of this version spans 200 V to 690 V AC, and the deciding limit is frame current: 250 A for the 3RW4453 frame against roughly 208 A of full-load current for a 110 kW pump at the new voltage, about 83% of rating.
Worked example, assumptions on the table:
I = P ÷ (√3 × U × PF × η) I = 110,000 W ÷ 530 ≈ 208 A
Power factor 0.85 and efficiency 0.90 are assumptions; the pump's nameplate full-load current is the value that governs the setting, and the result is an estimate to check against the equipment documentation. The catalog lists this frame at 132 kW for duty at the lower voltage, so the continuous fit is comfortable, but the starting duty — starts per hour, current limit, ramp time — still has to be checked against the sizing data for the frame, the same discipline as matching a soft starter current range to its power structure.
Two checks travel with the voltage change. The control supply is independent of the main circuit: on the BC control-voltage variant it accepts 110–230 V AC/DC at the control terminals, and the supply move does not touch it. And if the pump motor carries a dual-voltage nameplate, wire the connection the nameplate assigns to the new supply and use that connection's current, because the same shaft power draws 690 ÷ 400 = 1.73 times the high-voltage figure. Running the high-voltage connection straight on the lower supply gives a slow, high-slip motor — a different fault that often shares this panel.
What if the fault stays after the settings are corrected? #
Then go after a real defect on the line side or inside the starter — a fuse, a loose termination, a weak contactor pole or a thyristor that is not firing — because with the corrected setting programmed, a persistent trip means that phase genuinely reads low under load.
Lock out, disconnect and prove absence of voltage before opening the starter or any terminal cover: NFPA 70E, 2024 edition, sets the conditions for de-energized work and the requirements for any energized measurement, and your site program, the authority having jurisdiction and the equipment documentation govern how these checks are done.
- Supply: all three phase-to-phase pairs at the starter input should read within ±10% of the new nominal.
- Fuses and disconnect: a fuse holder or pole with high resistance reads full voltage unloaded and collapses under current, so judge it loaded, inside the permitted procedure.
- Terminations: with the circuit locked out, check lug torque on line and load sides — heat marks on one phase mark the resistance.
- Power structure: an open thyristor in the affected phase of the anti-parallel pair shows up as phase loss under load only, matching the load-dependent timing; use the device diagnostics in the operating instructions before condemning the semiconductor.
- Rotation: confirm the bus rotation with a phase-sequence meter and make sure it matches the starter's phase-sequence setting.
The supply-side half of this list is covered in troubleshooting a line side fault on a soft starter.
How do you confirm the fix before the pump goes in? #
Run the same motor ladder again — 5.5 kW, 15 kW, 30 kW, then the pump — and with both settings corrected each step should accelerate through its full ramp, transfer to bypass and hold with no trip and near-equal line currents.
- Enter the connected test motor's nameplate full-load current before each run.
- Watch all three line currents through the ramp with a true-RMS clamp meter built for chopped waveforms — measuring VFD and soft starter current with the right meter explains why the output side punishes an averaging meter.
- Confirm the ramp completes and the internal bypass takes over without a fault.
- Before the pump: enter its nameplate current at the new voltage, set current limit and ramp for the pump, and set the electronic overload to the same nameplate value — the rule behind setting overload relays from motor nameplate full-load current applies unchanged to the starter's own overload function.
- On the first pump start, compare the three currents at full speed: a steady-state spread wider than about 5% points at supply imbalance or the device, not at the settings.
Questions asked
Is the starter damaged by running on 400 V or by the repeated trips?
No damage comes from the lower supply itself: the main circuit of this version is specified from 200 V to 690 V AC, so 400 V sits inside the range. Repeated trip-and-restart cycles are different. Each attempt pushes starting-duty current through the semiconductors, so stop cycling the fault and correct the voltage setting.
Can you test the starter with no motor connected?
A no-load run proves little. The monitor needs phase current to confirm a live phase, so an output with nothing on it can trip phase loss on its own. Bench-test with the smallest motor available and that motor's nameplate current entered, which is exactly how this fault was chased down.
Does the 15% phase-loss threshold apply to other soft starter series?
The number is series-specific: it comes from the 3RW44 documentation, and other starters set their own thresholds and reference rules. The mechanism is common, because thresholds scale with the programmed mains voltage, so the same wrong-setting trip can appear on any starter after a voltage change, with a different percentage behind it.
How do you clear the fault after changing the settings?
Clear it from the operator panel, or cycle the control supply if the starter latched, once the cause is fixed. Reset only after reading the stored fault record: if the trip returns, the history is what tells you whether the reference, the supply or the power structure moved.