Does a two-speed motor's low speed have half the horsepower

Motors and motor starters Published 5 min read By Current Intel engineering team

Short answer

A two-speed motor's low speed has half the horsepower only when the winding is rated for about the same shaft torque at both speeds. The nameplate output at each speed decides; a rated-current cross-check separates constant-torque from constant-horsepower windings.

On this page
  1. Pole count sets the speed, not the horsepower
  2. Three winding characteristics, three different answers
  3. Working a 2.5 hp at 860 r/min and 5 hp at 1750 r/min nameplate
  4. The rated-current cross-check
  5. What to do with your motor
  6. Questions asked

Sometimes. Pole count fixes the speed; the winding's rated torque fixes the horsepower. Low speed is half the high-speed horsepower only when the winding is rated for about the same shaft torque at both speeds, which is the constant-torque case and the most common one on machine tools. On a constant-horsepower winding the two ratings are nearly equal, and on a fan or pump duty the low-speed rating can fall well below half. The deciding quantity is the manufacturer's rated output printed for each speed, and the nameplate currents give you a quick cross-check before you trust either number.

Pole count sets the speed, not the horsepower #

Synchronous speed comes from the supply frequency and the pole count: divide 120 times the frequency in hertz by the number of poles. On a 60 Hz supply that is 1800 r/min synchronous for four poles and 900 r/min for eight, and the loaded shaft runs below each of those figures by the slip needed to produce torque, so use the nameplate shaft speeds, not the synchronous ones, for any output calculation.

Mechanical power is torque times rotational speed. Pole count therefore fixes only one factor of the product. The other factor, the torque the winding may carry continuously, comes from the electromagnetic design, the current the conductors can carry, and the cooling available at that speed. There is no horsepower formula that is a function of poles alone, which is exactly why the electrical books you checked came up empty.

Three winding characteristics, three different answers #

Compare the low-speed rating against the high-speed rating at approximately half speed:

Winding characteristic Low-speed torque Low-speed horsepower Typical duty
Constant torque About equal About one-half Machine tools, conveyors; the usual result when one winding is reconnected to double the poles
Constant horsepower About twice About equal Applications needing high torque at reduced speed
Variable torque Falls with speed, roughly with the square for fans Well under one-half Fans and centrifugal pumps

When the lower speed uses the entire winding reconnected for twice the poles, most such pole-change windings are rated constant torque, so half the horsepower is a reasonable first expectation. Reasonable is not verified: the nameplate or the manufacturer's rating table settles it. Winding construction alone does not prove the output ratio, because separate-winding motors exist with ratings chosen almost independently for the two speeds.

Working a 2.5 hp at 860 r/min and 5 hp at 1750 r/min nameplate #

This is an illustrative nameplate, not a measured motor: a two-speed, three-phase motor on a 60 Hz supply, with 5 hp at 1750 r/min on the high-speed connection and 2.5 hp at 860 r/min on the low-speed connection, both connections at the same rated voltage.

The rule in words: power equals torque times speed, so with the speed ratio known, the torque ratio equals the power ratio multiplied by the speed ratio inverted. In symbols, taking low speed as subscript l and high speed as h:

T_l / T_h = (P_l / P_h) x (n_h / n_l)

The arithmetic:

  • Power ratio: P_l / P_h = 2.5 hp / 5 hp = 0.5
  • Speed ratio: n_h / n_l = 1750 r/min / 860 r/min = 2.03
  • Torque ratio: T_l / T_h = 0.5 x 2.03 = 1.02

The result: the low-speed connection is rated for about 2 percent more shaft torque than the high-speed connection. A torque ratio within a few percent of 1.0 classifies the winding as constant torque, so on this example nameplate the low speed genuinely is half the horsepower. Had the power ratio come out near 1.0, the same arithmetic would have given a torque ratio near 2.0 and classified the winding as constant horsepower. This classification is an estimate built on nameplate values; check it against the manufacturer's rating data before you load the machine to the limit at either speed.

The rated-current cross-check #

When the nameplate gives a current rating for each speed, the ratio between them hints at the characteristic. A low-speed rated current roughly equal to, or up to about 30 percent above, the high-speed value points to a constant-torque winding and a half-power low-speed rating. A low-speed rated current around 2.5 times the high-speed value points to a constant-horsepower winding. Treat these as screening clues, never as acceptance criteria: each current belongs with its own speed's voltage and connection, and the winding's efficiency and power factor can differ between connections.

Read the current correctly before comparing it, because motor nameplate current is line current, not winding current, and a reconnect that changes the connection geometry changes what the line sees.

What to do with your motor #

Work the decision in this order:

  1. Record both nameplate operating points: output, shaft speed, voltage, connection, and rated current, keeping each speed's values together.
  2. If both outputs are given, divide low by high and multiply by the inverted speed ratio as in the worked example. A torque ratio near 1.0 is a constant-torque winding and the low speed is half the horsepower; near 2.0 it is constant horsepower and the two ratings are close to equal; well under 0.5 it is a variable-torque duty such as a fan.
  3. If the nameplate gives only one output, do not assume half. Get the rating for the second connection from the motor manufacturer, and use the current ratio only as a preliminary clue.
  4. Match the load to the classified rating: on a constant-torque winding the driven machine must not need more torque at low speed than the rating provides, and on a fan or pump duty check the motor rating against the load's own speed-torque curve rather than assuming any ratio.
  5. Set overload protection from each connection's own rated current, per the manufacturer's instructions for the wiring arrangement, so neither speed runs unprotected.

If the low-speed connection runs unloaded but overheats, stalls under load, or pulls far above its rated current, the fault lies in the load, the connection, the supply, or the cooling rather than in the horsepower ratio; that investigation follows the same path as any low-speed failure on a two-speed motor. Before you open the motor's terminal box to check jumpers or the connection diagram, de-energize, lock out, and test for absence of voltage as NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, requires for the approach you use, and confirm both the procedure and the ratings with your authority having jurisdiction and the manufacturer's documentation.

Questions asked

The nameplate lists one horsepower and two speeds. What is the low-speed rating?

That nameplate does not define it. A single output figure with two speed entries leaves the low-speed rating open, and the current cross-check can hint at the characteristic but cannot confirm it. Get the winding's rating data for both connections from the motor manufacturer before loading the low speed or setting overload protection for it.

Does a constant-horsepower two-speed motor really make twice the torque at low speed?

At approximately half the speed, delivering the same shaft power requires about twice the shaft torque, so the low-speed connection of a constant-horsepower winding is rated for roughly double the torque of the high-speed connection. It also draws correspondingly more line current at its rating, which is why the current-ratio cross-check points the other way.

Can I replace a two-speed winding with a drive running at two frequencies?

Not as a like-for-like swap. A pole-changing winding is built for its two discrete pole counts, and self-cooled motors lose shaft-driven ventilation as speed falls, so the permitted continuous torque at the lower frequency is its own rating question. Treat that as a drive-and-motor sizing job with both manufacturers' documentation, not a reconnect of the existing winding.

Which speed should the overload relay be set from?

Both, separately. Each connection has its own rated current, and an overload setting taken from the high-speed rating can leave the low-speed connection under-protected, while the reverse can nuisance-trip the high speed. Where the controller has one overload device for both connections, set it per the motor manufacturer's instruction for that wiring arrangement.

Keep reading

  • How-to

    Why a stored vintage motor needs megger and winding tests before a VFD

    Yes, and before any drive is bought; a motor stored for twenty years needs a 500 V DC insulation test and three lead-to-lead resistance readings. The pass marks are 1.22 MΩ minimum for a 220 V winding per IEEE 43-2013, a polarization index of 2.0, and phase resistances within 5 percent. Pass, and either a 1 hp single-phase-input drive or the 5 hp rotary converter runs it; fail, and the motor is replaced, not repaired.

    Motors and motor starters

  • Explainer

    What changes when a motor is rewound from 220 V to 575 V

    A 220 V to 575 V rewind multiplies the stator turns by about 2.61, so horsepower, torque and speed hold while full-load current falls to 0.383 of the old nameplate reading. Locked-rotor current drops by the same factor, winding resistance climbs by roughly the turns ratio squared, and heat, efficiency and reliability ride on the copper fill the shop puts back in the slots.

    Motors and motor starters

  • Explainer

    Why a 415 V delta motor cannot run on 240 V

    A plate that reads 415 V delta, with no second voltage-connection pair, describes single-voltage windings that need 415 V across each coil. On a 240 V supply the motor reaches about one third of rated torque in delta and about one ninth in star, so it will not serve as a full-rated rotary phase converter idler. Replace it with a motor whose plate reads 240 V delta or feed it through a step-up transformer.