How-to
Why a stored vintage motor needs megger and winding tests before a VFD
Short answer
Yes, and before any drive is bought; a motor stored for twenty years needs a 500 V DC insulation test and three lead-to-lead resistance readings. The pass marks are 1.22 MΩ minimum for a 220 V winding per IEEE 43-2013, a polarization index of 2.0, and phase resistances within 5 percent. Pass, and either a 1 hp single-phase-input drive or the 5 hp rotary converter runs it; fail, and the motor is replaced, not repaired.
On this page
- Can I test a stored motor before buying a VFD?
- How do I isolate the motor before opening anything?
- What is the test procedure, step by step?
- What should the three lead-to-lead resistance readings be?
- What megger reading passes a motor wired for 220 V?
- What polarization index does a 1950s winding need?
- Will VFD PWM spikes damage a 1950s winding?
- Which supply should I pick: the drive or the free converter?
- What is the final go/no-go call?
- Questions asked
Test it first; the drive can wait. A motor stored for twenty years is judged in one afternoon with a DC insulation tester and a multimeter, before any supply is bought. The pass marks: a 60-second insulation resistance of at least 1 MΩ plus 1 MΩ per kV of rated voltage per IEEE 43-2013, a polarization index of 2.0 or better, and three lead-to-lead resistances within 5 percent of each other. Pass them and either supply works — a drive sized one rating up for single-phase input, or the 5 hp rotary converter already in hand, which is not too big for a half-horsepower lathe. The procedure starts with the motor locked out and verified dead. For machines already wired into plant gear, insulation resistance testing from switchgear versus motor terminals includes more than the winding; this is the standalone go/no-go check.
Can I test a stored motor before buying a VFD? #
Yes, and nothing about the drive choice matters until you do: one afternoon with a 500 V DC insulation tester and a digital multimeter tells you whether a motor stored for twenty years runs again or gets replaced. Two instruments decide it — the DC insulation tester, the meter everyone calls a megger, for the winding-to-frame picture, and the multimeter for the three winding resistances; everything else (drive size, converter, reactor, cable) is downstream of those readings. This guide carries one example machine throughout: a 1950s dual-voltage 60 Hz machine-tool motor of half a horsepower, wired for the 220 V connection, nameplate current near 1.8 A. If a reading fails, no drive gets bought; if all pass, the last sections spend the budget on the right box.
How do I isolate the motor before opening anything? #
Lock it out before you touch it: open and lock the disconnecting means, prove absence of voltage at the terminal box with a rated meter, and only then lift the cover and the leads — the sequence NFPA 70E, 2024 edition, sets for an electrically safe work condition. NFPA 70E covers workplace electrical safety in the United States; its test-before-touch step uses an instrument rated for the voltage class, proven on a known live source before and after. Confirm the sequence against your site's electrical safety program, the equipment documentation and the authority having jurisdiction. With the box dead, lift the motor leads off the starter or drive terminals so the tests see the winding alone, and clip the tester's ground lead to bare frame metal. Treat the tester leads as live whenever it is cranking, and discharge the winding after every measurement before touching a terminal.
What is the test procedure, step by step? #
Six steps in order, about an hour plus the ten-minute polarization wait: inspect, turn the shaft, measure the three lead-to-lead resistances, insulation-test the winding to the frame, run the polarization index, then finish with a short no-load run.
- Inspect. Pull the terminal-box cover and, if the end bells come off easily, look inside: dark or brittle varnish, moisture beads, rodent nests, cracked lugs. A burnt smell ends the evaluation — send it to a shop.
- Turn the shaft by hand. It should spin smoothly with only bearing drag; grinding or rubbing means bearing work before winding work.
- Measure DC resistance lead to lead — T1 to T2, T2 to T3, T1 to T3 — with one meter on one range, after shorting the meter's own leads to note their resistance. The balance limit is in the next section.
- Tie all three leads together and insulation-test the group against a clean bare spot on the frame for a full 60 seconds. Record the value, then discharge.
- Extend the same test to ten minutes and divide the ten-minute reading by the 60-second one — that ratio is the polarization index.
- Only if steps 3 to 5 pass, reconnect and run unloaded on a known-good three-phase supply or the converter for ten to fifteen minutes; the no-load current should sit near 30 to 60 percent of the nameplate full-load amps, even across phases, with no growl.
What should the three lead-to-lead resistance readings be? #
The three readings must match: hold the spread — highest minus lowest — within 5 percent of their average for a healthy stator, treat anything past 10 percent as a failed winding, and read an open circuit as exactly that. Expected magnitude, for the example machine: stator copper loss at full load runs roughly 60 W, about an eighth of a 500 W input, so 60 W ÷ (3 × 1.8 A × 1.8 A) ≈ 6.2 Ω per phase; each lead-to-lead reading spans two phases, so about 12 Ω is typical, and anything from a few ohms to a few tens of ohms is plausible for small motors. The absolute value is a sanity check only — the spread decides. A reading near zero while the others show ohms is a shorted section, not a meter error: remeasure once, then condemn it.
What megger reading passes a motor wired for 220 V? #
The documented floor is 1.22 MΩ: IEEE 43-2013 sets the minimum 60-second insulation resistance at 1 MΩ plus 1 MΩ per kV of rated voltage, and a 220 V winding gives 1 + 0.22 = 1.22 MΩ, referenced to a 40 °C winding. IEEE 43 is the recommended practice for insulation-resistance testing of rotating machinery — it prescribes the method and the minimum acceptable values for AC and DC windings, assigning a 500 V DC test to windings rated 600 V and below. Its formal scope starts at machines rated 750 W, so a half-horsepower motor sits under it; shops apply the same numbers to small machines anyway, because no weaker floor is defensible. As a working rule the reading halves for every 10 °C the winding is warmer, so compare retests at like temperatures. Decision bands on top of the floor:
| One-minute reading | Verdict |
|---|---|
| 100 MΩ or more | Go — run it on either supply |
| 10 to 100 MΩ | Conditional go — clean and dry it first; drive only behind a load reactor |
| Under 10 MΩ | Dry it, retest once; still under 10 MΩ or below the floor means replace the motor |
Wire the machine for its 440 V connection instead and the same formula puts the floor at 1.44 MΩ.
What polarization index does a 1950s winding need? #
A ratio of at least 2.0: the polarization index is the ten-minute insulation resistance divided by the 60-second value, and IEEE 43-2013 keeps 2.0 as the minimum for the older insulation classes in a pre-1960 machine. The ratio works because clean, dry winding insulation keeps absorbing charge for minutes, so the reading climbs; moisture and contamination conduct steadily and flatten the curve toward 1. Decide: 2.0 and above passes; 1.5 to 2.0 is a damp winding — dry at 60 to 80 °C for 24 to 48 hours with warm air or a heat lamp in a tented enclosure, then retest; below 1.5, replace the motor unless one drying cycle lifts it into the passing band. One exception covers many good old machines: when the one-minute reading already sits in the hundreds of megohms, there is little left to climb and the ratio trends toward 1 — there the raw reading decides, and a high flat reading is still a pass.
Will VFD PWM spikes damage a 1950s winding? #
More than a converter would: the machine predates the inverter-duty construction NEMA MG 1 Part 31 defines, so its enamel was never pulse-tested, and the drive is the harsher of your two supplies. ANSI/NEMA MG 1-2016, Part 31 covers definite-purpose inverter-fed motors — spike-resistant magnet wire and windings proven on PWM; a 1952 machine has Class A or Class B insulation, rated 105 °C or 130 °C, with no pulse rating at all. The threat in numbers, as an illustrative calculation: a drive on a 230 V supply holds about 325 V on its DC bus (230 × 1.41), and on long motor leads the reflected wave at the terminals can approach twice that, near 650 V, rising in roughly a tenth of a microsecond — on the order of 6500 V/µs (650 ÷ 0.1) applied to enamel that never saw such fronts. A rotary converter's output is close to a sine wave and delivers none of it. So if the drive wins, keep the motor cable short and put a load reactor or dV/dt filter on long runs — choosing a line reactor or a motor reactor for a VFD settles where that filter goes — then run the first week lightly and re-megger; insulation that survives the early pulses tends to keep surviving.
Which supply should I pick: the drive or the free converter? #
If you want variable speed, a drive rated for single-phase input at 1 hp with at least 5 A of output current is the pick: the motor's 1.8 A nameplate current then carries nearly three times headroom against the derating single-phase input demands. Why one rating up: on single-phase input only two rectifier legs feed the DC bus, so the input stage and capacitors run hotter and the same frame is derated — the common instruction is the next rating up, and the full procedure is in sizing a VFD for a three-phase motor on single-phase input. Program the drive with the nameplate data for the low-voltage connection and start unloaded. The converter side needs no purchase: an idler draws its own no-load losses plus real power in proportion to load, so the 5 hp idler feeding a half-horsepower lathe runs light, and the oversizing actually improves balance on the manufactured leg. Rule: speed control decides for the drive; the gentlest supply and zero new hardware decide for the converter. If the supply itself is the constraint, running a three-phase motor on single-phase 208 V lays out the remaining options.
What is the final go/no-go call? #
Commit like this: a resistance spread within 5 percent, insulation resistance at or above 100 MΩ and a polarization index at or above 2.0 mean run it on either supply; a reading below the floor after one drying cycle means replace it. Worked example, illustrative readings on the example motor at a 20 °C shop temperature: lead-to-lead 12.4 Ω, 12.1 Ω and 11.9 Ω, so the average is (12.4 + 12.1 + 11.9) ÷ 3 = 36.4 ÷ 3 = 12.13 Ω and the spread is (12.4 − 11.9) ÷ 12.13 = 0.5 ÷ 12.13 ≈ 4.1 percent — inside the limit. Insulation: 250 MΩ at one minute and 600 MΩ at ten, so the index is 600 ÷ 250 = 2.4, and the one-minute value sits about 200 times the floor (250 ÷ 1.22 ≈ 205). Supply: a 1 hp single-phase-input drive rated 5 A against the 1.8 A nameplate gives 5 ÷ 1.8 ≈ 2.8, ample for the single-phase derating. Verdict: keep the 1952 motor; drive for speed control, converter for sine power.
The decision for every other case:
- Spread past 10 percent, an open lead, or a shorted section: replace — a rewind of a half-horsepower stator almost never pays against a new motor.
- Clean resistances, insulation 10 to 100 MΩ, index at or above the mark: run it after a cleaning and a warm-air dry; drive only behind a load reactor.
- Insulation under 10 MΩ or index between 1.5 and 2.0: one drying cycle at 60 to 80 °C for 24 to 48 hours, then retest; recovered into the passing bands means run it, anything less means replace it.
- Green numbers but a no-load run that growls, heats unevenly or pulls well over the usual band: get a surge test before trusting it.
That is the whole decision: one afternoon of numbers first, and only then the drive or the converter.
Questions asked
Can I run the insulation test through the drive without disconnecting?
No. Lift the motor leads first: the tester's DC output charges the winding and feeds back into the drive's output stage and DC-bus capacitors, and any reading taken through the drive is meaningless. Test the motor alone, then test the motor cable separately with both ends lifted. Reconnect only after the winding is discharged and verified.
How long should I discharge the winding after a megger test?
For at least as long as the test voltage was applied — several minutes after a ten-minute polarization run — then prove it. Let the tester's discharge function bleed the charge, or short the tested leads to the frame through a power resistor. Touch nothing until a voltmeter reads effectively zero between winding and frame; a charged winding stores energy like a capacitor and bites.
Will these tests find a shorted turn?
Usually not, and that is the gap to know about. One shorted turn changes lead-to-lead resistance too little for a handheld meter to resolve and barely dents an insulation reading. A motor shop's surge comparison test finds it. Suspect shorted turns when the no-load current runs well past its usual fraction of full load, the three phase amps sit visibly unbalanced, or the machine growls without heating — get the surge test before spending on a drive.
Does a 500 V megger test stress an old winding?
No — it sits far below what the winding once passed. Under NEMA MG 1, a new winding is proof-tested for one minute at twice rated voltage plus 1000 V, about 1440 V for a 220 V machine, so a one-minute 500 V DC test leaves margin even on aged enamel. What damages windings is testing damp insulation at a higher range to force a number; stay at 500 V and let a low reading mean what it means.