Explainer
Estimating rotor inertia WK2 for a 25 hp 1750 rpm motor
Short answer
A 25 hp, 1750 rpm motor is a 4-pole machine, and the NEMA MG-1 estimating relation gives WK2 = 0.02 × 2^(p/2) × hp^(1.35 - 0.05p/2) = 4.47 lb·ft², or 0.188 kg·m². Published 25 hp 4-pole rotors run from about 4.0 to 5.7 lb·ft², so treat the estimate as a planning figure. Use it for first-pass sizing; take the datasheet value when the result is marginal or the rotor term dominates.

On this page
You do not need a test stand or a teardown to put a number on the rotor of a 25 hp, 1750 rpm motor. Count the poles from the nameplate speed, run the estimating relation quoted with NEMA MG-1, and the answer is WK2 = 4.47 lb·ft², which is 0.188 kg·m² in the units most drive sizing tools want. Published datasheets for 25 hp four-pole machines land anywhere from about 4.0 to 5.7 lb·ft², so the formula result is a planning figure with a spread of roughly -10% to +30% across designs, not a measurement. This article runs the estimate, the catalog cross-check, the unit conversion and the decision points where the difference actually matters. If the motor is in front of you and you plan to open its terminal box to confirm the connection, de-energize, lock out and test for absence of voltage first; everything after that step is desk work.
Two nameplate entries feed the estimate #
Only horsepower and pole count enter the relation. A nameplate speed of 1750 rpm at 60 Hz sits just under 1800 rpm, the synchronous speed for four poles (Ns = 120 × f / p = 120 × 60 / 4 = 1800 rpm), so this is a 4-pole machine running about 2.8% slip at full load. The 575 V rating, the 284T frame and the severe-duty build do not change the estimate; they describe winding and enclosure design, not the basis of the rotor value.
WK2 is the rotor weight times the square of its radius of gyration, and it is the same physical quantity as the moment of inertia J, only in different units. Fix the unit before comparing any two values, because this figure arrives as lb·ft², kg·m² or, on some US datasheets, lb·in².
The estimating relation, with the arithmetic #
The estimating relation long associated with NEMA MG-1, the NEMA standard for motors and generators, gives a typical rotor WK2 for a polyphase induction motor from its horsepower and pole count:
WK2 = 0.02 × 2^(p/2) × hp^(1.35 - 0.05 × p/2), with WK2 in lb·ft² and hp in horsepower.
For this motor, p = 4 and hp = 25:
- 2^(4/2) = 4, and 0.02 × 4 = 0.08
- the exponent is the whole bracket: 1.35 - 0.05 × (4/2) = 1.35 - 0.10 = 1.25
- 25^1.25 = 55.9
- WK2 = 0.08 × 55.9 = 4.47 lb·ft²
A hand result near 0.5 or near 45 means the bracket was mis-grouped or the poles/2 term was dropped; the full 1.25 applies to the horsepower. The relation returns a typical value for the rating — it does not know the rotor bar shape, the shaft or the fan — so treat the result as an estimate to be confirmed against the equipment documentation for the specific machine.
What published catalog values show #
Published rotor values for this rating spread wider than most engineers expect, which is why the estimate needs a cross-check before it goes into a sizing run:
| Value source, 25 hp 4-pole | WK2 (lb·ft²) | J (kg·m²) |
|---|---|---|
| MG-1 estimating relation | 4.47 | 0.188 |
| Catalog average, standard-duty designs | about 4.0 | about 0.169 |
| Severe-duty datasheet, one manufacturer | 5.7 | 0.240 |
The catalog average sits about 10% under the formula result and the severe-duty datasheet about 28% over it, and both are documented machines in this rating. Any value in that band is plausible for the rating; what disqualifies the estimate is not the spread itself but a calculation that flips from pass to fail inside the band. That flip is the tripwire for going to the datasheet, in the final section below.
Convert WK2 to J for the sizing tool #
Most drive and servo sizing tools take the moment of inertia in kg·m². The conversion is exact:
J (kg·m²) = WK2 (lb·ft²) × 0.04214
For the formula estimate: 4.47 × 0.04214 = 0.188 kg·m². For the catalog average: 4.0 × 0.04214 = 0.169 kg·m². Enter the number with its unit stated, and mark the source — MG-1 estimate, catalog average or datasheet — beside it in the calculation record, because the source is what tells you how far to trust the result when the sizing run comes back marginal.
Where the rotor number moves the answer #
Three calculations take the rotor value directly:
Acceleration time. t = (Jrotor + Jload) × Δω / Taccel, with speed in rad/s equal to rpm × 2π / 60; at 1750 rpm that is 183.3 rad/s. The starting-time method itself, with torque margin and the reflected load term, is laid out in Motor starting time calculation: torque margin and inertia — there the inertia is an input, and obtaining a defensible value for it is this article's subject.
Stored rotor energy. E = 0.5 × J × ω². With the converted estimate and 183.3 rad/s: E = 0.5 × 0.188 × 33,599 = 3,158 J, about 3.2 kJ — the figure a dynamic-braking or regen study needs first. How the load side feeds that same study on older machines is covered in a guide to estimating machine inertia for electronic braking.
Load-to-motor inertia ratio. Divide the load inertia referred to the motor shaft by the rotor value. A ratio of several to one makes the rotor uncertainty almost irrelevant; a ratio near one makes it the dominant error. For the load term on a pump, guide to estimating pump inertia for motor starting pairs with this estimate.
A high ratio also stretches acceleration into the overload relay's trip band; the trip-class settings for long starts are covered in Setting overload relays for high-inertia motor starts.
The decision, case by case #
- Load inertia several times the rotor value — most pumps and fans through a coupling: the spread on the rotor term moves the total by a few percent at most. Run the sizing with the formula value and move on.
- Result marginal, or load inertia comparable to the rotor — close-coupled pumps, light couplings, machines with little flywheel effect: the rotor term carries the result. Pull the datasheet value for the catalog number on the nameplate before committing.
- Different brand or a severe-duty replacement: datasheet value, without substitution, because rotor and fan construction differ between designs — the band above is the proof that the difference is real.
On the datasheet, look for the field printed as WK2, WR2, rotor inertia or moment of inertia, and read the unit printed beside it before the value enters any calculation. Whichever branch you take, record the source with the number and re-run the sizing at both ends of the band; if pass or fail holds at both ends, the estimate was good enough.
Questions asked
Can the drive measure the rotor inertia instead of my estimating it?
Often, yes. Many servo drives and some closed-loop vector drives include a commissioning routine that accelerates the motor with a known torque command and back-calculates the rotor inertia from the measured current; the drive manual names the routine for that model. Run it only with the driven machine safe to rotate and guards in place, and treat the identified value as a confirmation of the datasheet number rather than a replacement for it.
The datasheet lists the cooling fan inertia separately, do I add it?
Add it only when the fan is shaft-mounted and turns with the rotor, which the datasheet notes should say. A separately driven fan or one mounted at the brake end does not add rotating mass to the motor shaft. When you do add terms, add them in one unit system first and convert the total once, so a rounding error does not hide inside the conversion.
What is the rotor inertia of a 25 hp 2-pole version of the same machine?
Far lower. Published datasheets for 25 hp 2-pole machines list about 1.0 lb·ft², roughly 0.042 kg·m², close to a fifth of the 4-pole figure, because the rotor is long and slim rather than wide. Never carry an estimate across a pole count; the relation and the catalog tables give a different value for every pole number.
The datasheet value is far from my estimate, is something wrong?
Probably not. Published values for this rating run from about 4.0 to 5.7 lb·ft², so a brand-to-brand difference of that size is normal. Two signatures do mean a mistake: a number near 0.19 on a sheet you expected in pound-feet squared is a kg·m² value, and a number near 640 is lb·in². Beyond that, confirm the data row matches the pole count and rating on your nameplate.