Troubleshooting
Why a control transformer secondary shows voltage to ground
Short answer
The 42 V that climbs to 76 V as loads start and jumps to 131 V on the start button is capacitive coupling through a floating control transformer secondary, read by a 10 MΩ meter — not coil current. Meter across the coil and across X2-XF: about 0 V across the coil stopped and a steady nominal voltage across X2-XF means the circuit is healthy. Then the schematic decides whether X2's designed bond is open or the secondary runs floating.
On this page
- Why does a coil lead read 42 V to ground when the motor is stopped?
- Why does the to-ground reading climb from 42 V to 76 V as other loads start?
- Why does the reading jump to 131 V the moment the start button is pressed?
- How do you prove ghost voltage and not a live coil?
- Example: what does a 10 MΩ meter read on a floating 120 V secondary at 60 Hz?
- Should the control transformer secondary be bonded to ground?
- What fixes each reading for good?
- Questions asked
A stopped coil lead that reads 42 V to ground, climbs toward 76 V as other loads start, and jumps to 131 V when you press the start button is showing one signature, not three faults: the control transformer secondary has no working bond to earth, and the meter is displaying the winding's capacitive coupling instead of coil current. The machine builds its own control pair — X2 and XF at 120 V from a 208 V three-phase feed — and the incoming grounding conductor is a protective path, not the control return. Two differential measurements settle whether the circuit is healthy, and the schematic decides the repair. This article explains what each reading means, works the arithmetic behind all three, and ends with the fix for each case.
Why does a coil lead read 42 V to ground when the motor is stopped? #
A stopped lead reading 42 V to ground is ghost voltage: the secondary has no bond to earth, so the meter's 10 MΩ input is the highest-resistance path left, and it displays the winding's stray coupling instead of coil current.
The winding is live regardless — X2 to XF carries the full secondary voltage every second the machine is connected — but neither conductor is tied to the enclosure, so neither has a defined potential to earth. The primary couples to the secondary through stray winding capacitance, and the meter, referenced to earth through its grounding lead, completes that weak loop and displays whatever share the divider gives it. Because the loop is capacitive, the voltage arrives with almost no current behind it. The stop contact is open, so no current can flow through the control path, and microamps cannot pull an armature in anyway. Carry that combination through the rest of the checks: a real number on the display, and electrically nothing at the coil.
Why does the to-ground reading climb from 42 V to 76 V as other loads start? #
The reading moves because the measurement changes: every device that starts puts snubber and pilot-light capacitance in parallel with the stray coupling, so the meter claims a larger share of the coupled voltage — the climb from 42 V to 76 V is a re-balanced divider, not rising coil current.
Every starting device adds paths into that network: snubber capacitors across its contactor contacts, indicator and coil capacitance, suppression components on its loads. In parallel with the stray winding coupling, they lower the coupling impedance, and the meter reads more of the coupled voltage. The number tracks the plant state — which loads run, which indicators are lit. That sensitivity is the tell: a real feed into a coil holds its voltage no matter what else starts, while a ground-referenced number that follows the load map is a divider artifact. The worked example below reproduces both readings from one model.
Why does the reading jump to 131 V the moment the start button is pressed? #
Pressing the start button closes the control loop and rearranges all the capacitive paths, so the meter can read above nominal: a 131 V reading to ground on a 120 V control circuit is the floating secondary's coupling seen through the closed coil loop, not an overvoltage fault.
The closed loop connects the coil lead from X2 through the stop contact, the start contact and the coil toward XF, so the meter now looks into the connected winding plus every suppression component wired around it. A floating winding has no fixed common-mode point: its potential to earth settles wherever the whole capacitance network puts it, and that network includes coupling driven from the primary side, so the settling point can sit above the winding's own nominal — 131 V on a 120 V circuit with nothing stressed. The coil still sees only the differential voltage across itself. If the meter across the coil shows full nominal with the motor stopped, that is different: a real unintended feed is reaching the coil, and tracing it is the job, not explaining it.
How do you prove ghost voltage and not a live coil? #
Two differential measurements decide it: meter directly across the coil and directly across the transformer's X2 and XF terminals — about 0 V across the coil while stopped and a steady nominal secondary voltage across X2-XF prove the transformer and coil are healthy and the ground-referenced numbers are coupling.
These checks are energized measurements: run them as a qualified person with a meter and leads rated for the voltage, and de-energize and verify absence of voltage before any terminal you open or touch, as NFPA 70E, 2024 edition, requires — a ground-referenced reading is never proof that a conductor is dead.
- Across the coil, motor stopped. Expect about 0 V. Full nominal here with no start command is a real unintended feed — a welded contact or a jumpered branch — a wiring fault to trace, not ghost voltage. If the coil shows real voltage across itself and still will not pull in, the fault is the holding circuit, the subject of why a starter coil has voltage but won't pull in.
- Across X2 and XF at the transformer. Expect the steady nominal secondary voltage through every start and stop, independent of which loads run. A reading that sags here as loads start is real regulation trouble — transformer size, primary terminations or primary tap — and has nothing to do with the reference.
- Each secondary terminal to earth. Both numbers wandering with the running loads means the secondary carries no bond. Note what the schematic calls for before calling it a fault.
- Low-impedance confirmation. Repeat the stopped-lead reading on a solenoid-type tester or on the meter's low-impedance mode. A coupled point collapses toward zero under that load; a real feed holds its voltage. That comparison separates ghost voltage from a live conductor without any arithmetic.
Example: what does a 10 MΩ meter read on a floating 120 V secondary at 60 Hz? #
On these assumptions the meter reads 42 V on the stopped lead and 76 V once the other loads are running, because the coupling reactance falls from 18.6 MΩ to 5.79 MΩ and the 10 MΩ input claims a bigger share of the 120 V winding.
Model the floating secondary as its 120 V winding behind one series coupling capacitance C, feeding the meter's 10 MΩ input at 60 Hz. The capacitance values are illustrative, chosen to reproduce the reported readings; stray coupling in small control transformers lands anywhere from tens of picofarads to roughly a nanofarad, and the conclusion does not depend on which value you pick.
- Stopped. C = 143 pF. Coupling reactance X_C = 1/(2πfC) = 1/(2π × 60 Hz × 143 pF) = 18.6 MΩ. Meter and coupling form a series divider across the winding: V_meter = 120 V × 10 MΩ / (10 MΩ + 18.6 MΩ) = 42 V — the stopped reading, explained.
- Loads running. Snubber and indicator capacitance in parallel raise the effective coupling to 458 pF. X_C = 1/(2π × 60 Hz × 458 pF) = 5.79 MΩ, so V_meter = 120 V × 10 MΩ / (10 MΩ + 5.79 MΩ) = 76 V — the drift, explained.
- Current behind the reading. I = 42 V / 10 MΩ = 4.2 µA. A control coil draws tenths of an ampere to pull in; microamps move nothing, heat nothing and trip nothing.
- Low-impedance test. Same point, 3 kΩ tester input: V = 120 V × 3 kΩ / (3 kΩ + 18.6 MΩ) ≈ 0.02 V. The coupling collapses, which is what the low-impedance check in the measurement list exploits.
One point, three readings: the number belongs to the divider network, and only the differential measurements describe the circuit.
Should the control transformer secondary be bonded to ground? #
The schematic decides: if the drawing bonds X2 or XF to enclosure ground, restore the open bond; if the machine was built floating, the wandering readings are normal coupling and the bond must not be invented.
To the question the measurements raise — should X2 and XF both show potential to ground — at most one should: a bonded conductor reads near zero to earth and its partner holds steady nominal, while two wandering numbers mean no working bond, which is either the design or the fault, and only the drawing separates them.
NFPA 70, the National Electrical Code, 2023 edition, Article 250 is the rulebook for which secondaries must be grounded: systems under 50 V are grounded only when the conditions of 250.20(B) apply — among them a transformer supply circuit above 150 V to ground — and systems between 50 V and 150 V are grounded when the listed conditions of 250.21 apply. The 208 V phase-to-phase primary on this machine sits below that 150 V-to-ground threshold, so no clause in Article 250 forces a bond by itself; NFPA 79, the Electrical Standard for Industrial Machinery, 2024 edition, covers how machine control circuits and their transformers are built, and the machine drawing is the authority on whether X2 or XF is the grounded conductor. Requirements differ by country, edition and local amendment, so confirm the grounding requirement with the local authority having jurisdiction and the machine documentation.
Builders bond a secondary conductor for a reason: a referenced control circuit holds every conductor at a predictable potential, so the first accidental ground fault either blows the secondary fuse or announces itself, instead of leaving the circuit drifting at unknown potential. Machine builders choose the arrangement deliberately — the same decision runs through MCC control power, covered in grounded or floating control power transformer secondaries in MCCs. A deliberately floating circuit carries its own signature: the to-ground numbers wander until one conductor faults to the enclosure, then the faulted side sits near zero, its partner near full nominal, and the machine keeps running — steadiness there is the first fault, not a repair.
What fixes each reading for good? #
Nothing in the coil circuit needs replacing when the differential readings are healthy: restore the designed bond if the drawing shows one, fuse both secondary conductors as the drawing shows if it floats, and leave the drifting ground-referenced numbers alone — they disappear once the secondary has its reference.
The differential measurements sort every case in this article into one repair:
- Healthy differential, drifting ground numbers — steady nominal across X2 and XF, about 0 V across the coil while stopped: the transformer, coil and control path are good, and the only repair is the reference the drawing calls for.
- Bonded by drawing, readings wander — the designed bond is open: find the loose lug at the transformer, the broken grounding conductor or the missing jumper at the ground bus, and restore the bond at the drawn termination point.
- Floating by drawing — nothing to fix; keep both secondary conductors fused as the drawing shows, and read a sudden steadiness in the to-ground numbers as the first ground fault, not as improvement.
- X2-XF sags as loads start — real regulation, not reference: check the transformer rating against the connected control load, the primary tap and the primary terminations; heat-marked incoming terminals belong to this repair, not to the ghost readings.
- Nominal across the coil with no start command — an unintended closed path, such as a welded contact, a stuck overload trip contact (95–96) or a jumpered branch from another head's seal-in circuit: trace it on the schematic and clear it before trusting the circuit again.
Ghost voltage needs no repair; a missing reference does. The differential meters and the drawing tell you which one is in your cabinet.
Questions asked
Can that coupled voltage on a control wire give you a shock?
Not in any way you can feel. The coupling sits behind megohms of source impedance, so the deliverable current is a few microamps, far below perception and far below what a coil needs. The shock hazard in that cabinet is the genuinely live conductors beside the control wiring, which is why absence of voltage gets verified with a proven tester before anything is touched.
Does a floating secondary mean the control transformer is failing?
No. The transformer's job is the voltage between X2 and XF, and if that differential reading holds steady at the nominal secondary voltage through every start and stop, the winding is doing its work. Only a sag across X2 and XF when loads start points at the transformer itself — an undersized rating, a loose primary termination or the wrong primary tap — and that is a power problem, not a grounding one.
Does it matter whether X2 or XF is the grounded conductor?
Yes, and the drawing names it. Practice is to bond the conductor that stays unswitched and keep all contacts and fuses in the ungrounded conductor, so a single ground fault goes to the fuse instead of energizing a stopped coil. Bonding the switched side lets one fault to the enclosure act like a pressed start button. Restore the bond where the drawing puts it, not by habit.
Which tester shows ghost voltage for what it is?
A tester with a low-impedance input: a solenoid-type voltage tester or a digital multimeter switched to its low-impedance mode. Where a 10 MΩ meter lets the coupled voltage stand, the low-impedance input loads the same point down to nearly zero because the coupled source cannot deliver more than microamps. If a reading survives the low-impedance test near its original value, the source is real and the circuit needs a trace, not an explanation.